Pentair 300, 250 Service CHECKS-IGNITION Module, Flame Sensor Current Check, Service Checks

Page 31

Troubleshooting & Service

31

 

 

SERVICE CHECKS—IGNITION MODULE

Service Checks

Symptom

Cause/Cure

 

 

 

1.

Dead

A. Miswired

 

 

B. Transformer bad

 

 

C. Fuse/Circuit breaker bad

 

 

D.

Bad control (check LED for steady on)

 

 

 

 

2.

Thermostat on—no ignition

A.

Miswired

 

 

B. Bad thermostat no voltage at terminal W

 

 

 

 

3.

Valve on, no ignitor

A.

Defective ignitor

 

 

B.

Miswired

 

 

C. Bad control (check voltage at ignitor)

 

 

 

 

4.

Ignitor on, no valve

A.

Valve coil open

 

 

B. Open valve wire

 

 

C. Bad control (check voltage between V1 & V2)

 

 

 

 

5.

Flame okay during TFI,

A.

Bad ignitor

 

no flame sense (after TFI)

B.

Bad S1 wire

 

 

C. Poor ground at burner

 

 

D.

Poor flame (check flame current)

 

 

 

 

FLAME SENSOR CURRENT CHECK

MULTI-PURPOSE METER

USE MICROAMP SCALE

RED (+)

Figure 25.

BLACK (-)

2465H MODULE

SERVICE CHECKS

Flame current is the current which passes through the flame from the sensor to ground. The minimum flame current necessary to keep the system from lockout is 0.7 microamps. To measure flame current, connect an analog DC microammeter to the FC1/FC2 terminals per figure. Meter should read 0.7 µA or higher. If meter reads below “0” on scale, meter leads are reversed. Disconnect power and reconnect meter leads for proper polarity.

Rev. C 11-1-01

P/N 471593

Image 31
Contents For additional free copies of this manual call 800 MiniMax NT Low NOx SeriesTable of Contents Code Requirements MiniMax NT Low NOxSafety Rules Warranty InformationOperation Operation Lighting For Your Safety Read Before LightingSpecifications Installation InstructionsELECTRICAL, ALL HSI Units Installation ElectricalWire Remote TWO-WIRE or THREE-WIRE Remote HOOK-UPInstallation Remotes Three-wire remote Wiring Installation Single VoltageVoltage Installation SingleMiniMax NTLow Code or Superceding Local Wiring CodesPlumbing Water ConnectionsPlumbing Connections GAS Connections Indoor VENTING-General Requirements Installation IndoorSee page 17 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Indoor InstallationVentilation Installation OutdoorBasic System Operation General DescriptionBasic Operation Typical Water Pressure Switch Safety ControlsAIR Pressure FAN Switch Water Pressure SwitchOperation of Ignition Module Normal Operation no Remote Pentair Temperature Controller 7800 LayoutGeneral Basic Thermostat OperationTime Setting To Change the Factory Temperature SettingsTemperature & Time Setting Programming Time Setting Programming Time SETTING, cont’dSpring and Fall Operation Maintenance InstructionsMaintenance Energy Saving TipsIf pH becomes too high over alkaline, it has these effects Maintenance Water TreatmentChemical Balance Pool and SPA Water Normal Operation Sequence Troubleshooting-Normal Operation Sequence of HeaterPower Service Current Temp SET TEMP/TIME Troubleshooting-Normal Operation of HeaterTroubleshooting & Service Service Checks Service CHECKS-IGNITION ModuleFlame Sensor Current Check Heater Short Cycling Rapid On and Off Operation Troubleshooting GeneralMinimax NT LOW NOx Heater Single Voltage Description QTY Minimax NT LOW NOx Heater Dual Voltage MiniMax NT Low NOx Dual Voltage Replacement parts Rev. C Rev. C Rev. C MiniMax NT Low NOx Heaters Limited Warranty