Specifications
Notes
See the Liebert NXL UPS installation manual,
These are guidelines only and are superseded by local regulations and codes of practice where appli- cable.
•Take special care when determining the size of the neutral cable, as current circulating on the neutral cable may be greater than nominal current in the case of
•The ground conductor should be sized according to the fault rating, cable lengths, type of protec- tion, etc. The ground cable connecting the UPS to the main ground system must follow the most direct route possible.
•Consideration should be given to the use of smaller, paralleled cables for heavy currents, as a way to ease installation.
•In most installations, the load equipment is connected to a distribution network of individually protected busbars fed by the maintenance bypass cabinet output rather than being connected directly to the Maintenance bypass cabinet itself. Where this is the case, the maintenance bypass cabinet output cables can be rated to suit the individual distribution network demands rather than being fully
•When laying the power cables, do not form coils to avoid increasing formation of electromagnetic interference.
Table 15 Recommended lug sizes
Cable Size | T&B Series 54000 |
| Two Hole |
|
|
#8 AWG | 54850BE |
|
|
#6 AWG | |
|
|
#4 AWG | |
|
|
54811BE | |
|
|
#1 AWG | 54857BE |
|
|
#1/0 AWG | |
|
|
#2/0 AWG | 54862BE |
|
|
#3/0 AWG | 54864BE |
|
|
#4/0 AWG | 54866BE |
|
|
250kcmil | 54868BE |
|
|
300kcmil | 54870BE |
|
|
350kcmil | 54872BE |
|
|
400kcmil | 54874BE |
|
|
500kcmil | 54876BE |
|
|
600kcmil | 54878BE |
|
|
750kcmil | 54880BE |
|
|
Use the T&B crimping tools recommended for these types of lugs.