Emerson 5100 installation manual Device Configurator Screen for 7000 & 4000 Series ATSs

Page 13

Connectivity Module

7000 & 4000 Series ATSs 2-1

Device Configurator Screen for 7000 & 4000 Series ATSs

The Device Configurator Screen for 7000 & 4000 Series ATSs shows the Group 5 controller configuration settings (right side) and Connectivity Module (server) configuration settings (left side) for the selected ATS.

Group 5 Controller Configuration (right side)

Enter or change the ATS Name (8 char. max.)and the ATS Location (20 char. max.). Press the Update button when finished to save the controller configuration changes.

Connectivity Module (server) Configuration (left side)

Several configuration settings must be set appropriately as described below. Press the Update Server button when finished to save configuration changes.

Consult with your network administrator for these 4 settings:

IP Address

Subnet Mask

Gateway Address

TCP Port Number

(Range of ports allowed is:

10024-65535, but do not use

ports 14000-14009 or 30718)

Serial Port Speed 19200

Flow Control No flow control

Interface Mode RS485-4 or 2 Wire

Encyrption enable check box and assign an AES port (same range as TCP port but do not use the same port number used for TCP port.)

3rd party device running own protocols

SNMP refer to Appendix A-5

ATS Name

ATS Location

Press Update button when finished to save the configuration changes. Do this before you press Update Server button.

After Controller has been updated, press Update Server button to save the configuration changes.

Device Configurator Screen for 7000 & 4000 Series ATSs

When a Power Manager or Digital Power Meter is connected, additional buttons appear at the bottom of the Connectivity Module Device Configuration screen.

Press to configure the Power

Manager or Digital Power Meter.

Press to configure the Group 5 Controller.

After Controller, PM, or DPM has been updated, press Update Server button to save the configuration

Additional Buttons on Device Configurator Screen for

7000 & 4000 Series ATSs with Power Manager or Digital Power Meter

Image 13
Contents 381333-367 C Connectivity ModuleIi Welcome Connectivity Module Who Should Use this Installation ManualPrerequisites Important informationInstallation Overview SpecificationsCheck the DIP Switch Settings for RS485 DIP Switch on bottom of unitIv Outline and Mounting Drawing Connectivity Module Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Vii Wiring Diagrams Connectivity Module Connectivity Module Wiring Diagrams Status LEDs LED Description LED Function / Mode of OperationConnectivity Module Status LEDs How to Install the Connectivity Module on Asco 940/962 ATSs InstallationHow to Test Communication to the Connectivity Module Connectivity Module InstallationInstallation Connectivity Module Http//169.254.1.1/config.htmGroup 5 Controller Configuration right side Device Configurator Screen for 7000 & 4000 Series ATSsConnectivity Module server Configuration left side Device Configurator Screen for 7000 & 4000 Series ATSsInput Name & Output Names Power Manager only Power Manager or Power Meter Configuration7000 & 4000 Series ATSs Connectivity Module Accessory 85 Descriptive Tags Assigned Detail Screen for 7000 & 4000 Series ATSs Group 1 Controller Configuration right side Device Configurator Screen for Series 300 ATSsDevice Configurator Screen for Series 300 ATSs Connectivity Module Series 300 ATSsSeries 300 ATSs Connectity Module Power MeterDetail Screen for Series 300 ATSs Detail Screen for Series 300 ATSs with a Power ManagerPage Group 7A Controller Configuration right side Device Configurator Screen for Asco 940/962 ATSsDevice Configurator Screen without Power Manager Device Configurator Screen with Power ManagerDetail Screen for Asco 940/962 ATSs Detail Screen for Asco 940/962 ATSs with a Power ManagerAsco 940/962 ATSs Connectivity Module Input names Display Input & Output Names screen Output names Detail Screen for Digital Power Meters connected to a Load Detail Screen for Power Managers connected to a LoadDetail Screen for Power Detail Screen for Power Managers connected to a GeneratorDetail On Local Area Connection Properties screen Select All Programs Accessories Command Prompt Problem Cause Connectivity Module Troubleshooting A-3Read Requests Third Party Modbus Device ConfigurationSnmp Trap messages Connectivity Module Snmp Internet-standard Protocol A-5Snmp Internet-standard Protocol Connectivity Module Problem Cause SolutionSerial No Row IP Address Subnet Mask GatewayCatalog No Address set ATS Controller PM or DPM Communication Address Form for Connectivity Module CM Communication Address Form for Connectivity Module CM Index