Specifications
SU6000RT3U and SU10KRT3U models include a Power Module, Isolation Transformer Module and one Battery Module. SU6000RT3UXR models include a Power Module, Isolation Transformer Module and two Battery Modules.
Model | SU6000RT3U | SU6000RT3UXR | SU10KRT3U | |
Input |
|
|
| |
Input Voltage Range | 156V~276V Single Phase | 156V~276V Single Phase | 156V~276V Single Phase | |
Module Input Voltage | 200/208/240V | 200/208/240V | 200/208/240V | |
Input Frequency | 50/60 Hz ± 3 Hz | 50/60 Hz ± 3 Hz | 50/60 Hz ± 3 Hz | |
Input Current | 22.6A | 22.6A | 40A | |
Inrush Current | <150A | <150A | <200A | |
Power Factor (Full Load) | >0.97 | >0.97 | >0.97 | |
Efficiency (Full | >87% | >87% | >88% | |
Power Module Circuit Breaker | 40A (2 pole) | 40A (2 pole) | 63A (2 pole) | |
Transformer Module Circuit Breaker | 40A (2 pole) | 40A (2 pole) | 63A (2 pole) | |
|
|
|
|
|
Output |
|
|
| |
VA | 6000 | 6000 | 10000 | |
Watts (Power Factor: 0.7) | 4200 | 4200 | 7000 | |
Waveform | Sinewave | Sinewave | Sinewave | |
Waveform | Sinewave | Sinewave | Sinewave | |
Output Voltage (RMS) | 100/120/200/208/240V | 100/120/200/208/240V | 100/120/200/208/240V | |
Output Frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz | |
|
| (± 0.2 Hz on battery) | (± 0.2 Hz on battery) | (± 0.2 Hz on battery) |
Voltage Regulation | ±3% | ±3% | ±3% | |
Max. Harmonic Distortion |
|
|
| |
| (Linear Full Load) | <3% | <3% | <3% |
| <6% | <6% | <6% | |
Overload Capabilities | 102% (continuous) | 102% (continuous) | 102% (continuous) | |
|
| 102%~125% (1 min.) | 102%~125% (1 min.) | 102%~125% (1 min.) |
|
| 125%~150% (30 sec.) | 125%~150% (30 sec.) | 125%~150% (30 sec.) |
|
| >150% (Immediate) | >150% (Immediate) | >150% (Immediate) |
Short Circuit Capability | 90A* | 90A* | 160A* | |
Power Module Circuit Breaker | 40A | 63A | 63A | |
Transformer Module Circuit Breaker | 30A (3 pole) | 63A (3 pole) | 63A (3 pole) | |
Crest Factor | 3:1 | 3:1 | 3:1 |
*The short circuit capability at 1ø 2W 120V for the SU6000RT3U and SU6000RT3UXR is greater than 180A, and for the SU10KRT3U is greater than 320A.
Operation
|
|
| ||
(Line to Battery, Battery to Line) | 0 ms | 0 ms | 0 ms | |
Audible Noise (Full Load @ 1 m) | <50 dBA | <55 dBA | <55 dBA | |
Typical Backup Time (with included Battery Module) |
|
| ||
| (Full Load) | 15 min. + | 37 min. + | 8 min. + |
| (Half Load) | 37 min. + | 79 min. + | 20 min. + |
Indicators
Includes an LCD Display and LEDs (I/P (input), BATTERY, AC/DC, BYPASS DC/AC, O/P (output)).
Communications
Includes an
Physical Specifications
Unit Dimensions (H x W x D) |
|
|
|
Power Module | 5.25 (3U) x 17.5 x 22.5 in. | 5.25 (3U) x 17.5 x 22.5 in. | 5.25 (3U) x 17.5 x 22.5 in. |
| [13.4 x 44.5 x 57.2 cm.] | [13.4 x 44.5 x 57.2 cm.] | [13.4 x 44.5 x 57.2 cm.] |
Transformer Module | 5.25 (3U) x 17.5 x 26 in. | 5.25 (3U) x 17.5 x 26 in. | 5.25 (3U) x 17.5 x 26 in. |
| [13.4 x 44.5 x 66.1 cm.] | [13.4 x 44.5 x 66.1 cm.] | [13.4 x 44.5 x 66.1 cm.] |
Battery Module #1 | 5.25 (3U) x 17.5 x 22.5 in. | 5.25 (3U) x 17.5 x 22.5 in. | 5.25 (3U) x 17.5 x 22.5 in. |
| [13.4 x 44.5 x 57.2 cm.] | [13.4 x 44.5 x 57.2 cm.] | [13.4 x 44.5 x 57.2 cm.] |
Battery Module #2 (if applicable) | n/a | 5.25 (3U) x 17.5 x 22.5 in. | n/a |
|
| [13.4 x 44.5 x 57.2 cm.] |
|
|
|
|
|
Shipping Weight |
|
|
|
Power Module | 58 lb. | 58 lb. | 68 lb. |
| [27 kg.] | [27 kg.] | [31 kg.] |
Transformer Module | 124 lb. | 124 lb. | 124 lb. |
| [57 kg.] | [57 kg.] | [57 kg.] |
Battery Module #1 | 160 lb. | 160 lb. | 160 lb. |
| [73 kg.] | [73 kg.] | [73 kg.] |
Battery Module #2 (if applicable) | n/a | 160 lb. | n/a |
|
| [73 kg.] |
|
+ Backup times are expandable with additional Battery Modules (model: