Connectivity Module | ASCO 940/962 ATSs |
Device Configurator Screen for ASCO 940/962 ATSs
The Device Configurator Screen for ASCO 940/962 ATSs shows the Group 7A controller configuration settings (right side) and the Connectivity Module (server) configuration settings (left) for the selected ATS.
Group 7A Controller Configuration (right side)
Enter or change the ATS Name (18 char. max.) and ATS Nominal Voltage (must be entered to get correct reading). Press the Update button when finished to save the Group 7A controller configuration changes.
Connectivity Module (server) Configuration (left side)
Several configuration settings must be set appropriately as described below. Press the Update Server button when finished to save configuration changes.
Consult with your network administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
ports
Serial Port Speed 9600
Flow Control No flow control
Interface Mode
Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)
ATS Name | Nom. Voltage |
xxx
Press Update button when finished to save the configuration
Press Update Server button when finished to save the configuration changes.
Consult with your network administrator for these 4 settings:
IP Address
Subnet Mask
Gateway Address
TCP Port Number
(Range of ports allowed is:
ports
Serial Port Speed 9600 Flow Control No flow control Interface Mode
Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)
Device Configurator Screen without Power Manager
ATS Name | Nom. Voltage |
xxx
Press Update button when finished to save the configuration
Press Update Server button when finished to save the configuration changes.