37
Start up the loads to be supplied in a progressive way. The system is started up completely, and the loads are protected through the UPS.
2 | 1 |
| 3 |
Fig.25: LED indications control panel (PC)
a
b c
d e
5.2. Complete UPS shutdown
•Shutdown the loads.
•If the system has outgoing distribution protection, switch them “Off”.
•Shutdown the inverter. Through the keypad of the control panel ((3) from Fig.25), go down to “CNTL” submenu (screen 1.0), and select “OFF”.
You will get to screen 1.2, asking you to shut down the unit by pressing (ENT), see Fig.24.
•Turn the output switch (Q2) to “Off” position.
•Set the input switch (Q1a) to “Off” position.
•Turn fuse holder switch from battery cabinet (Q8) and/or battery fuse holder switch or switch from UPS (Q3), to “Off”.
•Cut the power supply of the UPS and the bypass with the
Electrical discharge hazard. If, after shutdown of the equipment, it is necessary to disconnect the separate battery pack/s, wait several minutes (5 min. approx), until the electrolytic capacitors have been discharged.
The equipment is completely shut down.