Lochinvar 2072, 502 operation manual Checking gas supply pressure, GAS Piping Size Chart

Page 33

3 Gas connections (continued)

Combination gas valve/regulators equipped with integral vent limiters are not required to have vent or relief lines piped to the outdoors. The termination of the vent limited opening on the combination gas valve/regulator complies with the safety code requirements of CSD-1, CF-190(a) as shipped from the appliance manufacturer without the installation of additional vent lines.

Checking gas supply pressure

Use the following procedure to check gas supply pressure.

Installation & Operation Manual

13.Remove the manometer and related fitting from the “inlet” side of the gas valve, replace 1/8" hex plug in gas valve and tighten.

14.Turn on gas supply at the manual valve, turn on L.P. gas at the tank if required.

15.Turn the power switch to the “ON” position.

16.Turn the gas valve knob to the “ON” position.

17.Set the electronic temperature control or thermostat to call for heat.

1.

Turn the main power switch to the “OFF” position.

2.

Turn gas valve knobs to the “OFF” position.

3.

Shut off gas supply at the field-installed manual gas cock in

 

the gas piping to the unit. If fuel supply is L.P. gas, shut off

 

gas supply at the tank.

4.

Remove the 1/8" hex plug, located on the “inlet” side of the

 

gas valve. You may also use a tapping on the field-installed

￿WARNING

After completing any testing on the gas system, leak test all gas connections. Apply a soap/water solution to all gas connections while main burners are operating. Bubbles forming indicate a leak. Repair all leaks at once. Do not operate this unit with a leak in the gas train, valves or related piping.

 

main manual gas cock or gas piping. Install a fitting in the

 

inlet pressure tapping suitable to connect to a manometer

 

or magnehelic gauge. Range of scale should be 14" w.c. or

 

greater to check inlet pressure.

5.

Turn on gas supply at the manual gas cock, turn on L.P. gas

 

at the tank if required.

6.

Turn the power switch to the “ON” position.

7.

Turn the gas valve knobs to the “ON” position. Set the

 

electronic temperature control or thermostat to call for

 

heat.

8.

Observe the gas supply pressure as all burners are firing.

 

Ensure that inlet pressure is within the specified range.

 

See Connecting To Gas Supply, page 31 for minimum and

 

maximum gas supply pressures.

9.

If gas pressure is out of range, contact gas utility, gas

 

supplier, qualified installer or service agency to determine

 

necessary steps to provide proper gas pressure to the

 

control.

10.

If gas supply pressure is within normal range, turn the

 

power switch to the “OFF” position.

11.

Turn gas valve knobs to the “OFF” position.

12.

Shut off gas supply at the manual gas cock in the gas piping

 

to the unit. If fuel supply is L.P. gas, shut off gas supply at

 

the tank.

Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see Burner Flames in the Copper-fin2Service Manual. Turn system off and allow burners to cool, then cycle burners again to ensure proper ignition and flame characteristics.

SUPPLYINLET

INLET

PRESSURE

TAP

GASOUTLET

VALVE

CONTROL

KNOB

Figure 3-3_Measuring Gas Supply Pressure at Combination Gas Valve

TABLE - 3D

GAS PIPING SIZE CHART

Nominal

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

 

Maximum

Iron Pipe

 

 

 

 

 

 

 

 

 

Capacity of Pipe

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in Thousands of

10

20

30

40

50

60

70

80

90

100

125

150

175

200

Inches

Btu/hr per hour

3/4

369

256

205

174

155

141

128

121

113

106

95

86

79

74

for gas pressures

of 14 Inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

697

477

384

328

292

267

246

256

210

200

179

164

149

138

Water Column

1 1/4

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

(0.5 PSIG) or less

and a pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 1/2

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

drop of 0.5 Inch

24,100 2,820 2,260 1,950 1,720 1,560 1,440 1,330 1,250 1,180 1,100 974 871 820 Water Column (Based on NAT

2 1/2

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

1,900

1,700

1,540

1,400

1,300

GAS, 1025 Btu/hr

3

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

3,300

3,000

2,720

2,500

2,340

per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of Gas and 0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

423,500 16,100 13,100 11,100 10,000 9,000 8,300 7,690 7,380 6,870 6,150 5,640 5,130 4,720 Specific Gravity)

33

Image 33
Contents Save this manual for future reference Installation & Operation Manual Models 502Contents Please read before proceeding Special instructionsRemoval of Combustion Chamber Lining or Base Panels Owner warning Safety informationCopper-fin2- How it works Copper-fin2- How it works Copper-fin2- How it works Ratings SpecificationsLocation of unit Determine unit locationIndoor clearances from combustible construction Freeze protectionLocation Outdoor pool heater installationHydronic systems anti-freeze Combustion and ventilation airMinimum Recommended Combustion AIR Supply to Equipment Room Outside Combustion Air Using Direct VentingCombustion air filter Exhaust fansIdentify your appliance’s vent system VentingCAT IV Flue pipe materials CAT I Negative pressure non-condensingDraft Venting Vent system optionsGeneral information Venting supportBarometric damper location Negative draft Conventional negative draft venting seeFlue outlet piping Common Venting SystemsMasonry chimney installations Vertical vent termination clearances and locationInspection of a masonry chimney 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Combustion air inlet piping Vertical DirectAire venting seeLength of air inlet pipe Sidewall air inletVertical Rooftop Air Inlet Combined air inlet pointsClearances Directaire Kits Model Horizontal KIT Vertical KIT Venting of flue productsSidewall with fan Sidewall venting seeSidewall venting termination Sidewall vent termination clearances and locationSidewall venting without fan Drain tee installationModels 502 Venting of flue products Horizontal DirectAire venting Powered Venting seeDirect venting see Flue outlet pipingVertical DV venting termination Horizontal DV venting termination Masonry chimney installationHorizontal Vent Termination Clearances and Location Combustion air inlet pipingAir inlet piping materials Connecting the air inlet pipe to the unitLength of air inlet pipe Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeVertical and sidewall combustion air inlet Multiple sidewall direct vent installationsHorizontal combustion air inlet clearances Vertical Combustion Air Inlet ClearancesOutdoor installation see Outdoor vent/air inlet locationOutdoor vent cap kit Gas connections Connecting to gas supplyGas connection Gas pressure testCombination gas valves Suggested GAS Pipe Size for Single Unit Installations ModelGas train and controls Venting of combination gas valvesChecking gas supply pressure GAS Piping Size ChartCirculating pump Water connections502 752 Models 992 1442 ModelsInitial set-up of maximum water flow Heat exchangerMinimum Pump Performance Auxiliary Mixed Water Limit Control3Heater Within 15 feet of Pool Piping 6Cascaded Heaters Beyond 15 feet of Pool Piping Pool Return Sensor Location MIN Primary Automatic bypass valve cover installation Pumped Automatic BypassOutdoor operation 3-way valve cover Pump purge delay Water flow switchPump purge pre-running delay Relief valveWay Automatic Bypass Valve Wiring Way automatic bypass valve wiringRemote Wire Connection Electrical connectionsPool heater operating control module Installation must comply withLine voltage connections AMP Draw DataPool return sensor 2-wire Louver proving switchPool supply/limit sensor 4-wire Low voltage connectionsWiring of the cascade Alarm contactsStartup Pre-start checklistStarting the filter system Check for gas leaksCheck vent and air piping Check thermostat circuitsPlacing the pool heater in operation Start the pool heater2Operating Instructions Set clock Configuration of the cascadeGeneral Operating informationPool heater temperature regulation DAY Switching on Sequence CascadeSequence of the cascade Sequence of operation Copper-fin2control module MENU/EXIT Display Screen ENTER/RESET UpdownInstaller Access modesUser To save parameters and exit programmingStatus display screens Sysrtn Open Unit Pump DelaySysrtn Shorted STG DemandMaintenance Maintenance and annual startup Service technicianOwner maintenance Address reported problems MaintenanceInspect appliance area Inspect appliance interiorCheck control settings Check all wiringCheck relief valve Inspect/replace hot surface igniter Ignition system checkoutInspect and clean burner Perform start-up and checks Check burner flameCheck flue gas passageways Oiled bearing circulators Review with ownerDigital Harness Connection diagramController LOW Voltage Ladder diagramRuntime Contacts 2BOARDCONNECTION Outdoor S5SENSOR POOL2ND Page
Related manuals
Manual 44 pages 17.92 Kb Manual 16 pages 36.89 Kb

2072, 502 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.