Emerson UPS Systems Recommended conduit and cable sizes-Maintenance Bypass Input

Page 31

Specifications

Table 7

Liebert NXL Maintenance Bypass Cabinet current ratings—System Input

 

 

 

 

 

 

 

 

 

 

UPS Rating

 

Voltage (VAC)

 

System Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

10 Minute

External Breaker

 

kVA

 

kW

Input

 

Bypass

Output

Current

Overload

Trip, Amps

 

250

 

225

480

 

480

480

301

376

400

 

 

 

 

 

 

 

 

 

 

 

 

300

 

270

480

 

480

480

361

451

500

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

480

 

480

480

481

601

700

 

 

 

 

 

 

 

 

 

 

 

Table 8

Liebert NXL Maintenance Bypass Cabinet current ratings—System Output

 

 

 

 

 

UPS Rating

 

Voltage, VAC

 

System Output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

10 Minute

External Breaker

 

kVA

 

kW

Input

 

Bypass

Output

Current

Overload

Trip, Amps

 

250

 

225

480

 

480

480

301

376

400

 

 

 

 

 

 

 

 

 

 

 

 

300

 

270

480

 

480

480

361

451

500

 

 

 

 

 

 

 

 

 

 

 

 

400

 

360

480

 

480

480

481

601

700

 

 

 

 

 

 

 

 

 

 

 

 

Table 9

Recommended conduit and cable sizes—Maintenance Bypass Input

 

 

 

 

 

 

 

 

Maintenance Bypass Input

 

 

 

 

 

 

UPS Rating

System Input Voltage (VAC)

Nominal Selection

Alternate Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maint

 

Top Cable Entry

Bottom Cable Entry

Top Cable Entry

Bottom Cable Entry

kVA

kW

Rectifier

Bypass

Output

Wire & Conduit

Wire & Conduit

Wire & Conduit

Wire & Conduit

Byp

Ph, N, G THW / FMC

Ph, N, G THW / RNC

Ph, N, G THW / FMC

Ph, N, G THW / RNC

250

225

480

480

480

480

(2) 3C 3-250kcmil,

(2) 3C 3-250kcmil,

(3) 2C 3-#2/0AWG,

(3) 2.5C 3-#2/0AWG,

2-250kcmil, #1/0AWG

2-250kcmil, #1/0AWG

2-#2/0AWG, #1/0AWG

2-#2/0AWG, #1/0AWG

 

 

 

 

 

 

300

270

480

480

480

480

(2) 3.5C 3-350kcmil,

(2) 3.5C 3-350kcmil,

(3) 3C 3-#4/0AWG,

(3) 3C 3-#4/0AWG,

2-350kcmil, #1/0AWG

2-350kcmil, #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

400

360

480

480

480

480

(2) 4C 3-500kcmil,

(2) 4C 3-500kcmil,

(3) 3C 3-250kcmil,

(3) 3C 3-250kcmil,

2-500kcmil, #1/0AWG

2-500kcmil, #1/0AWG

2-250kcmil, #1/0AWG

2-250kcmil, #1/0AWG

 

 

 

 

 

 

500

450

480

480

480

480

(3) 3.5C 3-500kcmil,

(3) 4C 3-500kcmil,

(4) 3C 3-250kcmil,

(4) 3C 3-250kcmil,

2-250kcmil , #1/0AWG

2-250kcmil , #1/0AWG

2-#4/0AWG, #1/0AWG

2-#4/0AWG, #1/0AWG

 

 

 

 

 

 

Table 10 Recommended conduit and cable sizes—Rectifier Input (1-Input System)

 

 

 

 

 

 

 

Rectifier Input (1-Input System)

 

 

 

 

 

 

UPS Rating

System Input Voltage (VAC)

Nominal Selection

Alternate Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maint

 

Top Cable Entry

Bottom Cable Entry

Top Cable Entry

Bottom Cable Entry

kVA

kW

Rectifier

Bypass

Output

Wire & Conduit

Wire & Conduit

Wire & Conduit

Wire & Conduit

Byp

Ph, N, G, THW / FMC

Ph, N, G THW / RNC

Ph, N, G THW / FMC

Ph, N, G THW / RNC

250

225

480

480

480

480

(2) 2.5C 3-250kcmil,

(2) 2.5C 3-250kcmil,

(3) 2C 3-#2/0AWG,

(3) 2C 3-#2/0AWG,

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

300

270

480

480

480

480

(2) 3C 3-350kcmil,

(2) 3C 3-350kcmil,

(3) 2.5C 3-#4/0AWG,

(3) 2.5C 3-#4/0AWG,

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

400

360

480

480

480

480

(2) 3C 3-500kcmil,

(2) 3.5C 3-500kcmil,

(3) 2.5C 3-250kcmil,

(3) 2.5C 3-250kcmil,

#1/0AWG

#1/0AWG

#1/0AWG

#1/0AWG

 

 

 

 

 

 

500

450

480

480

480

480

(3) 3C 3-500kcmil,

(3) 3.5C 3-500kcmil,

(4) 2.5C 3-250kcmil,

(4) 3C 3-250kcmil,

#2/0AWG

#2/0AWG

#2/0AWG

#2/0AWG

 

 

 

 

 

 

27

Image 31
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Interlock Control wiring connections withoutFrom Purpose Control wiring connections with interlockSection A-A Cabinet-to-Cabinet Liebert NXL Maintenance Bypass Cabinet specifications SpecificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Load Bank Output Recommended conduit and cable sizes-Module Bypass InputRecommended conduit and cable sizes-Module Output Recommended conduit and cable sizes-Load Output#4/0 AWG Recommended lug sizesSpecifications Page That Ne tIti Ti n