Emerson UPS Systems installation manual Power Cables

Page 8

Single-Module Mechanical Installation

1.6Power Cables

The Maintenance Bypass Cabinet requires both power and control cabling once it has been mechani- cally installed. All control cables must be separate from the power cables. Run control cables in metal conduits or metal ducts that are electrically bonded to the cabinets they are connected to.

The cable design must comply with the voltages and currents provided in Tables 7 and 8, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media).

For cable entry terminal, refer to Figure 9.

! WARNING

Before cabling up the cabinet, ensure that you are aware of the location and operation of the external isolators that connect the input/bypass supply.

Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.

The following are guidelines only and superseded by local regulations and codes of practice where applicable:

Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non- linear loads. Refer to Tables 7 and 8.

The grounding conductor should be sized according to the fault rating, cable lengths, type of pro- tection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.

Consider using smaller, paralleled cables for heavy currents as a way of easing installation.

Figure 1 Cabinet arrangement—Liebert NXL UPS, battery cabinets, maintenance bypass cabinet

Liebert

NXL

UPS

Liebert

NXL

UPS

Maintenance

Bypass

Cabinet

Note: If a maintenance bypass cabinet is used, it must be installed on the right side of the Liebert NXL UPS

Additional

Battery

Liebert

Maintenance

Battery

NXL

Bypass

Cabinet

Cabinet(s)

 

UPS

Cabinet

 

 

 

Additional

Battery

Cabinet(s)

Battery Cabinet

Liebert

NXL

UPS

Liebert

NXL

UPS

Battery Cabinet

Additional

Battery

Cabinet(s)

4

Image 8
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Control wiring connections without InterlockControl wiring connections with interlock From PurposeSection A-A Cabinet-to-Cabinet Specifications Liebert NXL Maintenance Bypass Cabinet specificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Module Bypass Input Recommended conduit and cable sizes-Module OutputRecommended conduit and cable sizes-Load Output Recommended conduit and cable sizes-Load Bank OutputRecommended lug sizes #4/0 AWGSpecifications Page Ne t ItiTi n That