Section 4 — Maintenance

Liquid-cooled 15, 20 and 25 kW Generators

‹ 4.7.2 BATTERY FLUID

 

‹ 4.8.6 PERFORM VISUAL INSPECTION

Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

‹4.7.3 ENGINE COOLANT

Check coolant level in coolant recovery bottle. See Specifications.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap (only when engine has cooled down) to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an Authorized Service Dealer. Inspect cooling system and coolant recov- ery system for leaks.

4.8MAINTENANCE OWNER/ OPERATOR CAN PERFORM

‹4.8.1 CHECK ENGINE OIL LEVEL

Refer to “Checking Fluid Levels”.

‹4.8.2 CHECK BATTERY

See “Checking Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹4.8.3 EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 12 minutes. See “Weekly Exercise Cycle”.

‹4.8.4 INSPECT COOLING SYSTEM

Inspect engine cooling system. See “Maintenance Schedule”.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹4.8.5 CHECK ENGINE COOLANT LEVEL

See “Checking Fluid Levels”.

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹4.8.7 INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

‹4.8.8 CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 of an inch. Adjust belt tension as required.

‹4.8.9 INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only

!qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incorrect frequency and/or voltage. Only quali- fied service technicians should adjust the gov- erned speed.

‹4.8.10 CHANGING ENGINE OIL

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 4.1) counterclockwise and remove. Properly dispose of old filter.

21

Image 23
Contents This manual should remain with the unit Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents General Hazards ‹ Standards Index Electrical HazardsGenerator Transfer SwitchAutomatic Transfer Switch ATS Mode Engineered Transfer Switch Wire Start GTS ModeGenerator Fuel System ‹ 1.8.1 LOW OIL Pressure Switch‹ 1.8.2 High Coolant Temperature Switch Main Circuit BreakerLifting the Generator UnpackingAWSF-52-C SpecificationsFuel Consumption Engine OIL Recommendations Before InstallationCoolant Recommendations ‹ 2.1.2 Other Published Standards Generator LocationGenerator Mounting Support ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Basic Standby Electric SystemTotal Circuit Isolation Method Grounding the GeneratorGenerator AC Neutral Connections Connection Diagram ATS ModeConnection Diagram GTS Mode ‹ 2.11.1 Vented Batteries Battery InstallationPreparation Before START-UP Manual Transfer START-UP Control Console ComponentsBat Red Oil Red Temp Red Speed Red Crank Red Engine Governor Gain AdjustmentsWeekly Exercise Cycle Manual Retransfer ShutdownAutomatic Operation Voltage Regulator Adjustment Control Board DIP Switch SettingsIntake Manifold Procedure Exhaust Manifold ProcedureChecking Fluid Levels Cylinder Head ProcedureCooling System Overload Protection for Engine DC Electrical System‹ 4.8.1 Check Engine OIL Level ‹ 4.7.2 Battery Fluid ‹ 4.8.6 Perform Visual Inspection‹ 4.8.2 Check Battery ‹ 4.7.3 Engine Coolant‹ 4.8.13 Coolant Change Miscellaneous Maintenance‹ 4.8.11 Changing the Engine AIR Cleaner ‹ 4.9.1 Cleaning the GeneratorPeriodic Replacement Parts ‹ 4.9.3 Battery Maintenance‹ 4.9.4 Battery Replacement Service Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsLiquid-cooled 15, 20 and 25 kW Generators Liquid-cooled 15, 20 and 25 kW Generators Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Page Battery Post Cover Black Support Battery TrayHold Down Battery Assembly Battery TrayTo B Duct Discharge RH AL 2.5L Assy Wire 14AWG 7.5 #0 GRN/YELDoor Battery Compartment Duct Intake MID AL 2.5LPage TOP, Control Panel Switch ROC Dpst 125V SPDSwitch ROC Dpdt ON-OFF-ON Hang TAG 2 Wire Start not ShownPage Harness Ctrl PNL 2.5L Ford AL not Shown 13 17 NUT HEX M10-1.5 G8 YEL CHR Tank Coolant RecoveryEngine 2.5L Ford STARTER, 12 VoltTo Engine Bracket Fuel Regulator Body Carburetor AssemblyCover AIR Cleaner GASKET, AIR Cleaner AdapterLocktight Rotor 390 40KW 1P Direct HSB 3.9L Chrysler Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordSaddle 2 Inch Pipe Muffler OUTPipe Exhaust 2.5L Ford Muffler 2.5L FordHarn GOV 2.5L Ford Housing Governor ConnectorCover Connector Housing ASM Motor StepperRadiator 2.5L Ford HOSE, 2.5L Ford LowerBarbed STR 1/4 NPT X 3/8 ALMInstallation Diagram PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyThis Warranty Shall not Apply to the Following

005028-0, 005030-0, 005028-0, 005031-0 specifications

Generac's line of generator models, including the 005028-0, 005030-0, 005031-0, and their closely related variant 005028-0, represent a fusion of durability, technology, and user-centric design focused on providing reliable power solutions for residential and commercial applications.

The Generac 005028-0 model stands out with its robust construction and efficient performance. It features a powerful engine that ensures a steady supply of electricity, capable of handling essential appliances during power outages. The model incorporates Generac's patented TruePower technology, which offers clean and stable power, ensuring sensitive electronics are safe from fluctuations. This feature is particularly appealing for homeowners who rely on medical equipment or sophisticated devices that require consistent power quality.

On the other hand, the 005030-0 model takes performance up a notch by equipped with a larger fuel tank, allowing for extended runtime during outages. It also has a quieter operation compared to its counterparts, making it suitable for residential areas where noise levels are a concern. The model includes an intuitive user interface that simplifies operation, letting users monitor their generator’s status effortlessly.

Similarly, the 005031-0 model boasts enhanced technology via a fully automatic transfer switch. This feature enables seamless switching between utility power and generator power without user intervention, ensuring that homes and businesses remain powered even during unexpected power failures. Equipped with advanced safety features, this model ensures that the generator operates only when necessary, significantly extending its lifespan and maintaining efficiency.

Additionally, all these Generac models share a durable casing designed to withstand harsh weather conditions. They are engineered for easy maintenance, with oil and fuel access points conveniently located for user convenience. Furthermore, the models come with various options for fuel types, including propane and natural gas, providing users flexibility based on their needs.

In summary, Generac's 005028-0, 005030-0, and 005031-0 models are characterized by their reliable performance, advanced technology, and user-friendly features. These generators are perfect solutions for anyone seeking a dependable source of backup power, ensuring that essential equipment runs smoothly without interruptions, no matter the situation.