UM581127000 | User Instructions |
Issue AB, March 22, 2012 | Spec. No. 581127000 (Model 710NPBA) |
|
|
Optional LVD Driver Circuit Card
The optional LVD driver circuit card contains an LVD inhibit switch and indicator. Refer to Figure
Caution: If the switch is returned to the ON (normal) position when low voltage disconnect alarms are active, a low voltage disconnection will occur.
Warning: While the LVD inhibit switch is in the OFF (inhibit) position, a low voltage disconnection will not occur if battery or load voltage decreases below the low voltage disconnect setpoint. For maximum battery protection, this switch should NOT be left in the OFF (inhibit) position.
J6 | J5 | J4 |
|
J9 |
|
|
|
| J3 | J2 | J1 |
J7 |
|
|
|
| S1 |
|
|
LVD Inhibit
Active Indicator
Illuminates when the low voltage disconnect circuit has been disabled through the use of the LVD Inhibit switch.
Note: The UP position will not close the LVBD contactor
LVD Inhibit Switchif the battery is manually disconnected using the Manual Battery Disconnect Switch.
Momentary UP / Middle / Down
Momentary UP Position: Closes all LVD Contactors (inhibit mode).
Middle Position: OFF (ACU+ DOES NOT control LVD’s) (inhibit mode).
DOWN Position: ON (ACU+ controls LVD’s).
Figure
Optional LVD Driver Circuit Card (P/N 540972)
Page 6 | Chapter 2. Operating Procedures |