Bryant ASPAX1BBA015 Setting the Exercise Timer, ‹ 3.5.2 Transfer Back to Utility Power Source

Page 17

5.To crank and start the engine, set the AUTO/OFF/ MANUAL switch to MANUAL.

6.Let the engine stabilize and warm up for a few minutes.

7.Set the generator’s main circuit breaker to its ON (or CLOSED) position. The standby power source now powers the loads.

‹3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE

When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows:

1.Set the generator’s main circuit breaker to its OFF (or OPEN) position.

2.Let the engine run for a minute or two at no-load to stabilize the internal temperatures.

3.Set the generator’s AUTO/OFF/MANUAL switch to its OFF (or OPEN) position. The engine should shut down.

4.Check that utility power supply to the transfer switch is turned OFF.

DANGER

Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal elec- trical shock.

5.Use the manual transfer handle inside the trans- fer switch to move the main contacts back to their UTILITY position, i.e., loads connected to the util- ity power source (Figure 3.2).

6.Turn ON the utility power supply to the transfer switch using the means provided.

7.Set the system to automatic operation as outlined in “Automatic Transfer Operation,” Section 2.3.

3.6SETTING THE EXERCISE TIMER

The generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day the following sequence is completed. During this exercise period, the unit runs for approx- imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle.

A switch on the control panel (see Figure 3.1) permits selection of the day and time for system exercise. To select the desired day and time of day, the following sequence must be performed at that time.

1.Verify that the AUTO/OFF/MANUAL switch is set to AUTO.

Section 3 — Operation

15 kW Generator

2.Hold down the set timer switch until the genera- tor starts (approximately 10 seconds) and then release.

3.The generator will start and run for approximate- ly 12 minutes and then shut down on its own. The exerciser will then be set to run at that time of day every week.

NOTE:

The exerciser will only work in the AUTO mode and will not work unless this procedure is per- formed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 (Remote Not Auto) on the controller printed circuit board is ON.

3.7PROTECTION SYSTEMS

‹3.7.1 LOW OIL PRESSURE SWITCH

This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.

‹3.7.2 HIGH TEMPERATURE SWITCH

This switch’s contacts (Figure 3.3) close if the tem- perature should exceed approximately 140º C (284º F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.

Figure 3.3 – Low Oil Pressure and

High Temperature Switches

Low Oil Switch

 

High Temp Switch

 

 

 

 

 

 

Loosen

Oil

Drain

Hose

Oil Filter

15

Image 17
Contents Installation ‹ Operation and Maintenance ‹ Contents‹ HOW to Obtain Service IntroductionMaintenance Post Installation Start-up AdjustmentsTroubleshooting Introduction Inside Front Cover Warning  ‹ Standards Index  Explosion Hazards Location UNPACKING/INSPECTIONProtection Systems System SET LEDGfci GeneratorFuel Requirements Recommendations SpecificationsFuel Consumption ‹ 1.6.1 Generator‹ 1.10.1 Generator Fuel System‹ 1.9.1 15KW, 990CC Engines Battery Battery Installation‹ 1.10.2 Transfer Switch 10.2.1 15 kW UnitsElectrical Checks Check Transfer Switch OperationBefore Initial START-UP Checking Automatic Operation Generator Tests Under LoadDual Fuel Regulators Adjusting the Regulator Natural GAS only‹ 2.7.1 15 KW Units Voltage Regulator AdjustmentBREAK-IN Procedure Automatic Transfer Operation ‹ 3.3.1 12 VDC Accessory Outlet‹ 3.2.1 Auto Position ‹ 3.2.2 OFF PositionSequence of Automatic Operation ‹ 3.5.1 Transfer to Generator Power SourceManual Transfer Operation ‹ 3.3.2 120 VAC Gfci Outlet‹ 3.5.2 Transfer Back to Utility Power Source Setting the Exercise Timer‹ 3.7.1 LOW OIL Pressure Switch ‹ 3.7.2 High Temperature SwitchChanging the Engine OIL Checking the Engine OIL LevelFuses Changing the OIL Filter ‹ 4.3.2 OIL Change ProcedureSpark Plugs ‹ 4.5.1 15 KW GeneratorsAdjusting Valve Clearance Battery MaintenanceCorrosion Protection Cooling System‹ 4.12.2 Return to Service OUT of Service Procedure‹ 4.12.1 Removal from Service Be performed by the nearest dealer Service ScheduleProblem Cause Correction Troubleshooting GuideMounting Dimensions Electrical Data Customer Connection KW Generator Electrical Schematic Drawing No E9017 SW1 Exploded Views and Parts Lists Part NO. QTY. Description KW Generator Control Panel Drawing No E9162-J Part NO. QTY Description 16B Item Part NO. QTY. Description 138 122 KNOB, AIR Cleaner Views and Parts Lists QTY Description KW Generator Gas Regulator Drawing No D8720-G CASTING, Twin Regulator Housing California and Federal Emission Control Warranty Statement Emission Control System Warranty Warranty Schedule