| Troubleshooting the ICA | |
|
|
|
| |
| Table | |||
| Symptom |
| Recommendation | |
|
| |||
|
|
|
|
|
| Modem is not |
| Run the ICAP program directly to the ICA to | |
| connecting |
| determine if the adapter is functioning and all | |
|
|
| connections to the adapter are correct. | |
| ICA and inverter |
| DC power was cycled on the inverter with ICAP |
|
| spontaneously jump |
| already running. This does not cause harm to the | |
| menus or give false |
| system; it is just a nuisance. To avoid it, make sure | |
| indicators |
| ICAP is started after the inverter is powered up. | |
|
|
|
|
|
Troubleshooting if No Response comes from the ICA
Check ID
If the ICA is not responding, ensure you have the correct “ICA unit number” selected on the ICAP user interface window, see figure
Reset Defaults
If the ICA is still not responding, then click on the “RESET TO DEFAULT” button, click “OK” (see figure
Check Settings
If there is still no response from the ICA, then check your settings.
•Ensure you are selecting the correct COM port
•Ensure your computer communication baud rate is fixed at 9600 Baud.
41 |