Raypak 122-322 manual Water Piping, Canadian Installations, General, Relief Valve Piping

Page 12

Btu per hr (11 cm2 per kW) of total input rating of all equipment in the enclosure.

2.One permanent opening, commencing within 12 in. (30 cm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (2.5 cm) from the sides and back and 6 in. (16 cm) from the front of the appliance. The opening shall directly communicate with the out- doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:

a.1 sq in. per 3000 Btu per hr (7 cm2 per kW) of the total input rating of all equipment located in the enclosure, and

b.Not less than the sum of the areas of all vent connectors in the confined space.

WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances.

Canadian Installations

CAUTION: All combustion air must be drawn from the air outside of the building; the mechanical equip- ment room must communicate directly with the outdoors.

1.Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in (2) and (3), but in no case shall the cross-sectional area be less than 10 sq. in. (6500 sq. mm.).

2.For heaters using a barometric damper in the vent system, and when air supply is provided by natu- ral air flow from the outdoors for natural draft, partial fan assisted, fan-assisted or power draft- assisted burners, there shall be a permanent air supply opening(s) having a cross section area of not less than 1 sq. in. per 7000 BTUH (310 sq. mm per kW) up to and including 1 million BTUH, plus 1 sq. in. per 14000 BTUH (155 sq. mm per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point neither more

than 18 in. (450 mm) nor less than 6 in. (150 mm) above the floor level. The duct can also "Goose Neck" through the roof. The duct is preferred straight down 18” from floor, but do not place near piping. This air supply opening requirement shall be in addition to the air opening for ventilation air required in (1).

3.For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in (1), there shall be a permanent air sup- ply opening(s) having a total cross-sectional area of not less than 1 sq. in. for each 30,000 BTUH (70 sq. mm per kW) of total rated input of the burn- er(s), and the location of the opening(s) shall not interfere with the intended purpose of the open- ing(s) for ventilation air referred to (1). This opening(s) can be ducted to a point neither more than 18 in. (450 mm) nor less than 6 in. (150 mm) above the floor level. The duct can also "Goose Neck" through the roof. The duct is preferred to be straight down 18” from floor, but do not place near piping.

4.Refer to the latest version of the B149 for addition- al information.

Water Piping

General

The heater should be located so that any water leaks will not cause damage to the adjacent area or struc- tures.

CAUTION: This heater requires forced water circulation when the burner is operating. See Table F and Table G for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater operation without water circulation.

Relief Valve Piping

WARNING: Pressure relief valve discharge piping must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.

12

Image 12
Contents Installation & Operating Instructions Page Contents Are important but not related to personal injury hazards Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations Component Locations-BackGeneral Information Model Quantity Vent Size Burners Gas Valves Blowers FlueModel Burners per Valve Stages Fire at Stage General Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Installation CodesIndoor Installations Equipment BaseOutdoor Installations Heater Min. Clearance Recommended From CombustibleInstallations Combustion and Ventilation AirConventional Combustion Air Supply Indoor UnitsCanadian Installations Water PipingGeneral Relief Valve PipingHydronic Heating Dual Boiler-Primary/Secondary Piping Domestic Hot Water Piping Piping-Heating BoilersAir-Separation/Expansion Tank Three-Way ValvesSingle Heater-Domestic Hot Water with One Storage Tank Pool Heating Gas SupplyAutomatic Chlorinators and Chemical Feeders Winterizing Your HeaterGas Supply Connection Gas Supply Pressure Gas Pressure RegulatorElectrical Power Connections Check the Power SourceSurge Protection Making the Electrical ConnectionsElectrical Connections-Domestic Hot Water Single Stage and 2-Stage TankstatVenting Definition of Appliance CategoriesBarometric Damper Support of Vent StackVent Terminal Location Table I Vent/Air Inlet Termination Clearances US Installations Canada InstallationsVenting Installation Tips Venting ConfigurationsNatural Draft Vertical Venting System Installation Natural Draft Vertical Vent TerminationModel Appliance Certified Vent Size Max. Venting Category Inches Length feetHorizontal Thru-wall Direct Vent Termination Certified Max Combustion Air Inlet Max. Air Venting Air IntakeCategory Inches Length FeetHorizontal Thru-wall Direct Vent Termination Min./Max Combustion Max. Air Certified VentingCategory Inches Height InchesOutdoor Installation Vertical Direct Vent System InstallationVertical Direct Vent Termination High Limit Manual Reset ControlsIgnition Control Module Flow Switch Low Water Cut Off OptionalWiring DIAGRAM-MODELS PRE-START-UP Initial START-UPMain Burner Adjustment Safety InspectionStart-Up Post START-UP Check OperationFollow-Up Operating InstructionsMaintenance Suggested Minimum Maintenance ScheduleTo Turn Off Gas To Appliance Yearly Beginning of each heating seasonAppendix Inside Combustion Air ContaminationMonthly QuarterlyCorporate Headquarters Page
Related manuals
Manual 56 pages 23.48 Kb

122-322 specifications

Raypak 122-322 is a cutting-edge pool and spa heater designed for optimal performance and efficiency. Known for its robust construction and reliable heating capabilities, this heater has become a preferred choice among pool owners.

One of the standout features of the Raypak 122-322 is its advanced copper fin tube heat exchanger. This innovative technology enhances the heater's efficiency by maximizing heat transfer while minimizing energy consumption. By efficiently circulating the water through the heat exchanger, the Raypak 122-322 quickly raises the temperature, allowing for an enjoyable swimming experience regardless of the weather.

The heater is equipped with a digital control system that allows for precise temperature adjustments. This user-friendly interface makes it easy to set and maintain the desired water temperature, promoting user convenience. The digital controls also provide diagnostic features, which simplify troubleshooting and maintenance, ensuring the heater operates smoothly for years to come.

Safety is a crucial aspect of the Raypak 122-322. It comes with a series of safety features, including a flame rollout switch, high limit switch, and a pressure switch that ensures the unit operates safely under various conditions. This focus on safety provides peace of mind for users, knowing that their heating system is designed with protective measures in place.

The Raypak 122-322 is environmentally friendly, designed to use less energy compared to conventional heating systems. Its efficient performance not only reduces operational costs but also lessens the overall environmental impact, making it a responsible choice for conscious consumers.

With a compact design, the Raypak 122-322 can fit easily into various installation spaces, making it versatile for numerous residential or commercial settings. Additionally, the unit is built with durable materials resistant to corrosion and weather conditions, ensuring longevity and minimal maintenance requirements.

Overall, the Raypak 122-322 stands out in the market due to its advanced features, safety mechanisms, energy efficiency, and ease of use. It exemplifies a perfect blend of innovation and reliability, making it an exceptional option for anyone looking to enhance their pool or spa experience.