AEG 2.33 2 user manual Battery safety instructions

Page 20

20

Once the power supply is connected to the input of the UPS (with static bypass included or with an independent static bypass line), although the inverter is “Off” (shut-down), it does not mean that no output voltage is available at the output terminals.

To do this, it is required to switch (Q1a), (Q4) and (Q2) to position “Off”. It is possible that the UPS might be supplying output voltage from the manual bypass, so this must be considered for the purpose of safety. If the output power supply of the UPS has to be interrupted in this situation, deactivate the switch (Q5).

In devices with battery terminals, precautions must be taken as they are not electrically insulated from the alternating input line, and there might be dangerous voltage between the battery terminals and the ground.

4.1.1. Battery safety instructions

The manipulation and connection of the batteries shall be only be carried out and supervised by personnel with battery knowledge.

For units requested without batteries, the acquisition, installation and connection of the batteries will always be done by the customer and it is under his responsibility. The relevant information on the batteries (number, capacity and voltage) are indicated in the battery label pasted beside the nameplate of the equipment. Strictly respect this data, the battery polarity connection and the circuit diagram provided with this documentation.

The battery supply can involve the risk of electric shock and can produce high short circuit current. Observe the following preventive measures before manipulating any terminal block identified in the labeling as “Battery”:

Disconnect the corresponding protection elements.

When connecting a battery cabinet to the equipment, respect the cable’s polarity and color (red-positive; black-negative) indicated in the manual and in the corresponding labeling.

Wear rubber gloves and shoes.

Use tools with insulated handles.

Removes watches, rings or other metal objects.

Do not place metal tools or objects on the batteries.

Never manipulate directly with your hands or through conducting objects, do not short the battery terminal block or the battery enclosure.

Never short the battery terminals as it involves a high risk. It may result in damage to the equipment and batteries.

Image 20
Contents Protect 2.33 Contents Operation Maintenance, warranty and service Using this manual IntroductionSymbols and conventions used Safety and instructions For more information and helpQuality and standard guarantee Management declarationStandards Environmental protectionPresentation Views Views of the equipmentNot available for Protect 2.33 No -3 battery cabinet front view with front door closed Corresponding legends for the equipment views LCD Structure Structural schema Operating principleOperation with inverter not active Normal operationOperation with mains failure Operation in manual bypass Parallel operationThere are two operation modes possible Installation Important safety instructionsBattery safety instructions Cabinet access Bypass Input Output Set up and installation Unpacking and content checking Storage Transportation to siteLocation Connection To the mains connection, terminals X1 to Front view for parallel systemPage Connection of the output, terminals X6 to Page Interface relay contacts, connector Connection example between a UPS and two battery cabinetsCOM-interface RS232 and RS485, connector Connector DB9 X31Page EPO terminals Parallel BUS connectionParallel BUS Connection Start up Control before start up Start up procedureOperation Close Battery Switch Complete UPS shutdown LED indications control panel PCTransfer to maintenance bypass Emergency power off EPO operationBypass manual switch Maintenance Principle of operation Transfer to normal operation Close Battery Switch Control panel and display description Control panel partsTouch Screen Basic functions of keyboard from synopticControl panel parts Messages menus and classification in submenus MainMenu structure Screen description Main level screen menu Screen 0.0 Main ScreenUPS status control screen menu MainPage 3. ‘‘MEASURES level screen menu Page Page 4. ‘‘SETTINGS level screen menu Screen 3.0 Settings and its submenusModbus Screen Page Page 5. ‘‘ALARMS level screen menu UPS Rectifier blocks Alarm list displayed in the LCD panel Alarm Page Page Alarm Page Page Page Page Alarm Error in configuration memory 6. ‘‘DATA Logger level screen menu Screen 5.0 Data logger Page Maintenance, warranty and service Basic maintenance guideBattery fuses BatteriesCapacitors Warranty conditionsCooling Fan Annexes Static Bypass Type External battery cabinet Dimensions & Weight External Battery CabinetSafety Instructions To provide forPage Page Page Operating Instructions 8000032013 BAL, EN