Safety
Operational Safety Procedures
Never work alone when servicing this equipment. A team of two is required until the equipment is properly
Thoroughly inspect the equipment prior to energizing. Verify that no tools or equipment have inadvertently been left behind.
Lockout and Tag
Safety requirements mandate that this equipment not be serviced while energized. Power sources for the Ethernet Communications Kit must be
WARNING: Shock Hazard
Review the system schematic for the installation to verify that all available energy sources are
The Inverter can be energized from both the AC source and the DC source. To ensure that the inverter is
1.Turn the Inverter main ON/OFF switch (S3) to the OFF position. This stops the inverter from exporting power to the AC utility grid.
2.Open, lockout, and tag the incoming power at the utility main circuit breaker.
3.Open, lockout, and tag the AC Disconnect (CB1) on the left door of the Inverter enclosure. See your GT100 or GT250 Grid Tie Inverter manual for the location of the AC Disconnect.
viii | 153553 |
This guide for use by qualified personnel only