Lochinvar 2072, 502 operation manual Copper-fin2- How it works

Page 5

Installation & Operation Manual

The Copper-fin2- How it works...

1.Heat exchanger

The heat exchanger allows system water to flow through specially designed tubes for maximum heat transfer. The glass lined headers and copper fined tubing are encased in a jacket that contains the combustion process.

2.Heat exchanger access cover

The heat exchanger access cover is a galvanized steel door which allows access for service, maintenance, and removal of the heat exchanger from inside the combustion chamber.

3.Blower

The blower pulls in and injects air into the individual burners along with gas from the gas manifold where the mix is burned inside the combustion chamber.

4.Gas valve

The referenced gas valves have a dual purpose; changing the gas supply pressure to manifold pressure, and the reference side of the gas valve is designed to allow chamber pressure to change the volume of gas through the valve. This is not a design to compensate for gas supply pressure issues.

5.Outlet/limit temperature sensor

This 4-wire limit rated sensor monitors the outlet temperature to ensure safe operation. The appliance will adjust its firing rate to maintain water temperatures below the maximum allowable outlet temperature.

6.Inlet temperature sensor

This 2-wire sensor monitors the inlet temperature. The appliance will adjust the position of the 3-way valve to maintain the inlet water temperature above the minimum allowable inlet temperature.

7.Electronic display

The electronic display consists of 6 buttons and a two-line 16-character liquid crystal display used to monitor the operation of the heater as well as enter and view the programming of the main control board.

8.Burner

The burner is a ported stainless steel construction which uses a gas air mix to operate at a fixed input. Banks of burners turn on or off to vary the firing rate.

9.Pool supply/limit sensor (not shown)

This 4-wire limit rated sensor monitors the temperature of the water being supplied to the pool to ensure safe operation. The appliance will shut down if the maximum allowable pool supply temperature is exceeded.

10.Pool return sensor (not shown)

This 2-wire sensor is the controlling sensor and it monitors the temperature of the pool water. The appliance will stage to maintain pool temperature set point and turn off when set point is met.

11.Gas supply pipe

The gas supply pipe on this appliance is 1 1/4 or 2" (depending on model) diameter NPT. Please reference the National Fuel Gas Code charts for connection details.

15.Low voltage connection board

The low voltage connection board provides a location to connect all of the low voltage devices to the appliance. This is where most of the external safety controls are connected.

16.Front doors - upper and lower

The front doors provide access to the gas train as well as the blower, burners and other key components for service and maintenance.

17.Hot surface igniter (HSI)

The hot surface igniter is a device that is used to ignite the air/gas mixture as well as monitor the performance of the flame during operation. This device acts as a flame sense electrode.

18.Flame inspection window (sight glass)

The flame inspection windows, located on either side of the appliance, allow for visual inspection of the burners and flame during operation.

19.Manual reset high limit sensor

This device monitors the outlet water temperature to ensure safe operation. If the temperature exceeds its setting (field adjustable), it will break the control circuit, shutting the appliance down. Manual reset is performed through the display.

20.Relief valve

The relief valve is a safety device that ensures the maximum pressure of the appliance is not exceeded. Pool heaters operate on temperature and pressure and are shipped standard as 150 PSI and 210°F (98.9°C).

21.Power switch

The power switch is used to engage and disengage power to the appliance on the 120 VAC circuit.

22.Air pressure switch

The air pressure switch is a safety device which ensures proper blower operation. The air pressure switch is wired in series with the low voltage control circuit in such a way that if the fan does not engage or shuts down prematurely the device will break the control circuit and the unit will shut down.

23.Flow switch

The flow switch is a safety device that ensures flow through the heat exchanger during operation. This appliance is low mass and should never be operated without flow. The flow switch makes contact when flow is detected and allows the unit to operate. If flow is discontinued during operation for any reason the flow switch will break the control circuit and the unit will shut down.

24.Drain port(s)

Location from which the heat exchanger can be drained. The drain ports are located underneath the front header.

25.Manual shutoff valve (not shown)

Manual valve used to isolate the unit from the gas supply.

12.SMART SYSTEM Control Module

The SMART System Control Module is the main control for the appliance. This module contains the programming that operates the blower, gas valve, and pumps in addition to other programmable features.

13.Air intake

Fresh air for combustion is drawn through a filter provided at the air intake, located at either the rear or right side of the appliance.

14.Line voltage terminal strip

The line voltage terminal strip provides a location to connect all of the line voltage (120 VAC) contact points to the unit.

5

Image 5
Contents Save this manual for future reference Installation & Operation Manual Models 502Contents Removal of Combustion Chamber Lining or Base Panels Please read before proceedingSpecial instructions Owner warning Safety informationCopper-fin2- How it works Copper-fin2- How it works Copper-fin2- How it works Ratings SpecificationsLocation of unit Determine unit locationIndoor clearances from combustible construction Freeze protectionLocation Outdoor pool heater installationHydronic systems anti-freeze Combustion and ventilation airMinimum Recommended Combustion AIR Supply to Equipment Room Outside Combustion Air Using Direct VentingCombustion air filter Exhaust fansIdentify your appliance’s vent system VentingCAT IV Flue pipe materials CAT I Negative pressure non-condensingDraft Venting Vent system optionsBarometric damper location General informationVenting support Negative draft Conventional negative draft venting seeFlue outlet piping Common Venting SystemsInspection of a masonry chimney Masonry chimney installationsVertical vent termination clearances and location 1Vent Termination from Peaked Roof 10 ft. or Less From Ridge Combustion air inlet piping Vertical DirectAire venting seeLength of air inlet pipe Sidewall air inletClearances Vertical Rooftop Air InletCombined air inlet points Directaire Kits Model Horizontal KIT Vertical KIT Venting of flue productsSidewall with fan Sidewall venting seeSidewall venting termination Sidewall vent termination clearances and locationSidewall venting without fan Drain tee installationModels 502 Venting of flue products Horizontal DirectAire venting Powered Venting seeVertical DV venting termination Direct venting seeFlue outlet piping Horizontal DV venting termination Masonry chimney installationHorizontal Vent Termination Clearances and Location Combustion air inlet pipingAir inlet piping materials Connecting the air inlet pipe to the unitLength of air inlet pipe Sealing PVC, CPVC, ABS, dryer vent, and flex duct vent pipeVertical and sidewall combustion air inlet Multiple sidewall direct vent installationsHorizontal combustion air inlet clearances Vertical Combustion Air Inlet ClearancesOutdoor vent cap kit Outdoor installation seeOutdoor vent/air inlet location Gas connections Connecting to gas supplyGas connection Gas pressure testCombination gas valves Suggested GAS Pipe Size for Single Unit Installations ModelGas train and controls Venting of combination gas valvesChecking gas supply pressure GAS Piping Size ChartCirculating pump Water connections502 752 Models 992 1442 ModelsInitial set-up of maximum water flow Heat exchangerMinimum Pump Performance Auxiliary Mixed Water Limit Control3Heater Within 15 feet of Pool Piping 6Cascaded Heaters Beyond 15 feet of Pool Piping Pool Return Sensor Location MIN Primary Outdoor operation 3-way valve cover Automatic bypass valve cover installationPumped Automatic Bypass Pump purge delay Water flow switchPump purge pre-running delay Relief valveWay Automatic Bypass Valve Wiring Way automatic bypass valve wiringRemote Wire Connection Electrical connectionsPool heater operating control module Installation must comply withLine voltage connections AMP Draw DataPool return sensor 2-wire Louver proving switchPool supply/limit sensor 4-wire Low voltage connectionsWiring of the cascade Alarm contactsStartup Pre-start checklistStarting the filter system Check for gas leaksCheck vent and air piping Check thermostat circuitsPlacing the pool heater in operation Start the pool heater2Operating Instructions Set clock Configuration of the cascadeGeneral Operating informationPool heater temperature regulation Sequence of the cascade DAY Switching on SequenceCascade Sequence of operation Copper-fin2control module MENU/EXIT Display Screen ENTER/RESET UpdownInstaller Access modesUser To save parameters and exit programmingStatus display screens Sysrtn Open Unit Pump DelaySysrtn Shorted STG DemandOwner maintenance Maintenance Maintenance and annual startupService technician Address reported problems MaintenanceInspect appliance area Inspect appliance interiorCheck control settings Check all wiringCheck relief valve Inspect/replace hot surface igniter Ignition system checkoutCheck flue gas passageways Inspect and clean burnerPerform start-up and checks Check burner flame Oiled bearing circulators Review with ownerDigital Harness Connection diagramController LOW Voltage Ladder diagramRuntime Contacts 2BOARDCONNECTION Outdoor S5SENSOR POOL2ND Page
Related manuals
Manual 44 pages 17.92 Kb Manual 16 pages 36.89 Kb

2072, 502 specifications

Lochinvar 2072,502 is an innovative and robust water-heating solution tailored for residential and commercial applications. This model represents a significant advancement in energy efficiency and performance, catering to the dynamic heating requirements of modern buildings.

One of the standout features of Lochinvar 2072,502 is its advanced thermal efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, the unit delivers exceptional heat output while minimizing energy consumption. This not only reduces utility bills for homeowners and businesses but also supports sustainability efforts by decreasing carbon footprints.

The Lochinvar 2072,502 incorporates cutting-edge technologies that set it apart in the market. It is equipped with advanced control systems that allow users to precisely manage heating outputs, ensuring optimal comfort while conserving energy. The user-friendly digital display provides real-time data, allowing for efficient monitoring and control.

Another significant characteristic of the Lochinvar 2072,502 is its robust stainless-steel construction. This feature enhances the unit's durability and longevity, ensuring reliable performance even in challenging conditions. The high-quality materials also contribute to maintaining consistent water temperatures, which is essential for both residential and commercial heating needs.

The Lochinvar 2072,502 operates silently, making it ideal for installations in areas where noise is a concern. Its compact design allows for flexible installation options, fitting seamlessly into various spaces, whether it’s a utility room, basement, or outdoor area.

Furthermore, the unit supports multiple venting options, accommodating different building architectures and layouts. This versatility makes it an ideal choice for new builds and retrofitting existing systems.

Maintenance is streamlined with the Lochinvar 2072,502, as it features a self-diagnostics system that simplifies troubleshooting. Regular service check-ups are made easier with accessible components, allowing technicians to perform maintenance tasks efficiently.

In summary, the Lochinvar 2072,502 stands out for its high efficiency, advanced technology, durability, and flexible installation options. It is an ideal choice for those seeking a reliable and technologically advanced water-heating solution that meets the challenges of contemporary heating demands while promoting energy savings and environmental responsibility.