FRAMING

It is best to frame your fireplace after it is positioned and the vent system is installed. Use 2x4’s and frame to local build- ing codes.

Note: In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the fi replace body, it is recommended that the walls of the fi replace enclosure

CLEARANCE TO COMBUSTIBLES

MAINTAIN THESE MINIMUM CLEARANCES TO COM- BUSTIBLES:

Fireplace framing - 0” to stand-offs (top, rear & sides) Fireplace finishing - 4” to sides of fireplace opening.

FIGURE 30

- 21 3/4” to top of fireplace opening.

be “fi nished” (ie: drywall/sheetrock), as you would fi nish any other outside wall of a home. This will ensure that clearance to combustibles is maintained within the cavity.

For convenience, the stand-offs have been shipped fl at. Be- fore framing, ensure the stand-offs are opened and screwed in place.

It is not necessary to install a hearth extension, but the fi re- place should be raised to be fl ush with either the hearth or the fi nished fl oor.

When roughing in the fi replace, raise the fi replace to accom- modate for the thickness of the fi nished fl oor materials, i.e. tile, carpeting, hard wood.

NON-COMBUSTIBLE FINISHING MATERIAL

 

 

 

Non-combustible

 

 

 

finishing material

 

 

 

(ie: cement board,

 

 

 

21

3/4"

 

brick, stone, tile)

 

 

 

may be used to fi n-

 

 

 

 

 

 

ish the front of the

 

 

 

unit.

59 3/8"

Objects placed in front of the fi replace should be kept a mini- mum of 48” away from the front face.

4" 24" 4"

32"

1"

 

 

 

MIN

 

 

 

44"

 

 

 

1"

 

"

FIGURE 28

MIN

29"

1/8

 

62

 

IMPORTANT:

T h e requires a minimum inside enclo- sure height of 72”.

For temperature require- ments, this area must be left unobstructed.

It is recommended that the enclosure be ventilat- ed at the top and bottom to circulate the hot air.

COMBUSTIBLE

MATERIAL

FIRESTOP

 

SPACER

2"

STUD

 

 

2"

STAND OFF

 

SPACER

 

72"

72"

58 1/2"

29"

22 1/2"

FIGURE 29

22 1/2"

 

29"

10"

 

MIN

W415-0583 / D / 07.24.07

 

FIGURE 31

NON-COMBUSTIBLE

WARNING

Facing and/or finishing

material must never

overhang into the fireplace

opening.

Do not distort or force the frame

kit components.

When using a rough finish materi- al (i.e.; stone), maintain a ¼” - ½” border from the framing components.

Image 14 Contents
Installation Operation Instructions Table of Contents Napoleon GAS Fireplace PRESIDENT’S Lifetime Limited Warranty General Instructions General InformationVenting Lengths & AIR Terminal Locations VentingCare of Glass Elbow Vent Length Values TOP Exit / Horizontal TerminationDefinitions Since both formulas are met, this vent confi guration is ac HT + VT= 10.7 + 6 =16.7VT = 4.2 x 6 = 25.2 ft CeptableTOP Exit Vertical Termination TOP Vertical TerminationW415-0583 / D Installation Wall and Ceiling Protection Vertical Installation Horizontal InstallationVertical AIR Terminal Installation Using Flexible Vent ComponentsHorizontal AIR Terminal Installation Extended Horizontal AIR Terminal Installation Using Rigid Vent ComponentsVertical Venting Installation Fireplace Vent ConnectionRestricting Vertical Vents GAS InstallationMobile Home Installation Framing Clearance to CombustiblesElectrical Connection Hard Wiring ConnectionElectrical Schematic Mantle ClearancesFinishing / Servicing BOWL, Mesh & Rock Replacement Burner Base RemovalTurn off the power to the fi replace Turn off the gas valve Blower ReplacementBattery Replacement Time OUT Night Lighttm ReplacementOperation / Maintenance Fireplace OperationHand Held Remote Operations Flame HeightFAN Speed Setting Address Setting Procedure DIP Switch Number 0 = on / 1 = OFF Lighting Instructions Operating InstructionsWhat to do if YOU Smell GAS To Turn OFF GASPilot Burner Adjustment AdjustmentsMaintenance Flame CharacteristicsClosing the air shutter Venturi AdjustmentConversion KIT Replacements 000 Trouble Shooting Guide Symptom Problem Test SolutionBurner is in ‘OFF’ Supply working pressure Position Pilot goes out while Gas piping is undersizedStanding Main Fireplace Service History W415-0583 / D