Raypak 1287-1758, 2100-4001 manual Mechanical for Qualified Service Personnel only, Problem, Cause

Page 27

SECTION 5 / TROUBLESHOOTING GUIDE

IMPORTANT NOTICE

These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these instructions.

MECHANICAL (FOR QUALIFIED SERVICE PERSONNEL ONLY)

PROBLEM

Harmonics, or whining noise

CAUSE

U.G. Inoperative……………………

*Debris or restriction in system……

*Debris in gas line…………………..

Low flow……………………………...

SOLUTION

Check movement by putting in hot water (110°F or higher). If no move- ment, replace.

Locate the restriction and remove. Flush system and clean.

Remove debris or blow out gas line. Scale forming in heat exchanger - clean heat exchanger and check pool pH and total alkalinity.

Heater going on and off continously

Liming or scale forming on heat exchanger

Dirty filter……………………………

Low water evel in pool………………

External bypass setting out of adjustment…………………………..

*Pressure switch out of adjustment…………………………..

Pool water…………………………....

Backwash filter.

Raise water level.

Adjust bypass

Adjust pressure switch

Recommended pH should be be- tween 7.2 and 7.8 total alkalinity 100- 150 PPM maximum. Hardness -150- 400 PPM maximum.

Sooting

Pilot outage

Yellow lazy flame

High flow rates…………………….....

U.G.Inoperative……………………..

*Air starvation………………………..

*Improperventing…………………....

*Insects or debris clogging

burner intake ports…………………..

Low gas pressure…………………....

Restricted pilot……………………....

Weak pilot generator………………..

Low gas pressure…………………....

*Insects or debris clogging

burner intake ports…………………..

Reduce by adding manual bypass valve and adjust by putting ther- mometer in header (1/4" NPT) drain opening. Set bypass so thermome- ter reads between 105° and 110°F. Check movement by putting in hot water (110°F or higher). If no move- ment, replace.

Refer to installation instructions. Follow recommended installation instructions.

Clean burners

Adjust gas pressure.

Clean pilot.

Replace pilot.

Adjust gas pressure.

Clean burners.

*Usually occurs on initial start-up

27

Image 27
Contents Installation and Operating Instructions Raythermtm Contents Base Installation Important NoticeCode Requirements Outdoor Heaters Models ClearancesALL Heaters Outdoor HeatersZ223.1/NFPA VentingconnectionsFIG. #8090.0 GAS Supply ConnectionsPipe Sizing for GAS Connections WaterconnectionsLocation Unitherm Governor Operation Water Pressure SwitchControls Automatic Chlorinators and Chemical FeedersFlow RATES/WATER Connections Models 1287/1336 1758/1826Poolstat Control Page To adjust the temperature Models 2100 thru Temperaturecontrols Highlimits Pool StatLOW Water CUT-OFF High & LOW GAS Pressure Switches Electrical WiringElectronic Ignition Wiring Diagram Models 926 Wiring Diagram MODELS1287-1826 Wiring Diagram Models Wiring Diagram Models Temperaturecontrol Pressure SwitchPressure Switch Adjustment START-UPPROCEDURES Controls InspectionproceduresAfter START-UP Main Burner FlameServicing Procedures Tube Cleaning Procedure TypicalRaypak Tube Cleaning KIT GAS Valve Removal Pilot Removal and CleaningHeat Exchanger Reassembly Burner Drawer RemovalUnitherm Governor Replacement Control Well ReplacementTube Replacement Procedure Procedure for Cleaning Flue GAS PassagewaysWinterization MaintenanceandcareCause Mechanical for Qualified Service Personnel onlyProblem SolutionThis does not take into account heat High Voltage Electrical Electronic Ignition IID IIDReplacement Parts List Page Page Page Models 2100, 2500, 3001, 3500 Page Page Exclusive Warranty Limitation of Liability Heat Exchanger WarrantyParts Replacement To Make Warranty ClaimLitho in U.S.A