Raypak P926, P1826, P2100, P4001 manual Temperaturecontrol, Pressure Switch Adjustment

Page 20

SECTION 4/ SERVICING INSTRUCTIONS

GENERAL LOCATION OF CONTROLS

MODELS 926-1826

Inlet/Outlet

Pressure

Header

Switch

Unitherm

Electrical

Governor

Conn.

Hi-limit

 

control/

 

Temp. Control

Main Burner Gas Valve

MODELS2100-4001

Inlet/Outlet

Header w/Bypass

Pump

 

 

Electrical

 

 

Connection

 

Main Burner

Fig. #9261.1

 

 

Manual On/Off Valve

Gas Valve

 

TEMPERATURECONTROL

The pool water temperature is controlled by the pool thermostat.

The heater water temperature high limit is controlled by the manual reset high limit.

PRESSURE SWITCH

The pressure switch, or heater actuator, ensures that the heater operates only when the filter pump is in operation. It is factory set at 1.75 PSI for deck level installations. When the heater is located below the level of the spa or pool, it may be necessary to reset the pressure switch to compensate for the no-flow static head. If it is necessary to reset the pressure switch, we recommend the following procedure:

PRESSURE SWITCH ADJUSTMENT:

1.Make sure the pool filter is clean before adjusting the switch.

2.Set the heater control to the OFF mode.

3.Turn the filter pump on and confirm that the pressure switch is closed (use a multimeter to check). If the pressure switch fails to close, either the switch setting is too high or the filter pump is not supplying enough pressure.

4.Turn the heater ON.

5.Manually turn the pressure adjustment knob clock- wise until the heater shuts off. (A flat screw driver may be necessary if knob is too tight).

6.Slowly turn the adjustment knob counter-clockwise until the heater calls for heat again.

7.Turn an additional 1/2 turn counter-clockwise.

8.While the heater is running, check the adjustment by turning the pump off and on several times. The burners should shut off immediately when the pump is turned off. If it does not, repeat the above steps until proper operation is observed.

20

Image 20
Contents Installation and Operating Instructions Raythermtm Contents Code Requirements Base InstallationImportant Notice Clearances ALL HeatersOutdoor Heaters Outdoor Heaters ModelsVentingconnections Z223.1/NFPAGAS Supply Connections FIG. #8090.0Location Pipe Sizing for GAS ConnectionsWaterconnections Water Pressure Switch ControlsAutomatic Chlorinators and Chemical Feeders Unitherm Governor OperationModels 1287/1336 1758/1826 Flow RATES/WATER ConnectionsPoolstat Control Page To adjust the temperature Models 2100 thru LOW Water CUT-OFF Temperaturecontrols HighlimitsPool Stat Electronic Ignition High & LOW GAS Pressure SwitchesElectrical Wiring Wiring Diagram Models 926 Wiring Diagram MODELS1287-1826 Wiring Diagram Models Wiring Diagram Models Pressure Switch Adjustment TemperaturecontrolPressure Switch START-UPPROCEDURES Inspectionprocedures After START-UPMain Burner Flame ControlsRaypak Tube Cleaning KIT Servicing ProceduresTube Cleaning Procedure Typical Pilot Removal and Cleaning Heat Exchanger ReassemblyBurner Drawer Removal GAS Valve RemovalControl Well Replacement Tube Replacement ProcedureProcedure for Cleaning Flue GAS Passageways Unitherm Governor ReplacementMaintenanceandcare WinterizationMechanical for Qualified Service Personnel only ProblemSolution CauseThis does not take into account heat Electrical Electronic Ignition IID IID High VoltageReplacement Parts List Page Page Page Models 2100, 2500, 3001, 3500 Page Page Heat Exchanger Warranty Parts ReplacementTo Make Warranty Claim Exclusive Warranty Limitation of LiabilityLitho in U.S.A