2 Installation and safety considerations

Installation and safety considerations

You can install the Brocade ICX 6650 in the following ways:

As a standalone unit on a flat surface.

In an EIA cabinet using a fixed-rail rack mount kit. The optional fixed-rail rack mount kit can be ordered from your switch retailer. Both the 24”-28” rack depth kit and the 28”-32” rack depth kit will work with the ICX 6650 device.

In a 2-post Telco rack using a flush mount rack kit. The optional flush mount rack kit for switches can be ordered from your switch retailer.

In a 2-post Telco rack using a mid-mount rack kit. The optional mid-mount rack kit for switches can be ordered from your switch retailer.

Electrical considerations

To install and operate the switch successfully, ensure compliance with the following requirements:

The primary outlet is correctly wired, protected by a circuit breaker, and grounded in accordance with local electrical codes.

The supply circuit, line fusing, and wire size are adequate, as specified by the electrical rating on the switch nameplate.

The power supply standards are met.

Environmental considerations

For successful installation and operation of the switch, ensure that the following environmental requirements are met:

Because the Brocade ICX 6650 can be ordered with fans that move air either front to back or back to front, be sure to orient your switch with the airflow pattern of any other devices in the rack. All equipment in the rack should force air in the same direction to avoid intake of exhaust air.

The ambient air temperature does not exceed 40°C (104°F) while the switch is operating.

Location Considerations

Before installing the device, plan its location and orientation relative to other devices and equipment. Devices can be mounted in a standard 19-inch equipment rack or on a flat surface. Be sure to follow the guidelines below when choosing a location.

The site should meet the following requirements:

Maintain the operating environment as specified in the section “Environmental considerations” on page 45.

Allow a minimum of 3 in. of space between the front and the back of the device and walls or other obstructions for proper air flow.

Allow at least 3 in. of space at the front and back of the device for the twisted-pair, fiber-optic, and power cabling.

Be accessible for installing, cabling and maintaining the devices.

8

Brocade ICX 6650 Hardware Installation Guide

 

53-1002599-01

Image 24
Contents Brocade ICX Brocade Communications Systems, Incorporated Contents Chapter Configuring the Brocade ICX Appendix C Brocade ICX 6650 Cautions and Danger Notices Index Figures Brocade ICX 6650 Installation Guide Tables Brocade ICX 6650 Ethernet Installation Guide About This Document AudienceSupported hardware and software Brocade ICX 6650 slot and Ethernet port numberingHow this document is organized Command syntax conventions Document conventionsText formatting Related publications Corporation Referenced Trademarks and ProductsAdditional information Getting technical helpDocument feedback Brocade resourcesBrocade ICX 6650 slot and Ethernet port numbering Brocade ICX 6650 Overview This chapterBrocade ICX 6650 overview Views of the Brocade ICX 6650 switch 3 4Ports-on-Demand licensing Shows the rear-panel portsBrocade ICX 6650 slot and Ethernet port numbering Supported transceivers and cables Breakout cables Installing the Brocade ICX Package contentsUnpacking the device Installation and safety considerations Electrical considerationsEnvironmental considerations Location ConsiderationsCabinet considerations Recommendations for cable managementInstallation tasks Installation precautionsGeneral precautions Lifting precautions Power precautionsInstalling the device in a rack or cabinet Post rack mount installation Proceed to Attaching a PC or terminal on Show exploded views of the optional 4-post rack mount kit Optional 4-post Rack Mount Kit, Rear Attach Powering on the system Attaching a PC or terminalInstalling an SFP+ transceiver Installing an SFP+ transceiver in a port slotConfiguring the Brocade ICX Assigning permanent passwords Setting passwords Recovering from a lost passwordConfiguring IP addresses Devices running Layer 2 softwareDevices running Layer 3 software Syntax no ip address ip-addr/mask-bitssecondary Syntax router-interface ve num Syntax interface ve num Connecting network devices ConnectorsConnecting a network device to a fiber port Installing a transceiver Testing connectivity Troubleshooting network connectionsPinging an IP address Tracing a routeBrocade ICX 6650 Operation LED activity interpretationBrocade ICX 6650 front panel LEDs Brocade ICX 6650 front panel LEDs and port numbering Brocade ICX 6650 rear panel LEDs Shows the LEDs on the rear panel of the Brocade ICXLED patterns PSU 1 and PSU2Brocade ICX 6650 maintenance Diagnostic tests and monitoringDiagnostic tests and monitoring Managing temperature settings Managing the Brocade ICXDisplaying the temperature Displaying Syslog messages for temperature Changing the temperature warning levelChanging the temperature poll time Hardware maintenance schedule Removing MAC address entriesDisplaying Brocade ICX 6650 CPU usage Replacing a copper or fiber optic module Removing a copper or fiber optic moduleFRU removal and replacement procedures Cleaning the fiber optic connectorsCabling a fiber optic module Replacing a power supply unit Determining the need to replace a power supply Replacing a power supplyTime and items required Replacing fan trays Determining the need to replace a fan assembly Replacing the fan assemblyBrocade ICX 6650 Specifications Weight and physical dimensionsThis appendix Environmental considerations Cooling system and fansAirflow Intake airflow label Power supply specifications General specificationsPinouts and signalling Memory specificationsSupported media types Brocade ICX 6650 Regulatory Statements USA FCC CFR 47 Part 15 WarningIndustry Canada statement Europe and Australia Cispr 22 Class a Warning Germany Noise WarningJapan Vcci Japan power cord KoreaChina Bsmi statement Taiwan Regulatory complianceRegulatory compliance Brocade ICX 6650 Cautions and Danger Notices Vorsicht Devices near the input power connectors Never leave tools inside the chassis Vorsicht Orangefarbenen Pfeil mit dem Buchstaben I gekennzeichnet Gefahr Schwerer desto tiefer darüber untergebracht werden Remove both power cords before servicing Brocade ICX 6650 Hardware Installation Guide Index NumericsBrocade ICX 6650 Hardware Installation Guide Brocade ICX 6650 Hardware Installation Guide 53-1002599-01 Brocade ICX 6650 Hardware Installation Guide