Pentair 250, 300 installation manual Installation, Indoor

Page 18

P/N 471593

vent terminated at least 24" above

any object within 10 ft.

INDOOR INSTALLATIONS

MINIMAX NT LOW NOx VENTING GUIDELINES

Installation

10 ft.

Vent

Ridge

Cap

 

2 ft. min.

 

3 ft. min.

J

 

K

Detail H

L

Chimney

Vent for roof penetration installations:

Jmust extend at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code.

K must use a double-wall vent pipe through

the roof penetration.

H

E Air Supply

Ventilation

4'

Vent Hood

Air Supply

A Combustion

7'

F 1' min.

 

 

1' min.

 

Vent Hood

F

 

 

G

B

C

3'

4' D

 

 

 

 

1' min.

Vent Hood

 

above grade

G

(Indoor)

Rev.

L must terminate with an approved (listed)

roof jack, storm collar, and vent/weather cap.

Vent pipe extension:

must be the same diameter as the vent connector.

must be suitable for use with category III appliances which have flue gas temperatures of less than 400 deg. F.

may use a single wall vent pipe with

Walkway

Recommended sources for

side wall Vent Hood; see page 15, Section Venting.

Vent termination for side wall installations:

Amust be not less than 7 ft. above public walkways.

Bmust be at least 3 ft. above any outside air intake located within a 10 ft. radius.

must NOT be within 3 ft. of an inside corner of the structure.

C must be at least 1 ft. above grade.

must be located the following distances away from any door, window, or gravity air inlet:

D4 ft. below

E4 ft. horizontally

F1 ft. above

C

permanently sealed seams and joints.

Air Supply

Figure 16.

18

11-1-01

G See Air Supply Requirements Table.

(Table 2 on page 17.)

Image 18
Contents MiniMax NT Low NOx Series For additional free copies of this manual call 800Table of Contents MiniMax NT Low NOx Code RequirementsWarranty Information Safety RulesOperation For Your Safety Read Before Lighting Operation LightingInstallation Instructions SpecificationsInstallation Electrical ELECTRICAL, ALL HSI UnitsTWO-WIRE or THREE-WIRE Remote HOOK-UP Wire RemoteInstallation Remotes Three-wire remote Installation Single Voltage WiringInstallation Single VoltageCode or Superceding Local Wiring Codes MiniMax NTLowWater Connections PlumbingPlumbing Connections GAS Connections Installation Indoor Indoor VENTING-General RequirementsSee page 17 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Installation IndoorInstallation Outdoor VentilationGeneral Description Basic System OperationBasic Operation Water Pressure Switch Safety ControlsAIR Pressure FAN Switch Typical Water Pressure SwitchOperation of Ignition Module Basic Thermostat Operation Pentair Temperature Controller 7800 LayoutGeneral Normal Operation no RemoteTo Change the Factory Temperature Settings Time SettingTemperature & Time Setting Programming Time SETTING, cont’d Time Setting ProgrammingEnergy Saving Tips Maintenance InstructionsMaintenance Spring and Fall OperationPool and SPA Water Maintenance Water TreatmentChemical Balance If pH becomes too high over alkaline, it has these effectsTroubleshooting-Normal Operation Sequence of Heater Normal Operation SequenceTroubleshooting-Normal Operation of Heater Power Service Current Temp SET TEMP/TIMETroubleshooting & Service Service CHECKS-IGNITION Module Service ChecksFlame Sensor Current Check Troubleshooting General Heater Short Cycling Rapid On and Off OperationMinimax NT LOW NOx Heater Single Voltage Description QTY Minimax NT LOW NOx Heater Dual Voltage MiniMax NT Low NOx Dual Voltage Replacement parts Rev. C Rev. C Rev. C MiniMax NT Low NOx Heaters Limited Warranty