Emerson UPS Systems Specifications, Liebert NXL Maintenance Bypass Cabinet specifications

Page 30

Specifications

3.0SPECIFICATIONS

Table 6

Liebert NXL Maintenance Bypass Cabinet specifications

 

 

 

 

 

 

 

 

 

 

Model Size

 

250

 

300

 

400

 

 

 

 

 

 

 

Input Parameters

 

 

 

 

 

 

 

 

 

 

 

Input Voltage to Bypass, VAC

 

480V 3-phase, 3-wire or 4-wire

 

 

 

 

 

 

Permissible Input Voltage Range, VAC

 

 

 

+10% to -30%

 

 

 

 

 

 

 

 

 

Input Frequency, Hz

 

 

60

 

 

 

 

 

 

 

 

Permissible Input Frequency Range, Hz

 

 

 

55 to 65

 

 

 

 

 

 

 

Neutral Current

 

 

1.7 times full phase current

 

 

 

 

 

 

 

Output Parameters

 

 

 

 

 

 

 

 

 

 

 

Inverter Type

 

IGBT-based Sine-Sine PWM Controlled

 

 

 

 

 

 

 

 

Output Power, kW

 

225

 

270

 

360

 

 

 

 

 

 

 

 

 

Output Voltage, VAC

 

 

 

480V 3-ph, 4-w

 

 

 

 

 

 

 

 

 

Output Frequency, Hz

 

 

60

 

 

 

 

 

 

 

 

 

Physical Parameters & Standards, in (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Width in. (mm)

 

 

24.2 (615)

 

 

 

without side panels attached

 

 

 

 

 

 

 

 

 

 

 

 

Depth in. (mm)

 

33.5 (850)

 

33.5 (850)

 

39.4 (1000)

 

 

 

 

 

 

 

 

 

Height in. (mm)

 

 

76.8 (1950)

 

 

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

755 (342.5)

 

 

 

 

 

 

 

 

 

Color

 

 

Charcoal (ZP-0420)

 

 

 

 

 

 

 

Front Door Opening (for serviceability)

 

 

 

More than 180°

 

 

 

 

Degree of Protection for UPS Enclosure

 

IP 20 (with and without front door open)

 

 

 

 

 

 

 

 

 

 

 

 

UL 1778

 

 

 

 

 

 

CSA 22.2 107.3

 

 

Standards and Conformities

 

 

FCC Part 15, Class A

 

 

 

 

 

ISTA Procedure 1H

 

 

 

 

 

 

WEEE

 

 

 

 

 

 

 

 

 

Minimum clearance, Top, in (mm)

 

 

24 (610)

 

 

 

 

 

 

 

 

 

 

Minimum clearance, Back, in (mm)

 

 

0

 

 

 

 

 

 

 

 

Minimum clearance, Sides, in (mm)

 

 

0

 

 

 

 

 

 

 

 

 

 

Location of cable entrance

 

 

 

Top or Bottom

 

 

 

 

 

 

 

 

Environmental Parameters

 

 

 

 

 

 

 

 

 

 

 

Storage Temperature Range, °F (°C)

 

 

-13 to 158 (-25 to 70)

 

Operating Temperature Range, °F (°C)

 

 

 

0 to 40 (UPS)

 

 

 

 

 

 

Relative Humidity

 

Maximum 95% Non-Condensing

 

 

(Operating and Non-Operating)

 

 

 

 

 

 

 

 

 

 

4920 (1500) (as per IEC 62040/3) -

Maximum Altitude above MSL, ft (m)

1% maximum kW derate / 328 rise between 4921-9843

 

 

 

(100 rise between 1500-3000)

26

Image 30
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Control wiring connections without InterlockControl wiring connections with interlock From PurposeSection A-A Cabinet-to-Cabinet Specifications Liebert NXL Maintenance Bypass Cabinet specificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Load Output Recommended conduit and cable sizes-Module Bypass InputRecommended conduit and cable sizes-Module Output Recommended conduit and cable sizes-Load Bank OutputRecommended lug sizes #4/0 AWGSpecifications Page Ti n Ne tIti That