SM-DU+ and Shunt Interface Assembly Replacement

Procedure

1)Performing this procedure may activate external alarms. Do one of the following. If possible, disable these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard any future alarms associated with this system while the procedure is being performed.

Danger: Performing the next steps exposes service personnel to battery potential. Exercise extreme caution not to inadvertently contact or have any tool inadvertently contact any energized electrical termination.

2)Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.

Warning: Damage to the circuit card may result if the next step is not followed.

3)Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.

4)Carefully label the wires connected to the shunt input terminal blocks on circuit card. These wires must be connected to the same terminals on the replacement circuit card. Refer to Figure 4-12.

5)Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the same connectors on the replacement circuit card. Refer to Figure 4-12.

Danger: In the next step, external wiring may be energized from an external source. DO NOT allow bare wire ends to contact any grounded or energized object.

6)Remove the external wiring from the shunt input terminal blocks. DO NOT allow the bare wire end to contact any grounded or energized object. Isolate the wire end with electrical tape. Repeat for each wire to be removed.

7)Unplug all connectors plugged into the circuit card.

8)Remove the screw securing the SM-DU+ and Shunt Interface Assembly to the bottom of the distribution cabinet, and remove the assembly.

9)SM-DU+:In this step, ensure you do not intermix the old and replacement circuit cards. Set the switches on the replacement circuit card to the same settings as the old circuit card. Switch settings are documented in CHAPTER 3. SETTING JUMPERS AND SWITCH OPTIONS of the Power System Installation Instructions (IM581127000).

10)Slide the replacement SM-DU+ and Shunt Interface Assembly into the mounting position inside the distribution cabinet, and secure with the screw removed from the old assembly.

11)Plug all connectors removed from the old circuit card into the same position on the replacement circuit card.

Danger: In the next step, external alarm wiring may be energized from an external source. DO NOT allow bare wire ends to contact any grounded or energized object.

12)Reconnect the external wiring to the correct terminals on the shunt input terminal blocks. First remove the electrical tape that was applied to the bare wire end in a previous step. DO NOT allow the bare wire end to contact any grounded or energized object. After securing the wire, gently tug on the wire to ensure that it

Page 36

Chapter 4. Troubleshooting and Repair

This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy

Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.

Image 42
Contents UM581127000 Issue AB, March 22 User InstructionsSPEC. NO. Model 581127000 710NPBA Page Table of Contents Voltages General SafetyBattery AC Input Voltages DC Input/Output VoltagesCircuit Card Handling Static Warning System Description Bound System Installation ManualCustomer Documentation Package USB Drive with All Customer DocumentationACU+ Advanced Control Unit Plus Controller Module Mounting AssemblyDistribution Cabinet Rectifier ModulesCONTROLLER, RECTIFIERS, and Optional Converters Local Controls and IndicatorsRefer to Figure Operating Procedures Estop FunctionCircuit Card Locations Operating Procedures IB2System Interface Circuit Card Optional LVD Driver Circuit Card P/N Operating Procedures Optional LVD Driver Circuit CardOptional LVD Driver Lite Circuit Card Optional Manual Battery Disconnect Circuit Card Middle Position Normal OperationSystem Maintenance Procedures Installers connectionsMaintenance Procedures to be Performed at 6-Month Intervals User Instructions Issue AB, March 22 Spec. No Model 710NPBA ProcedureInstalling a Field Expansion Module Mounting Assembly User Instructions Spec. No Model 710NPBA Spec. No Model 710 Npba Issue AB, March 22 Communications Cables MaintenanceChanging the ACU+ LVD Control Level for a Contactor Troubleshooting Alarm Conditions on the ACU+ Controller ACU+ Controller ConfigurationSystem Troubleshooting Information Contact InformationProcedure Clearing a Rectifier Lost Alarm Clearing a Converter Lost AlarmReplacing a Rectifier or Converter Module Replacement InformationReplacement Procedures Replacing the ACU+ ControllerDistribution Fuse Alarm Fuse Replacement Replacing a Distribution DeviceGeneral Replacing a TPS/TLS Fuse Procedure Fuseholder AssemblyReplacing a Bullet Nose Fuseholder Procedure Into corresponding sockets Replacing a Bullet Nose Circuit Breaker ProcedureInsert these terminals On distribution panelReplacing a TPH Fuse Procedure Replacing a TPL-B Fuse Troubleshooting and Repair Replacing a GJ/218 Circuit Breaker Procedure Installing Circuit Breaker Pole breaker shown Pole and 4-pole breakers similar List AC Only List BC Only Circuit Card Replacement Procedures Issue AB, March 22 Spec. No Model 710 NpbaSystem Interface Circuit Card Replacement Procedure UM581127000 TB2 Spec. No Model 710NPBA Issue AB, March 22 Relay Optional EIB Interface Board Assembly Top View SM-DU+ and Shunt Interface Assembly Replacement Procedure UM581127000 SM-DU+ Spec. No Model 710NPBA Issue AB, March 22 UM581127000 UM581127000 User Instructions Issue AB, March 22 Spec. No Model 710NPBA UM581127000 Procedure Removing the Distribution Panel Replacing a Distribution PanelInstalling the Distribution Panel Replacing a Distribution Panel Troubleshooting and Repair Installing the Replacement Contactor Replacing a Battery or Load Disconnect ContactorProcedure Removing the Contactor Restarting the Power SystemWhite/Black Wire Spec. No Model 710 Npba Issue AB, March 22 Black Wire Load Disconnect Change Issue Number Description of Change LLP215523 New LLP216783 Misc. updates Revision RecordFor More Information NetPerform Optimization ServicesDownload service & maintenance reports Online Answers technical product and system