7 Operating information

The control monitors the temperature difference between the inlet and the outlet sensor. If this difference exceeds the first limit the control will turn off stages. If the temperature difference exceeds a second limit the control will shut the unit down. The unit will restart automatically once the temperature difference has dropped 10°F (6°C) and the minimum off time has expired.

RISE LIMITING

Outlet Temperature

Firing Rate

Up to 180°F (82°C)

Full Fire

180°F (82°C) to 185°F (85°C)

Low Fire

Above 185°F (85°C)

Off

Freeze protection

DO NOT install the appliance in a room likely to freeze.

The following integral feature of the SMART SYSTEM control module provides some protection for the appliance only -- not for the system.

The SMART SYSTEM control module provides freeze-up protection as follows when the appliance water temperature drops below 45°F (7.2°C):

Below 45°F (7.2°C), the appliance and system pumps operate constantly.

Below 37°F (2.7°C), the appliance turns on.

Appliance and pumps turn off if appliance water temperature rises above 45°F (7.2°C).

￿CAUTION This feature of the SMART SYSTEM control module does not eliminate the

possibility of freezing. The installer must still use recognized design, installation and maintenance practice to prevent freeze potential for the appliance and system.

High limit operations

When outlet temperature exceeds 210°F (99°C), high limit action occurs. The appliance shuts down until the outlet water cools down and the RESET button on the Operator Interface is pressed.

Low water cutoff protection

1.The SMART SYSTEM control module uses temperature sensing of both inlet and outlet areas of the heat exchanger. If the flow rate is too low or the outlet temperature too high, the control module modulates and shuts the appliance down. This along with the flow switch, ensures appliance shutdown in the event of low water or low flow conditions.

2.Some codes and jurisdiction may accept these integral features of the control in lieu of requiring an additional limit control or low water cutoff. Consult local jurisdiction to determine. Contact manufacturer for low water cutoff kit availability.

50

Monitor external limits

Connections are provided on the connection board for external limits such as a louver proving switch. The SMART SYSTEM will shut off the burner and inhibit relighting whenever any of these external limits open.

Run-time and alarm outputs

The appliance provides dry contacts for indicating when the appliance is running, and when it is unable to operate.

Run-time and cycle counting

The control uses two timers to monitor the total hours of burner operation. One timer monitors the time the appliance is firing under 50% of rate. The other timer monitors the time the appliance is firing over 50% rate.

The control uses four (4) ignition counters to monitor the amount of appliance cycles. The first counter counts all ignitions of the control. The second counter counts only ignition attempts that have failed. The third and fourth counters are the same as the first and second respectively, but can be reset by the installer.

Service reminder

The control can be programmed for service reminder notification. This notification will become active when either a set time frame has expired, or a set amount of running hours or cycles has expired (all adjustable by the installer). The display will alternate the standard text on the display screen with Service Due every 5 seconds. The service reminder notification can be reset by the installer.

Error logging

The control will hold in memory the last 10 error codes as well as the last 10 turn-off functions. The date and time of the occurrence will be recorded as well. Only the 10 most current occurrences will be held in memory.

Pool heater temperature regulation

Operating temperature (target)

The SMART SYSTEM control module senses water temperature and regulates appliance firing rate to achieve a target temperature. The target temperature can be set between 40°F (4.5°C) and 105°F (40.5°C).

Image 50
Contents Installation & Operation Manual Models 502 Save this manual for future referenceContents Removal of Combustion Chamber Lining or Base Panels Please read before proceedingSpecial instructions Safety information Owner warningCopper-fin2- How it works Copper-fin2- How it works Copper-fin2- How it works Specifications RatingsIndoor clearances from combustible construction Determine unit locationLocation of unit Freeze protectionHydronic systems anti-freeze Outdoor pool heater installationLocation Combustion and ventilation airOutside Combustion Air Using Direct Venting Minimum Recommended Combustion AIR Supply to Equipment RoomExhaust fans Combustion air filterCAT IV Flue pipe materials VentingIdentify your appliance’s vent system CAT I Negative pressure non-condensingVent system options Draft VentingBarometric damper location General informationVenting support Flue outlet piping Conventional negative draft venting seeNegative draft Common Venting SystemsInspection of a masonry chimney Masonry chimney installationsVertical vent termination clearances and location 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Length of air inlet pipe Vertical DirectAire venting seeCombustion air inlet piping Sidewall air inletClearances Vertical Rooftop Air InletCombined air inlet points Venting of flue products Directaire Kits Model Horizontal KIT Vertical KITSidewall venting termination Sidewall venting seeSidewall with fan Sidewall vent termination clearances and locationDrain tee installation Sidewall venting without fanModels 502 Horizontal DirectAire venting Powered Venting see Venting of flue productsVertical DV venting termination Direct venting seeFlue outlet piping Horizontal Vent Termination Clearances and Location Masonry chimney installationHorizontal DV venting termination Combustion air inlet pipingLength of air inlet pipe Connecting the air inlet pipe to the unitAir inlet piping materials Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeHorizontal combustion air inlet clearances Multiple sidewall direct vent installationsVertical and sidewall combustion air inlet Vertical Combustion Air Inlet ClearancesOutdoor vent cap kit Outdoor installation seeOutdoor vent/air inlet location Gas connection Connecting to gas supplyGas connections Gas pressure testGas train and controls Suggested GAS Pipe Size for Single Unit Installations ModelCombination gas valves Venting of combination gas valvesGAS Piping Size Chart Checking gas supply pressure502 752 Models Water connectionsCirculating pump 992 1442 ModelsMinimum Pump Performance Heat exchangerInitial set-up of maximum water flow Auxiliary Mixed Water Limit Control3Heater Within 15 feet of Pool Piping 6Cascaded Heaters Beyond 15 feet of Pool Piping Pool Return Sensor Location MIN Primary Outdoor operation 3-way valve cover Automatic bypass valve cover installationPumped Automatic Bypass Pump purge pre-running delay Water flow switchPump purge delay Relief valveRemote Wire Connection Way automatic bypass valve wiringWay Automatic Bypass Valve Wiring Electrical connectionsLine voltage connections Installation must comply withPool heater operating control module AMP Draw DataPool supply/limit sensor 4-wire Louver proving switchPool return sensor 2-wire Low voltage connectionsAlarm contacts Wiring of the cascadeStarting the filter system Pre-start checklistStartup Check for gas leaksPlacing the pool heater in operation Check thermostat circuitsCheck vent and air piping Start the pool heater2Operating Instructions Configuration of the cascade Set clockOperating information GeneralPool heater temperature regulation Sequence of the cascade DAY Switching on SequenceCascade Sequence of operation MENU/EXIT Display Screen ENTER/RESET Updown Copper-fin2control moduleUser Access modesInstaller To save parameters and exit programmingStatus display screens Sysrtn Shorted Unit Pump DelaySysrtn Open STG DemandOwner maintenance Maintenance Maintenance and annual startupService technician Inspect appliance area MaintenanceAddress reported problems Inspect appliance interiorCheck relief valve Inspect/replace hot surface igniter Check all wiringCheck control settings Ignition system checkoutCheck flue gas passageways Inspect and clean burnerPerform start-up and checks Check burner flame Review with owner Oiled bearing circulatorsConnection diagram Digital HarnessController Ladder diagram LOW VoltageRuntime Contacts 2BOARDCONNECTION Outdoor S5SENSOR POOL2ND Page
Related manuals
Manual 44 pages 17.92 Kb Manual 16 pages 36.89 Kb

2072, 502 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.