Electrical Power Connections

Installations must follow these codes:

·National Electrical Code and any other national, state, provincial or local codes or regulations hav- ing jurisdiction

·Safety wiring must be N.E.C. Class 1

·Heater must be electrically grounded as required by N.E.C.

·In Canada, C22.1

The heater is wired for 120 VAC, 12 AMPS. The volt- age is indicated on the tie-in leads. Consult the wiring diagram shipped with the heater in the instruction packet. The remote tank control stat, thermostat, or electronic heater control as applicable, may be con- nected to stage selector terminal (See wiring diagram). 24 Volts are supplied to this connection through the heater transformer. DO NOT attach line voltage to the “TH” leads. Before starting the heater check to ensure proper voltage to the heater and pump.

Install a separate disconnect means for each load. Use appropriate-sized wire as defined by NEC, CSA and/or local code. All primary wiring should be 125% of minimum rating.

It is strongly recommended that all individually-pow- ered control modules and the heater should be supplied from the same power source.

Surge Protection

Microprocessor-based and solid state controls are vul- nerable to damage from voltage and amperage fluctuations in the power supply. All sensitive control components should be protected by a suitable com- mercial-grade surge protection device.

If any of the original wire as supplied with the heater must be replaced, it must be replaced with 105°C wire or its equivalent.

Check the Power Source

WARNING: Using a volt-ohm meter (VOM), check the following voltages at the terminal block inside the unit. Make sure proper polarity is followed and house ground is proven.

AC = 108 Volts AC Minimum, 132 Volts AC MAX AB = 108 Volts AC Minimum, 132 Volts AC MAX BC = < 1 Volt AC

Fig. 13: Check Power Source

Making the Electrical Connections

Refer to Fig. 14 Wiring Connection, and the Wiring Diagram.

1.Verify circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.

2.Turn off all power to the heater. Verify that power has been turned off by testing with a volt-ohm meter prior to working with any electrical connec- tions or components.

3.Observe proper wire colors while making electrical connections. Many electronic controls are polarity sensitive. Components damaged by improper electrical installation are not covered by warranty.

4.Provide an external surge suppressor capable of maintaining system integrity.

5.Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.

6.Install heater controls, thermostats, or building management systems in accordance with the applicable manufacturer’s instructions.

7.Conduit should not be used as the ground. There must be a solidly wired ground.

NOTE: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and the grounded service conductor to the grounding electrode.

19

Image 19
Contents Installation & Operating Instructions Page Contents Are important but not related to personal injury hazards Model Identification Before InstallationInstallations at Elevation Product ReceiptComponent Locations-Back Component LocationsModel Quantity Vent Size Burners Gas Valves Blowers Flue General InformationModel Burners per Valve Stages Fire at Stage Time/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Equipment Base InstallationInstallation Codes Indoor InstallationsHeater Min. Clearance Recommended From Combustible Outdoor InstallationsIndoor Units InstallationsCombustion and Ventilation Air Conventional Combustion Air SupplyRelief Valve Piping Canadian InstallationsWater Piping GeneralHydronic Heating Dual Boiler-Primary/Secondary Piping Three-Way Valves Domestic Hot Water PipingPiping-Heating Boilers Air-Separation/Expansion TankSingle Heater-Domestic Hot Water with One Storage Tank Winterizing Your Heater Pool HeatingGas Supply Automatic Chlorinators and Chemical FeedersGas Pressure Regulator Gas Supply Connection Gas Supply PressureMaking the Electrical Connections Electrical Power ConnectionsCheck the Power Source Surge ProtectionSingle Stage and 2-Stage Tankstat Electrical Connections-Domestic Hot WaterDefinition of Appliance Categories VentingSupport of Vent Stack Barometric DamperVent Terminal Location Table I Vent/Air Inlet Termination Clearances Canada Installations US InstallationsVenting Configurations Venting Installation TipsNatural Draft Vertical Vent Termination Natural Draft Vertical Venting System InstallationCategory Inches Length feet Model Appliance Certified Vent Size Max. VentingHorizontal Thru-wall Direct Vent Termination Feet Certified Max Combustion Air Inlet Max. AirVenting Air Intake Category Inches LengthHorizontal Thru-wall Direct Vent Termination Height Inches Min./Max Combustion Max. Air CertifiedVenting Category InchesVertical Direct Vent System Installation Outdoor InstallationVertical Direct Vent Termination Controls High Limit Manual ResetIgnition Control Module Low Water Cut Off Optional Flow SwitchWiring DIAGRAM-MODELS Initial START-UP PRE-START-UPSafety Inspection Main Burner AdjustmentStart-Up Operating Instructions Post START-UP CheckOperation Follow-UpYearly Beginning of each heating season MaintenanceSuggested Minimum Maintenance Schedule To Turn Off Gas To ApplianceQuarterly AppendixInside Combustion Air Contamination MonthlyCorporate Headquarters Page
Related manuals
Manual 56 pages 23.48 Kb

122-322 specifications

Raypak 122-322 is a cutting-edge pool and spa heater designed for optimal performance and efficiency. Known for its robust construction and reliable heating capabilities, this heater has become a preferred choice among pool owners.

One of the standout features of the Raypak 122-322 is its advanced copper fin tube heat exchanger. This innovative technology enhances the heater's efficiency by maximizing heat transfer while minimizing energy consumption. By efficiently circulating the water through the heat exchanger, the Raypak 122-322 quickly raises the temperature, allowing for an enjoyable swimming experience regardless of the weather.

The heater is equipped with a digital control system that allows for precise temperature adjustments. This user-friendly interface makes it easy to set and maintain the desired water temperature, promoting user convenience. The digital controls also provide diagnostic features, which simplify troubleshooting and maintenance, ensuring the heater operates smoothly for years to come.

Safety is a crucial aspect of the Raypak 122-322. It comes with a series of safety features, including a flame rollout switch, high limit switch, and a pressure switch that ensures the unit operates safely under various conditions. This focus on safety provides peace of mind for users, knowing that their heating system is designed with protective measures in place.

The Raypak 122-322 is environmentally friendly, designed to use less energy compared to conventional heating systems. Its efficient performance not only reduces operational costs but also lessens the overall environmental impact, making it a responsible choice for conscious consumers.

With a compact design, the Raypak 122-322 can fit easily into various installation spaces, making it versatile for numerous residential or commercial settings. Additionally, the unit is built with durable materials resistant to corrosion and weather conditions, ensuring longevity and minimal maintenance requirements.

Overall, the Raypak 122-322 stands out in the market due to its advanced features, safety mechanisms, energy efficiency, and ease of use. It exemplifies a perfect blend of innovation and reliability, making it an exceptional option for anyone looking to enhance their pool or spa experience.