Emerson UPS Systems installation manual Installation Drawings

Page 23

Installation Drawings

Table 2 Liebert-supplied interconnect wiring for two-input Liebert NXL Maintenance Bypass Cabinet

Run

To

From

Conductor

 

 

 

 

A

Utility AC - Phase A

MBC Bypass AC - Phase A

Maintenance Bypass AC - Phase A

 

 

 

 

B

Utility AC - Phase B

MBC Bypass AC - Phase B

Maintenance Bypass AC - Phase B

 

 

 

 

C

Utility AC - Phase C

MBC Bypass AC - Phase C

Maintenance Bypass AC - Phase C

 

 

 

 

D

Utility Neutral

MBC Neutral

System Input Neutral

 

 

 

 

E

Utility Ground

MBC Ground

System Ground

 

 

 

 

F

MBC Bypass AC - Phase A

UPS Bypass AC - Phase A

UPS Bypass Input - Phase A

 

 

 

 

G

MBC Bypass AC - Phase B

UPS Bypass AC - Phase B

UPS Bypass Input - Phase B

 

 

 

 

H

MBC Bypass AC - Phase C

UPS Bypass AC - Phase C

UPS Bypass Input - Phase C

 

 

 

 

I

Utility Bypass AC - Phase A

UPS Rectifier AC - Phase A

UPS Rectifier Input - Phase A

 

 

 

 

J

Utility Bypass AC - Phase B

UPS Rectifier AC - Phase B

UPS Rectifier Input - Phase B

 

 

 

 

K

Utility Bypass AC - Phase C

UPS Rectifier AC - Phase C

UPS Rectifier Input - Phase C

 

 

 

 

L

MBC Neutral

UPS Bypass Neutral

UPS Neutral

 

 

 

 

M*

MBC Ground

UPS Equipment Ground

UPS Ground

 

 

 

 

N

UPS Output AC - Phase A

MBC Output AC - Phase A

UPS Output - Phase A

 

 

 

 

O

UPS Output AC - Phase B

MBC Output AC - Phase B

UPS Output - Phase B

 

 

 

 

P

UPS Output AC - Phase C

MBC Output AC - Phase C

UPS Output - Phase C

 

 

 

 

Q

MBC Output AC - Phase A

Load AC - Phase A

Load AC Input - Phase A

 

 

 

 

R

MBC Output AC - Phase B

Load AC - Phase B

Load AC Input - Phase B

 

 

 

 

S

MBC Output AC - Phase C

Load AC - Phase C

Load AC Input - Phase C

 

 

 

 

T

MBC Neutral

Load Neutral

Load Neutral

 

 

 

 

U

MBC Ground

Load Ground

Load Equipment Ground

 

 

 

 

V

MBC Terminal Strip

UPS External Interface Board

Control Wiring

 

 

 

 

* For detached units only

19

Image 23
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Interlock Control wiring connections withoutFrom Purpose Control wiring connections with interlockSection A-A Cabinet-to-Cabinet Liebert NXL Maintenance Bypass Cabinet specifications SpecificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Load Bank Output Recommended conduit and cable sizes-Module Bypass InputRecommended conduit and cable sizes-Module Output Recommended conduit and cable sizes-Load Output#4/0 AWG Recommended lug sizesSpecifications Page That Ne tIti Ti n