Raypak P926, P1826, P2100, P4001 manual Electrical Electronic Ignition IID IID, High Voltage

Page 29

ELECTRICAL (ELECTRONIC IGNITION IID) IID

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

WARNING

HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

SPARK ACROSS

IGNITER/SENSOR GAP

YES

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

NO

NO

NO

NO

NO

NO

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure.

Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring.

Pull ignition lead and check spark at module.

Spark Okay?

YES

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

Check that all manual gas valves are open, supply tubing and pressures are good, and pilot burner orifice is not blocked.

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

NOTE: If S8600H goes into lockout, reset system. Lockout is used on Pro. models.

Check continuity of ignition cable and ground wire.

Clean flame rod.

Check electrical connections between flame rod and module.

Check for cracked ceramic flame rod insulator.

Check that pilot flame covers flame rod and is steady and blue.

Adjust pilot flame.

If problem persists, replace module.

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

Check electrical connections between module and gas control. If okay, replace gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

NOTE: IF S8600H goes into lockout, reset system.

• Check continuity of ignition cable and ground wire.

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

Check for proper thermostat (controller) operation.

Remove MV lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.

Repeat procedure until trouble free operation is obtained.

29

Image 29
Contents Installation and Operating Instructions Raythermtm Contents Code Requirements Base InstallationImportant Notice ALL Heaters ClearancesOutdoor Heaters Outdoor Heaters ModelsZ223.1/NFPA VentingconnectionsFIG. #8090.0 GAS Supply ConnectionsLocation Pipe Sizing for GAS ConnectionsWaterconnections Controls Water Pressure SwitchAutomatic Chlorinators and Chemical Feeders Unitherm Governor OperationFlow RATES/WATER Connections Models 1287/1336 1758/1826Poolstat Control Page To adjust the temperature Models 2100 thru LOW Water CUT-OFF Temperaturecontrols HighlimitsPool Stat Electronic Ignition High & LOW GAS Pressure SwitchesElectrical Wiring Wiring Diagram Models 926 Wiring Diagram MODELS1287-1826 Wiring Diagram Models Wiring Diagram Models Pressure Switch Adjustment TemperaturecontrolPressure Switch START-UPPROCEDURES After START-UP InspectionproceduresMain Burner Flame ControlsRaypak Tube Cleaning KIT Servicing ProceduresTube Cleaning Procedure Typical Heat Exchanger Reassembly Pilot Removal and CleaningBurner Drawer Removal GAS Valve RemovalTube Replacement Procedure Control Well ReplacementProcedure for Cleaning Flue GAS Passageways Unitherm Governor ReplacementWinterization MaintenanceandcareProblem Mechanical for Qualified Service Personnel onlySolution CauseThis does not take into account heat High Voltage Electrical Electronic Ignition IID IIDReplacement Parts List Page Page Page Models 2100, 2500, 3001, 3500 Page Page Parts Replacement Heat Exchanger WarrantyTo Make Warranty Claim Exclusive Warranty Limitation of LiabilityLitho in U.S.A