NOTE

The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen for proper gas combustion. The air supply

b)Construct a non-combustible base from masonry blocks as illustrated, see Figure 14.

openings should be sized according to Table 2.

Air supply requirements below apply to all MiniMax NT Low NOx heaters*.

 

REQUIRED AIR SUPPLY

 

 

 

Model

Air for Combustion

Air Ventilation

 

Sq. In.

Sq. In.

 

 

 

200

200

200

 

 

 

250

250

250

 

 

 

300

300

300

BASE FOR USE ON COMBUSTIBLE FLOORS

SHEET METAL

BLOCKS

Figure 14.

. Min 6"

. Min 6"

HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH

24 GA. (MIN.) GALVANIZED SHEET METAL.

400

400

400

Table 2.

*NOTE

The openings listed in Table 2 are free open vent area—if the vents incorporate restrictive louvers, the vent openings must be increased to compensate for the area blocked by the louvers (or grills).

INSTALLATION ON FLOORS CONSTRUCTED OF COMBUSTIBLE MATERIALS

The heater may be placed on a “combustible floor” using either of the two methods listed below:

a)Use Listed Factory Non-combustible Base Kit for use on combustible floors.

Model

Non-Combustible Base Kit

 

 

200

471961

 

 

250

460509

 

 

300

471960

 

 

400

460508

 

 

CAUTION

Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.

INDOOR VENT ADAPTORS (FITS ALL MODELS)

The proper draft hood and adapter must be installed on the heater as shown below and on pages 15 and 16:

Product No.

Vent Dia.

 

 

460506

4 in.

 

 

460507

5 in.

 

 

Indoor Vent

Adaptor

Figure 15.

Rev. C 11-1-01

P/N 471593

Image 17
Contents For additional free copies of this manual call 800 MiniMax NT Low NOx SeriesTable of Contents Code Requirements MiniMax NT Low NOxOperation Warranty InformationSafety Rules Operation Lighting For Your Safety Read Before LightingSpecifications Installation InstructionsELECTRICAL, ALL HSI Units Installation ElectricalInstallation Remotes TWO-WIRE or THREE-WIRE Remote HOOK-UPWire Remote Three-wire remote Wiring Installation Single VoltageVoltage Installation SingleMiniMax NTLow Code or Superceding Local Wiring CodesPlumbing Connections Water ConnectionsPlumbing GAS Connections Indoor VENTING-General Requirements Installation IndoorSee page 17 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Indoor InstallationVentilation Installation OutdoorBasic Operation General DescriptionBasic System Operation AIR Pressure FAN Switch Safety ControlsWater Pressure Switch Typical Water Pressure SwitchOperation of Ignition Module General Pentair Temperature Controller 7800 LayoutBasic Thermostat Operation Normal Operation no RemoteTemperature & Time Setting Programming To Change the Factory Temperature SettingsTime Setting Time Setting Programming Time SETTING, cont’dMaintenance Maintenance InstructionsEnergy Saving Tips Spring and Fall OperationChemical Balance Maintenance Water TreatmentPool and SPA Water If pH becomes too high over alkaline, it has these effectsNormal Operation Sequence Troubleshooting-Normal Operation Sequence of HeaterPower Service Current Temp SET TEMP/TIME Troubleshooting-Normal Operation of HeaterTroubleshooting & Service Flame Sensor Current Check Service CHECKS-IGNITION ModuleService Checks Heater Short Cycling Rapid On and Off Operation Troubleshooting GeneralMinimax NT LOW NOx Heater Single Voltage Description QTY Minimax NT LOW NOx Heater Dual Voltage MiniMax NT Low NOx Dual Voltage Replacement parts Rev. C Rev. C Rev. C MiniMax NT Low NOx Heaters Limited Warranty