Emerson 5100 Connectivity Module Snmp Internet-standard Protocol A-5, Snmp Trap messages

Page 31

Connectivity Module

SNMP Internet-standard Protocol A-5

How to set SNMP (Simple Network Management Protocol) Configuration

Firmware 869764-003 and higher provides SNMP configuration.

1.On the Device Configuration screen (page 2-1 or 3-1) click the SNMP button at the bottom.

2.On the SNMP Configuration screen click the check box ; SNMP Enabled (to enable it).

3.Assign the Community name for READ and

Community name for WRITE.

4.Assign the SNMP Manager IP Addresses. Start with the 1 IP address and be sure the addresses have 4 octets where each octet has 3 digits in it. Click the Close button. xxx.xxx.xxx.xxx

5.Review all settings, then click Update Server button to save the configuration settings.

SNMP TRAP messages

With SNMP enabled the CM can notify changes on ATS status and power metering conditions by sending TRAP messages. The changes listed below are regarded as alarms and are strictly monitored during runtime.

1.ATS transfer to emergency source

2.ATS retransfer to normal source

3.Engine running

4.Normal source unavailable

5.Emergency source unavailable

6.Power manager digital inputs 1 to 8 activation.

7.Power manager digital outputs 1 to 4 activation

Device Configuration Screen (see page 2-1 or 3-1)

SNMP Configuration Screen

RESET

button

RESET button on CM

Image 31
Contents 381333-367 C Connectivity ModuleImportant information Who Should Use this Installation ManualIi Welcome Connectivity Module PrerequisitesDIP Switch on bottom of unit SpecificationsInstallation Overview Check the DIP Switch Settings for RS485Iv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Status LEDs LED Description LED Function / Mode of OperationConnectivity Module Status LEDs How to Install the Connectivity Module on Asco 940/962 ATSs InstallationHow to Test Communication to the Connectivity Module Connectivity Module InstallationInstallation Connectivity Module Http//169.254.1.1/config.htmDevice Configurator Screen for 7000 & 4000 Series ATSs Device Configurator Screen for 7000 & 4000 Series ATSsGroup 5 Controller Configuration right side Connectivity Module server Configuration left sideInput Name & Output Names Power Manager only Power Manager or Power Meter Configuration7000 & 4000 Series ATSs Connectivity Module Accessory 85 Descriptive Tags Assigned Detail Screen for 7000 & 4000 Series ATSs Connectivity Module Series 300 ATSs Device Configurator Screen for Series 300 ATSsGroup 1 Controller Configuration right side Device Configurator Screen for Series 300 ATSsSeries 300 ATSs Connectity Module Power MeterDetail Screen for Series 300 ATSs Detail Screen for Series 300 ATSs with a Power ManagerPage Device Configurator Screen with Power Manager Device Configurator Screen for Asco 940/962 ATSsGroup 7A Controller Configuration right side Device Configurator Screen without Power ManagerDetail Screen for Asco 940/962 ATSs Detail Screen for Asco 940/962 ATSs with a Power ManagerAsco 940/962 ATSs Connectivity Module Input names Display Input & Output Names screen Output names Detail Screen for Digital Power Meters connected to a Load Detail Screen for Power Managers connected to a LoadDetail Screen for Power Detail Screen for Power Managers connected to a GeneratorDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Problem Cause Connectivity Module Troubleshooting A-3Read Requests Third Party Modbus Device ConfigurationSnmp Trap messages Connectivity Module Snmp Internet-standard Protocol A-5Snmp Internet-standard Protocol Connectivity Module Problem Cause SolutionSerial No Row IP Address Subnet Mask GatewayCatalog No Address set ATS Controller PM or DPM Communication Address Form for Connectivity Module CM Communication Address Form for Connectivity Module CM Index