6kVA Redundant Configuration (6kVA max load)

Introduction

Congratulations! Your SUPDMB-Series Parallel PDU allows you to configure two 6kVA UPS systems for fault-tolerant operation or increased output capacity. Your UPS will auto-configure for redundancy or increased capacity based on the attached equipment’s load. In order to configure your UPS for redundancy, you will need to obtain two separate 6kVA UPS systems with parallel configuration ports and a SUPDMB12KHW Parallel PDU module. Contact Tripp Lite for additional configuration help.

6kVA Redundant Configuration (6kVA max load)

12kVA Non-Redundant Configuration (12kVA max load)

6kVA UPS

6kVA UPS

Parallel

PDU

Loads 6kVA and lower

Redundant Operation

YES

Fault-Tolerance

YES

Hot-Swappable UPS Replacement

YES

Increased Capacity

NO

When two UPS systems are loaded to a maximum of 50%, your configuration will receive full redundancy—fault- tolerance with full support for hot- swappable UPS replacement in the case of sudden UPS failure.

6kVA UPS

6kVA UPS

Parallel

PDU

Loads 6-12kVA

Redundant Operation

NO

Fault-Tolerance

NO

Hot-Swappable UPS Replacement

YES

Increased Capacity

YES

When two UPS systems are loaded to a maximum of 100%, your configuration will receive the full capacity of both UPS systems combined to power larger loads. This configuration does NOT carry redundancy or fault-tolerance.

To ensure fault-tolerance, load the two parallel UPS systems to a maximum of 50% of the combined rating for both UPS systems. For example, if you have two 6kVA UPS systems, you will have fault- tolerant operation if the load level remains at 6kVA or lower.

You can use this configuration to grow your UPS power capacity to 12kVA In this configuration, fault-tolerance is NOT available.

Important Safety Warnings

SAVE THESE INSTRUCTIONS. This manual contains important instructions and warnings that should be followed during the installation and maintenance of this product.

Location Warnings

Install the PDU Kit in a structurally sound area. Take care when moving and lifting the unit.

Only operate your PDU Kit at indoor temperatures between 32° F and 104° F (between 0° C and 40° C). For best results, keep indoor temperatures between 62° F and 84° F (between 17° C and 29° C).

Equipment Connection Warnings

When connecting to the UPS systems, the UPS is connected to a DC energy source (battery). The output terminals may be live even when the

UPS is not connected to an AC supply.

Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.

Maintenance Warning

Your PDU Kit does not require routine maintenance. Do not open the PDUs for any reason. There are no user-serviceable parts inside.

Service and repair should be done only by trained personnel. Prior to any service work performed, all units should be turned off or manually bypassed. Prior to any service work performed on power modules that plug directly into wall outlets, they should be turned off and unplugged.

Note that potentially lethal voltages exist as long as the battery supply is connected.

2

Image 2
Contents Primary & Secondary Parallel PDU Units Owner’s ManualParallel PDU Kit SmartOnline UPS Systems 6kVA 12kVA Non-Redundant Configuration 12kVA max load Maintenance Warning6kVA Redundant Configuration 6kVA max load Location WarningsSecondary Parallel PDU Module 2 Parallel Connector For UPS communication in parallelPrimary Parallel PDU Module PARALLEL MASTER 6 Power ON UPS system 1, being sure that the output breakers are OFFUPS systems PARALLEL SLAVEManual Bypass Operation for UPS maintenance or replacement UPS RemovalStorage ServiceWARRANTY REGISTRATION 2-Year LimitedUnidades de PDU paralelos principales y secundarios Manual del propietarioKit de PDU paralelo para Sistemas UPS SmartOnline 6kVA Advertencias sobre la conexión de equipos Configuración redundante para 6kVA 6kVA de carga máxAdvertencias de ubicación Advertencias de mantenimientoMódulo de PDU paralelo principal Módulo de PDU paralelo secundariosistema UPS 2 mostrará “Paralelo Esclavo” Extracción del UPS Únicamente la PDU principalGarantía limitada por 2 años AlmacenamientoServicio Conformidad con las regulaciones sobre números de identificaciónUnités PDU parallèles principales et secondaires Manuel de l’utilisateurEnsemble de PDU parallèle pour systèmes d’ASI SmartOnline 6kVA Avertissements concernant le branchement de l’équipement Avertissements concernant l’emplacement de la PDUConfiguration redondante de 6kVA charge maximale de 6kVA Avertissements concernant l’entretienModule de la PDU parallèle principal Module de la PDU parallèle secondaire1 En vous assurant que tous les interrupteurs sont éteints et que toutes les unités sont coupées, reportez-vous à la section « Montage » du manuel. Montez d’abord les systèmes d’ASI puis les PDU parallèles principale et secondaire fonctionnement normal Retrait de l’ASIÉtat de la de sortie État de la seortie Mode puissanceNuméros d’identification de conformité réglementaire EntreposageGarantie limitée de 2 ans Первичные и вторичные блоки PDU при параллельном включении Руководство по эксплуатацииНабор для параллельного включения ИБП SmartOnline 6 кВА Меры предосторожности при обслуживании Правила безопасности при выборе места для установкиПравила безопасности при подключении оборудования 2 Разъем для параллельного подключения Для связи с параллельным ИБП Первичный блок PDU параллельной конфигурацииВторичный блок PDU параллельной конфигурации Page Ручное переключение на работу в обход для обслуживания или замены ИБП Снятие ИБПХранение Сервисное обслуживание