Introduction
Congratulations! Your
6kVA Redundant Configuration (6kVA max load) | 12kVA |
6kVA UPS
6kVA UPS
Parallel
PDU
Loads 6kVA and lower
Redundant Operation | YES |
YES | |
YES | |
Increased Capacity | NO |
When two UPS systems are loaded to a maximum of 50%, your configuration will receive full
6kVA UPS
6kVA UPS
Parallel
PDU
Loads
Redundant Operation | NO |
NO | |
YES | |
Increased Capacity | YES |
When two UPS systems are loaded to a maximum of 100%, your configuration will receive the full capacity of both UPS systems combined to power larger loads. This configuration does NOT carry redundancy or
To ensure
You can use this configuration to grow your UPS power capacity to 12kVA In this configuration,
Important Safety Warnings
SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of this product.
Location Warnings
•Install the PDU Kit in a structurally sound area. Take care when moving and lifting the unit.
•Only operate your PDU Kit at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures between 62° F and 84° F (between 17° C and 29° C).
Equipment Connection Warnings
•When connecting to the UPS systems, the UPS is connected to a DC energy source (battery). The output terminals may be live even when the
UPS is not connected to an AC supply.
•Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.
Maintenance Warning
•Your PDU Kit does not require routine maintenance. Do not open the PDUs for any reason. There are no
•Service and repair should be done only by trained personnel. Prior to any service work performed, all units should be turned off or manually bypassed. Prior to any service work performed on power modules that plug directly into wall outlets, they should be turned off and unplugged.
Note that potentially lethal voltages exist as long as the battery supply is connected.
2