Emerson UPS Systems installation manual Recommended conduit and cable sizes-Module Bypass Input

Page 32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications

 

Table 11

Recommended conduit and cable sizes—Module Bypass Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Module Bypass Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating

 

System Input Voltage (VAC)

 

 

Nominal Selection

 

 

 

 

 

Alternate Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maint

 

 

 

Top Cable Entry

 

Bottom Cable Entry

 

 

Top Cable Entry

Bottom Cable Entry

 

kVA

kW

Rectifier

Bypass

Output

 

Wire & Conduit

 

Wire & Conduit

 

 

Wire & Conduit

Wire & Conduit

 

 

Byp

 

Ph, N, G,THW / FMC

 

Ph, N, G, THW / RNC

 

Ph, N, G, THW / FMC

Ph, N, G THW / RNC

 

250

225

 

480

480

 

480

480

 

(2) 3C 3-250kcmil,

 

(2) 3C 3-250kcmil,

 

(3) 2C 3-#2/0AWG,

(3) 2.5C 3-#2/0AWG,

 

 

 

 

2-250kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

 

2-#2/0AWG, #1/0AWG

2-#2/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

270

 

480

480

 

480

480

 

(2) 3.5C 3-350kcmil,

 

(2) 3.5C 3-350kcmil,

 

(3) 3C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

 

 

 

 

2-350kcmil, #1/0AWG

 

2-350kcmil, #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

360

 

480

480

 

480

480

 

(2) 4C 3-500kcmil,

 

(2) 4C 3-500kcmil,

 

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

 

 

 

 

2-500kcmil, #1/0AWG

 

2-500kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

2-250kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

450

 

480

480

 

480

480

 

(3) 3.5C 3-500kcmil,

 

(3) 4C 3-500kcmil,

 

(4) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

 

 

 

 

2-250kcmil , #1/0AWG

 

2-250kcmil , #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 12

Recommended conduit and cable sizes—Module Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

System

 

 

 

 

 

 

 

 

 

Module Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rating

 

 

Input Voltage (VAC)

 

 

 

 

Nominal Selection

 

 

 

 

 

Alternate Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maint

 

 

 

Top Cable Entry

 

Bottom Cable Entry

 

 

Top Cable Entry

Bottom Cable Entry

 

kVA

kW

Rectifier

Bypass

Output

 

Wire & Conduit

 

Wire & Conduit

 

 

Wire & Conduit

Wire & Conduit

 

 

Byp

 

Ph, N, G THW / FMC

 

Ph, N, G THW / RNC

 

Ph, N, G THW / FMC

Ph, N, G THW / RNC

 

250

225

 

480

480

 

480

480

 

(2) 3C 3-250kcmil,

 

(2) 3C 3-250kcmil,

 

(3) 2C 3-#2/0AWG,

(3) 2.5C 3-#2/0AWG,

 

 

 

 

2-250kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

 

2-#2/0AWG, #1/0AWG

2-#2/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

270

 

480

480

 

480

480

 

(2) 3.5C 3-350kcmil,

 

(2) 3.5C 3-350kcmil,

 

(3) 3C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

 

 

 

 

2-350kcmil, #1/0AWG

 

2-350kcmil, #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

360

 

480

480

 

480

480

 

(2) 4C 3-500kcmil,

 

(2) 4C 3-500kcmil,

 

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

 

 

 

 

2-500kcmil, #1/0AWG

 

2-500kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

2-250kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

450

 

480

480

 

480

480

 

(3) 3.5C 3-500kcmil,

 

(3) 4C 3-500kcmil,

 

(4) 3C 3-250kcmil,

(4) 3C 3-250kcmil,

 

 

 

 

2-250kcmil , #1/0AWG

2-250kcmil , #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 13

Recommended conduit and cable sizes—Load Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Rating

System Input Voltage (VAC)

 

Nominal Selection

 

 

 

 

 

Alternate Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maint

 

 

 

 

Top Cable Entry

 

Bottom Cable Entry

 

 

Top Cable Entry

Bottom Cable Entry

 

kVA

 

kW

Rectifier

Bypass

 

 

Output

 

Wire & Conduit

 

Wire & Conduit

 

 

Wire & Conduit

Wire & Conduit

 

 

 

Byp

 

Ph, N, G THW / FMC

 

Ph, N, G THW / FMC

 

Ph, N, G THW / FMC

Ph, N, G THW / FMC

 

250

 

225

480

 

480

 

 

480

 

480

 

 

(2) 3C 3-250kcmil,

 

(2) 3C 3-250kcmil,

 

 

(3) 2C 3-#2/0AWG,

(3) 2.5C 3-#2/0AWG,

 

 

 

 

 

 

 

2-250kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

 

2-#2/0AWG, #1/0AWG

2-#2/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

 

270

480

 

480

 

 

480

 

480

 

(2) 3.5C 3-350kcmil,

 

(2) 3.5C 3-350kcmil,

 

 

(3) 3C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

 

 

 

 

 

 

 

2-350kcmil, #1/0AWG

 

2-350kcmil, #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

480

 

480

 

 

480

 

480

 

 

(2) 4C 3-500kcmil,

 

(2) 4C 3-500kcmil,

 

 

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

 

 

 

 

 

 

 

2-500kcmil, #1/0AWG

 

2-500kcmil, #1/0AWG

 

2-250kcmil, #1/0AWG

2-250kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

450

480

 

480

 

 

480

 

480

 

(3) 3.5C 3-500kcmil,

 

(3) 4C 3-500kcmil,

 

 

(4) 3C 3-250kcmil,

(4) 3C 3-250kcmil,

 

 

 

 

 

 

 

2-250kcmil , #1/0AWG

 

2-250kcmil , #1/0AWG

 

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 14

Recommended conduit and cable sizes—Load Bank Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Rating

 

 

 

 

 

 

 

System Input Voltage, VAC

 

 

 

 

 

Load Bank Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal Selection

 

 

kVA

 

 

 

kW

 

 

 

Rectifier

 

Bypass

 

 

Maint Byp

 

Output

 

Front Cable Entry

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire-3W + GND

 

 

250

 

 

 

225

 

 

 

 

480

 

 

480

 

480

 

480

 

(1) 3-500kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

 

 

 

270

 

 

 

 

480

 

 

480

 

480

 

480

 

(2) 3-#4/0AWG, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

 

 

360

 

 

 

 

480

 

 

480

 

480

 

480

 

(2) 3-350kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

450

 

 

 

 

480

 

 

480

 

480

 

480

 

(2) 3-500kcmil, #1/0AWG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Image 32
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Control wiring connections without InterlockControl wiring connections with interlock From PurposeSection A-A Cabinet-to-Cabinet Specifications Liebert NXL Maintenance Bypass Cabinet specificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Module Bypass Input Recommended conduit and cable sizes-Module OutputRecommended conduit and cable sizes-Load Output Recommended conduit and cable sizes-Load Bank OutputRecommended lug sizes #4/0 AWGSpecifications Page Ne t ItiTi n That