Generac 04758-1, 04759-1, 04760-1 owner manual Voltage Regulator Adjustment, BREAK-IN Procedure

Page 15

Section 3 — Operation

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

Figure 2.3 — Engine Governor Adjustment

Idle Spring

Governor

Shaft

(Rotate

Clockwise)

Governor Clamp Bolt

No Load Idle

Adjustment Screw

 

2.7.2 12 KW AND 15 KW UNITS

1.Loosen governor clamp bolt (See Figure 2.3).

2.Completely remove the idle spring.

3.With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.

4.Start unit and apply full load. Use full load speed adjust screw (Figure 2.4) to adjust frequency to 58 Hz.

5.Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.

6.Using a hand, push the governor arm to the closed throttle position. Make sure the idle spring does not stretch at all.

7.Restart the unit.

8.Slowly turn the idle adjust screw to adjust the no- load idle frequency to 63-63.5 Hz.

9.The governor is now set.

2.7.3 ADDITIONAL CORROSION PROTECTION

Periodically spray all engine linkage parts and brack- ets with corrosion inhibiting spray such as WD-40 or a comparable product.

2.8VOLTAGE REGULATOR

ADJUSTMENT

With the frequency between 62-63.5 Hertz, slowly turn the slotted potentiometer (Figure 2.5) until line voltage reads 244-252 volts.

NOTE:

Remove the access panel on top of the control panel to adjust the voltage regulator.

Figure 2.5 – Voltage Adjustment Potentiometer

NOTE:

The voltage regulator is housed above the genera- tor's control panel. The regulator maintains a volt- age in direct proportion to frequency. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.

Figure 2.4 — Full Load Speed Adjust Screw

Full Load Speed Adjust Screw

3.1BREAK-IN PROCEDURE

Once the unit has been installed, with utility power connected to the transfer switch, and all electrical checks have been made, it is strongly recommended that the following “Break-in Procedure” be completed to ensure correct generator operation in the future.

1.Set the generator’s AUTO/OFF/MANUAL switch to AUTO.

2.Turn OFF the utility power supply to the transfer switch using the means provided (such as a utili- ty main line circuit breaker).

3.The unit will start, and the transfer switch will transfer to standby.

4.Run the unit for one hour at 25 percent load.

5.Run the unit for one hour at 50 percent load.

6.Run the unit for one hour at 75 percent load.

7.Run the unit for one hour at 100 percent load.

13

Image 15
Contents Installation Introduction Introduction Inside Front Cover Post Installation Start-up AdjustmentsMaintenance TroubleshootingGeneral Hazards ‹ Standards Index Electrical HazardsUNPACKING/INSPECTION Protection SystemsSystem SET LED 7 kW, Single Cylinder GH-410 Engine GeneratorSpecifications ‹ 1.5.1 Generator‹ 1.5.2 Engine 1 7 KW, 410CC Reconfiguring the Fuel SystemFuel Requirements Recommendations Fuel Consumption2.1 7 kW, 12 kW and 15 kW Units Transfer SwitchLocation GeneratorBattery Battery InstallationCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadAdjusting the Regulator Natural GAS only Engine Governor Adjustment1 7 KW Units Voltage Regulator Adjustment BREAK-IN Procedure2 12 KW and 15 KW Units ‹ 3.2.2 OFF Position Automatic Transfer OperationSequence of Automatic Operation ‹ 3.2.1 Auto PositionManual Transfer Operation ‹ 3.5.2 Transfer Back to Utility Power Source‹ 3.7.3 Overcrank Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.2 High Temperature SwitchChecking the Engine OIL Level Changing the Engine OIL‹ 4.3.1 Engine OIL Recommendations ‹ 4.3.2 OIL Change Procedure Changing the OIL Filter‹ 4.5.1 7 KW, 12 KW and 15 KW Generators Spark Plugs Battery MaintenanceCooling System Adjusting Valve ClearanceCorrosion Protection OUT of Service Procedure‹ 4.12.2 Return to Service ‹ 4.12.1 Removal from ServiceSYSTEM/COMPONENT Procedure Frequency Service ScheduleProblem Cause Correction Troubleshooting GuideElectrical Data Customer Battery Utility Battery Charger Utility Connection BCR SW1 Exploded Views and Parts Lists Part NO.QTY. Description Exploded Views and Parts Lists Part NO. QTY. Description 140 Part NO. QTY Description 138 122 QTY Description 28 31 ADAPTOR, Engine Exploded Views and Parts Lists Stator 12KW Exploded Views and Parts Lists ASSEMBLY, Connecting ROD Exploded Views and Parts Lists SCREW, Taptite M6-1.0X8 Yellow Chrome For GT 760 Engine only CASTING, Twin Regulator Housing Mounting Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators California and Federal Emission Control Warranty Statement Emission Control System Warranty This Warranty Shall not Apply to the Following Warranty Schedule