Generac 005030-0, 005028-0, 005031-0 ‹ 4.9.3 Battery Maintenance, ‹ 4.9.4 Battery Replacement

Page 25

Section 4 — Maintenance

Liquid-cooled 15, 20 and 25 kW Generators

‹4.9.3 BATTERY MAINTENANCE

The battery should be inspected per Section 4.7, Scheduled Maintenance. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. Do not use tap water in batteries.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- ! sive sulfuric acid solution that can cause severe

burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster bat- ! tery to crank and start the generator engine. If

the battery has completely discharged, remove it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to ! the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL,

the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply to the battery charger is turned off, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

‹4.9.4 BATTERY REPLACEMENT

When replacing batteries, use the same number and the type of battery that follows:

 

BCI Group No.

CCA

 

 

26-60R

525 @ 0 deg. F

 

 

 

 

 

NOTE:

The BCI number should be located directly on the battery.

PERIODIC REPLACEMENT PARTS

Part Name

Part Number

 

 

Oil Filter

Motorcraft FL-400-S (supplied with engine)

Radiator Cap

# 046627

Air Cleaner

# 059402

Spark Plug

Motorcraft AWSF-52-C (supplied with engine)

Battery

# 077483

23

Image 25
Contents This manual should remain with the unit ‹ Operation and Maintenance Authorized Service Dealer Location‹ HOW to Obtain Service IntroductionTable of Contents General Hazards ‹ Standards Index Electrical HazardsAutomatic Transfer Switch ATS Mode Transfer SwitchEngineered Transfer Switch Wire Start GTS Mode Generator‹ 1.8.2 High Coolant Temperature Switch ‹ 1.8.1 LOW OIL Pressure SwitchMain Circuit Breaker Generator Fuel SystemLifting the Generator UnpackingFuel Consumption SpecificationsAWSF-52-C Coolant Recommendations Before InstallationEngine OIL Recommendations Generator Mounting Support Generator Location‹ 2.1.1 Nfpa Standards ‹ 2.1.2 Other Published StandardsTotal Circuit Isolation Method Basic Standby Electric SystemGrounding the Generator Emergency Circuit Isolation MethodGenerator AC Neutral Connections Connection Diagram ATS ModeConnection Diagram GTS Mode ‹ 2.11.1 Vented Batteries Battery InstallationPreparation Before START-UP Manual Transfer START-UP Control Console ComponentsBat Red Oil Red Temp Red Speed Red Crank Red Engine Governor Gain AdjustmentsAutomatic Operation Manual Retransfer ShutdownWeekly Exercise Cycle Voltage Regulator Adjustment Control Board DIP Switch SettingsIntake Manifold Procedure Exhaust Manifold ProcedureCooling System Cylinder Head ProcedureOverload Protection for Engine DC Electrical System Checking Fluid Levels‹ 4.8.2 Check Battery ‹ 4.7.2 Battery Fluid ‹ 4.8.6 Perform Visual Inspection‹ 4.7.3 Engine Coolant ‹ 4.8.1 Check Engine OIL Level‹ 4.8.11 Changing the Engine AIR Cleaner Miscellaneous Maintenance‹ 4.9.1 Cleaning the Generator ‹ 4.8.13 Coolant Change‹ 4.9.4 Battery Replacement ‹ 4.9.3 Battery MaintenancePeriodic Replacement Parts Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 15, 20 and 25 kW Generators Liquid-cooled 15, 20 and 25 kW Generators Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Page Hold Down Battery Support Battery TrayAssembly Battery Tray Battery Post Cover BlackTo B Door Battery Compartment Assy Wire 14AWG 7.5 #0 GRN/YELDuct Intake MID AL 2.5L Duct Discharge RH AL 2.5LPage Switch ROC Dpdt ON-OFF-ON Switch ROC Dpst 125V SPDHang TAG 2 Wire Start not Shown TOP, Control PanelPage Harness Ctrl PNL 2.5L Ford AL not Shown 13 17 Engine 2.5L Ford Tank Coolant RecoverySTARTER, 12 Volt NUT HEX M10-1.5 G8 YEL CHRTo Engine Cover AIR Cleaner Body Carburetor AssemblyGASKET, AIR Cleaner Adapter Bracket Fuel RegulatorLocktight Rotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 40KW 1P Direct HSB 3.9L ChryslerPipe Exhaust 2.5L Ford Pipe Muffler OUTMuffler 2.5L Ford Saddle 2 InchCover Connector Housing Housing Governor ConnectorASM Motor Stepper Harn GOV 2.5L FordBarbed STR 1/4 NPT X 3/8 HOSE, 2.5L Ford LowerALM Radiator 2.5L FordInstallation Diagram MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following

005028-0, 005030-0, 005028-0, 005031-0 specifications

Generac's line of generator models, including the 005028-0, 005030-0, 005031-0, and their closely related variant 005028-0, represent a fusion of durability, technology, and user-centric design focused on providing reliable power solutions for residential and commercial applications.

The Generac 005028-0 model stands out with its robust construction and efficient performance. It features a powerful engine that ensures a steady supply of electricity, capable of handling essential appliances during power outages. The model incorporates Generac's patented TruePower technology, which offers clean and stable power, ensuring sensitive electronics are safe from fluctuations. This feature is particularly appealing for homeowners who rely on medical equipment or sophisticated devices that require consistent power quality.

On the other hand, the 005030-0 model takes performance up a notch by equipped with a larger fuel tank, allowing for extended runtime during outages. It also has a quieter operation compared to its counterparts, making it suitable for residential areas where noise levels are a concern. The model includes an intuitive user interface that simplifies operation, letting users monitor their generator’s status effortlessly.

Similarly, the 005031-0 model boasts enhanced technology via a fully automatic transfer switch. This feature enables seamless switching between utility power and generator power without user intervention, ensuring that homes and businesses remain powered even during unexpected power failures. Equipped with advanced safety features, this model ensures that the generator operates only when necessary, significantly extending its lifespan and maintaining efficiency.

Additionally, all these Generac models share a durable casing designed to withstand harsh weather conditions. They are engineered for easy maintenance, with oil and fuel access points conveniently located for user convenience. Furthermore, the models come with various options for fuel types, including propane and natural gas, providing users flexibility based on their needs.

In summary, Generac's 005028-0, 005030-0, and 005031-0 models are characterized by their reliable performance, advanced technology, and user-friendly features. These generators are perfect solutions for anyone seeking a dependable source of backup power, ensuring that essential equipment runs smoothly without interruptions, no matter the situation.