Bryant ASPAX1BBA015 owner manual OUT of Service Procedure, ‹ 4.12.1 Removal from Service

Page 22

Section 4 — Maintenance

15 kW Generator

4.12 OUT OF SERVICE PROCEDURE

‹4.12.1 REMOVAL FROM SERVICE

If the generator cannot be exercised every seven days, and will be out of service longer than 90 days, pre- pare the generator for storage as follows:

1.Start the engine and let it warm up.

2.Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.

3.Once the unit has shut down, it will signal a low oil fault.

4.Set the generator’s main circuit breaker to its OFF (or open) position.

5.Set the Auto/Off/Manual switch to OFF and turn off the utility power to the transfer switch. Remove the 7.5A and 15A fuses from the genera- tor control panel. Disconnect the battery cables as outlined in “General Hazards” (page 2). Turn on the utility power supply to the transfer switch in order to power the emergency load centers cir- cuits while utility power is available.

6.While the engine is still warm from running, drain the oil completely. Refill the crankcase with oil. See ”Engine Oil Recommendations,” Section.

7.Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.

8.Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).

9.Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.

10.Clean and wipe the entire generator.

‹4.12.2 RETURN TO SERVICE

To return the unit to service after storage, proceed as follows:

1.Verify that utility power is turned off and that the Auto/Off/Manual switch is set to OFF.

2.Check the tag on the engine for oil viscosity and classification. Verify that the correct recom- mended oil is used in the engine (see “Engine Oil Recommendations”). If necessary, drain and refill with the proper oil.

3.Check the state of the battery. Fill all cells of unsealed batteries to the proper level with dis- tilled water. DO NOT USE TAP WATER IN THE BATTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the bat- tery. See the “Specifications” Section, for type and size.

4.Clean and wipe the entire generator.

5.Remove the 7.5A and 15A fuses from the genera- tor control panel. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.

6.Open the fuel shutoff valve.

7.Insert the 7.5A and 15A fuses into the generator control panel. Start the unit by moving the Auto/ Off/Manual switch to MANUAL. Allow the unit to warm up thoroughly.

8.Stop the unit by setting the Auto/Off/Manual switch to OFF.

9.Turn on the utility power to the transfer switch.

10.Set the Auto/Off/Manual switch to AUTO.

11.The generator is now ready for service.

NOTE:

If the battery was dead or disconnected, the exer- cise timer must be reset.

20

Image 22
Contents Installation ‹ HOW to Obtain Service ‹ Contents‹ Operation and Maintenance IntroductionTroubleshooting Post Installation Start-up AdjustmentsMaintenance Introduction Inside Front Cover Warning   Explosion Hazards  ‹ Standards IndexProtection Systems UNPACKING/INSPECTIONLocation System SET LEDGenerator GfciFuel Consumption SpecificationsFuel Requirements Recommendations ‹ 1.6.1 Generator‹ 1.9.1 15KW, 990CC Engines Fuel System‹ 1.10.1 Generator ‹ 1.10.2 Transfer Switch Battery InstallationBattery 10.2.1 15 kW UnitsBefore Initial START-UP Check Transfer Switch OperationElectrical Checks Generator Tests Under Load Checking Automatic OperationAdjusting the Regulator Natural GAS only Dual Fuel RegulatorsBREAK-IN Procedure Voltage Regulator Adjustment‹ 2.7.1 15 KW Units ‹ 3.2.1 Auto Position ‹ 3.3.1 12 VDC Accessory OutletAutomatic Transfer Operation ‹ 3.2.2 OFF PositionManual Transfer Operation ‹ 3.5.1 Transfer to Generator Power SourceSequence of Automatic Operation ‹ 3.3.2 120 VAC Gfci Outlet‹ 3.7.1 LOW OIL Pressure Switch Setting the Exercise Timer‹ 3.5.2 Transfer Back to Utility Power Source ‹ 3.7.2 High Temperature SwitchFuses Checking the Engine OIL LevelChanging the Engine OIL Spark Plugs ‹ 4.3.2 OIL Change ProcedureChanging the OIL Filter ‹ 4.5.1 15 KW GeneratorsBattery Maintenance Adjusting Valve ClearanceCooling System Corrosion Protection‹ 4.12.1 Removal from Service OUT of Service Procedure‹ 4.12.2 Return to Service Service Schedule Be performed by the nearest dealerTroubleshooting Guide Problem Cause CorrectionMounting Dimensions Electrical Data Customer Connection KW Generator Electrical Schematic Drawing No E9017 SW1 Exploded Views and Parts Lists Part NO. QTY. Description KW Generator Control Panel Drawing No E9162-J Part NO. QTY Description 16B Item Part NO. QTY. Description 138 122 KNOB, AIR Cleaner Views and Parts Lists QTY Description KW Generator Gas Regulator Drawing No D8720-G CASTING, Twin Regulator Housing California and Federal Emission Control Warranty Statement Emission Control System Warranty Warranty Schedule