Bryant ASPAX1BBA015 Automatic Transfer Operation, ‹ 3.2.1 Auto Position, ‹ 3.2.2 OFF Position

Page 15

Section 3 — Operation

9.Allow the unit to cool.

10.Set the generator’s main circuit breaker to its OFF (or OPEN) position.

11.Set the generator's AUTO/OFF/MANUAL switch to OFF. Remove the 7.5A and 15A fuses from the generator control panel. Disconnect the battery cables as outlined in “General Hazards” (page 2).

12.Drain the oil and remove the oil filter. Replace the oil filter according to Section 3.4, “Changing the Oil Filter”. Replace the oil with synthetic oil as recommended in Section 3.3, “Changing the Engine Oil”.

13.Reconnect the battery cables as outlined in “General Hazards” (page 2) and insert the 7.5A and 15A fuses into the generator control panel. The generator is now ready for service.

3.2USING THE AUTO/OFF/MANUAL SWITCH (FIGURE 3.1)

‹3.2.1 “AUTO” POSITION

Selecting this switch position activates fully auto- matic system operation. It also permits starting and exercising the engine every seven days with the set- ting of the exercise timer (see “Setting the Exercise Timer” section). This position also is used for remote starting, when it is set up.

‹3.2.2 “OFF” POSITION

This switch position shuts down the engine. This position also prevents automatic operation.

15 kW Generator

With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre- set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove both fuses before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.

3.3AUTOMATIC TRANSFER

OPERATION

To select automatic operation, do the following:

1.Make sure the transfer switch main contacts are set to their UTILITY position, i.e., loads con- nected to the utility power source (Figure 3.2).

2.Be sure that normal utility power source voltage is available to transfer switch terminal lugs N1 and N2.

3.Set the generator’s AUTO/OFF/MANUAL switch to AUTO.

4.Set the generator’s main circuit breaker to its ON (or CLOSED) position.

With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to Section 3.4, “Sequence of Automatic Operation.”

‹3.2.3 “MANUAL” POSITION

Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.

Figure 3.1 – Generator Control Panel

OUTLET FUSE

 

 

EXTERNAL

 

 

 

GFCI

 

 

 

 

 

7.5A

 

 

CIRCUIT

 

AUTO OFF

MAN.

BREAKER

SYSTEM SET

 

 

 

 

 

 

12 VDC

LOW OIL

 

 

 

 

SYSTEM FUSE

 

 

 

HIGH TEMP.

 

 

 

 

OVER SPEED

 

 

 

 

OVER CRANK

15A

SET

 

 

F L A S H IN G G R E E N L E D =

 

 

N O U T IL IT Y S E N S E

 

ACCESSORY

 

EXERCISE

4 F L A S H IN G R E D L E D S =

 

TIME

OUTLET 7.5A MAX

E X E R C IS E R N O T S E T

‹3.3.1 12 VDC ACCESSORY OUTLET

The generator is equipped with a 12 VDC accessory outlet in the generator control panel (Figure 3.1). With the generator running or in standby mode, this outlet may be used to temporarily power low power accessories such as a work light, cell phone, radio or any other automotive style accessory. This outlet is capable of delivering a MAXIMUM of 7.5 amps. If the accessory to be used through this circuit demands too much power, the fuse that protects this circuit will melt open and the circuit will not be functional.

This 12 VDC outlet draws power from the gen- erator’s starting battery and extended use of this outlet may drain the battery and the engine may not start. This outlet should NOT be used for battery charging.

13

Image 15
Contents Installation Introduction ‹ Contents‹ Operation and Maintenance ‹ HOW to Obtain ServiceIntroduction Inside Front Cover Post Installation Start-up AdjustmentsMaintenance Troubleshooting Warning  ‹ Standards Index  Explosion Hazards System SET LED UNPACKING/INSPECTIONLocation Protection SystemsGfci Generator‹ 1.6.1 Generator SpecificationsFuel Requirements Recommendations Fuel ConsumptionFuel System ‹ 1.9.1 15KW, 990CC Engines‹ 1.10.1 Generator 10.2.1 15 kW Units Battery InstallationBattery ‹ 1.10.2 Transfer SwitchCheck Transfer Switch Operation Before Initial START-UPElectrical Checks Checking Automatic Operation Generator Tests Under LoadDual Fuel Regulators Adjusting the Regulator Natural GAS onlyVoltage Regulator Adjustment BREAK-IN Procedure‹ 2.7.1 15 KW Units ‹ 3.2.2 OFF Position ‹ 3.3.1 12 VDC Accessory OutletAutomatic Transfer Operation ‹ 3.2.1 Auto Position‹ 3.3.2 120 VAC Gfci Outlet ‹ 3.5.1 Transfer to Generator Power SourceSequence of Automatic Operation Manual Transfer Operation‹ 3.7.2 High Temperature Switch Setting the Exercise Timer‹ 3.5.2 Transfer Back to Utility Power Source ‹ 3.7.1 LOW OIL Pressure SwitchChecking the Engine OIL Level FusesChanging the Engine OIL ‹ 4.5.1 15 KW Generators ‹ 4.3.2 OIL Change ProcedureChanging the OIL Filter Spark PlugsAdjusting Valve Clearance Battery MaintenanceCorrosion Protection Cooling SystemOUT of Service Procedure ‹ 4.12.1 Removal from Service‹ 4.12.2 Return to Service Be performed by the nearest dealer Service ScheduleProblem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Customer Connection KW Generator Electrical Schematic Drawing No E9017 SW1 Exploded Views and Parts Lists Part NO. QTY. Description KW Generator Control Panel Drawing No E9162-J Part NO. QTY Description 16B Item Part NO. QTY. Description 138 122 KNOB, AIR Cleaner Views and Parts Lists QTY Description KW Generator Gas Regulator Drawing No D8720-G CASTING, Twin Regulator Housing California and Federal Emission Control Warranty Statement Emission Control System Warranty Warranty Schedule