Emerson UPS Systems installation manual Positioning

Page 7

Single-Module Mechanical Installation

1.3.2Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Table 6).

1.4Positioning

The cabinet is structurally designed to handle lifting from the base.

Access to the power terminals, auxiliary terminals blocks and power switches is from the front.

The top and front removable panels are secured to the chassis by screws. The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. Front door can be opened at 180° for better Service and more flexibility in installations.

1.4.1Moving the Cabinets

The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).

Ensure that the cabinet weight is within the designated surface weight loading (kg/cm2) of any han- dling equipment. See Table 6 for weight.

Ensure that any lifting equipment used in moving the cabinet has sufficient lifting capacity.

The Maintenance Bypass Cabinet can be handled by means of a fork lift or similar equipment. For operations with a fork lift, refer to installation drawings in 2.0 - Installation Drawings.

Because the weight distribution in the cabinet is uneven, use extreme care during handling and transporting.

When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.

Handling the unit with straps is not authorized.

! CAUTION

Take extreme care when handling Maintenance Bypass Cabinets to avoid equipment damage or injury to personnel.

1.4.2Clearances

Liebert NXL Maintenance Bypass Cabinets have no ventilation grilles at either side or at the rear. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.

1.4.3Floor Installation/Anchoring

The installation diagrams in 2.0 - Installation Drawings of this manual identify the location of the holes in the base plate through which the equipment can be bolted to the floor. If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equip- ment point loading. Refer to the base view to design this pedestal.

1.5Cable Entry

Cables can enter the Maintenance Bypass Cabinet from the bottom or top.

3

Image 7
Contents Liebert NXL Maintenance Bypass Cabinet Product Warranty Registration Table of Contents Figures Important Safety Instructions Introduction Positioning Power Cables Power Cable Connection Procedure Single-Module Mechanical Installation Installation Drawings Two-Breaker Maintenance Bypass Cabinet, two-input, attached Busbar Detail B Front Section A-A Bottom View Footprint Bottom View Footprint TOP View BUS BAR Detail a BUS Termination Detail Cable routing Front Run From Conductor Bypass Installation Drawings P1 D T Installation Drawings Interlock Control wiring connections withoutFrom Purpose Control wiring connections with interlockSection A-A Cabinet-to-Cabinet Liebert NXL Maintenance Bypass Cabinet specifications SpecificationsRecommended conduit and cable sizes-Maintenance Bypass Input Recommended conduit and cable sizes-Load Bank Output Recommended conduit and cable sizes-Module Bypass InputRecommended conduit and cable sizes-Module Output Recommended conduit and cable sizes-Load Output#4/0 AWG Recommended lug sizesSpecifications Page That Ne tIti Ti n