Power ON/OFF
1.Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons ( A and B ) at once. Scroll through the setup options (using A or B ) and select the appropriate setting for each of the following options using the “SELECT” button B .
•Input & Output Voltage: Select 200, 208 or 240 VAC.
•Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.
•Economy Mode: Your UPS can provide
•After you have set these options, “exit” the setup mode with the scroll button A , then exit bypass mode by holding the ON button C down until you hear a beep.
2.Turn input to the UPS ON: If the UPS power module is connected to a transformer module, turn the tranformer module’s
3.Turn UPS output ON: Turn the UPS power module’s Output Circuit Breaker H ON. If the UPS is connected to a transformer module, turn the transformer module’s Manual Bypass Switch I from BYPASS to NORMAL and its Output Circuit Breaker ON. Your UPS will now provide power to connected equipment.
4.To turn the UPS power module and transformer module OFF: Press the UPS power module’s OFF button E until you hear a beep. Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display F will show BYPASS MODE. Turn the UPS power module’s Input and Output Circuit Breakers ( E and H ) OFF. If the UPS is connected to a transformer module, turn the transformer module’s power