Tripp Lite SU16000RT4UHW Hardwiring Cautions, Attach the PDU to the Power Module and Battery Pack

Page 8
K . See “Startup Self-

Connection

Note: The output voltage is set at 208/120V~ when the UPS is shipped from the factory. If you need to change the output voltage of the UPS, refer to “Output Voltage Selection” in the “Operation” section. You should select the correct output voltage before connecting equipment to the UPS.

Hardwiring Cautions

Wiring must be installed by a qualified electrician.

When making wiring connections, observe the regulations appropriate to your region [National Electrical Code (NEC) in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 newton-meters). Make sure that your equipment is properly grounded.

Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to make wiring connections. Ground conductors must be the same size and type as the power conductors used.

Refer to National Electrical Code (NEC) guidelines for proper wire gauge and output protection circuit requirements.

Input and Output Ratings

 

Input

Maximum Rated Maximum Rated

Typical

Model

Voltage

 

Input Current

Output Current

Wire Size

SU16000RT4U

100-140V

(L1-N: L2-N)

68A

70A

4 AWG

SU16000RT4UHW 100-140V

(L1-N: L2-N)

68A

70A

4 AWG

Contacts on Power Module and PDU

WARNING! High Voltage! Risk of electrical shock!

Do not let these contacts touch any surface!

See "Manual Bypass Procedure" section for more information.

1Attach the PDU to the Power Module and Battery Pack.

Align and connect the PDU's power module terminal block with the input/output terminal

block A on the back of the power module. Secure the PDU to the power module with four screws. Before proceeding, ensure that the bypass switch is set to NORMAL. Remove the utility input terminal block cover B .

2Hardwire the PDU to a Utility Power Source.

Pass user-supplied cabling through the knockouts on the top of the PDU C and connect it to the PDU's input terminals D . Replace the terminal block cover. Connect the other end of the cabling to a dedicated utility power circuit of sufficient amperage.

3Connect the Battery Pack to the Power Module.

Consult the owner’s manual that came with the battery pack. Remove the retention brackets E from the power module's battery connector F and one of the battery pack's rear panel connectors G . Attach one end of the detachable battery power cable H to each connector. (Small sparks may occur; this is normal.) Reattach the retention brackets immediately to the right of each connector, using the additional screw holes I provided to

the right of the original bracket position. The brackets will secure the battery power cable connection. Warning: Always use the connector retention brackets to secure the battery pack connection. Do not attempt to operate the UPS system without the connector retention brackets in place. NOTE: the power module does not contain internal batteries and will not start until a battery pack is connected. Allow the battery to charge for at least 12 hours to ensure full battery backup for connected equipment. If you require increased battery backup runtime, an unlimited number of additional external battery packs may be daisy-chained to the primary battery pack. Adding additional external battery packs will increase runtime battery backup runtime, but it will also increase recharge time.

4Turn the UPS On.

Press the “ON” Button J until you hear a beep to begin inverter operation. The UPS will now provide output power through its AC outlets to connected equipment. The UPS will perform a brief self-test and show the results on the LCD Display

Test” in the “Operation” section for the display sequence.

Cold Start: To use the UPS as a stand-alone power source when AC input power is unavailable (i.e. during a blackout), you can cold start the UPS and power connected equipment from the battery. The battery must be at least partially charged for this operation to succeed. Press and hold the “ON” Button until you hear a beep to cold start the UPS. The LCD Display will show “ON BATTERY MODE”. Battery power will begin discharging. Some electronic equipment may draw more amps during startup; when cold starting, consider reducing the initial load on the UPS.

 

 

A

 

 

B

1

 

 

 

D

C

 

 

2

 

 

 

I

 

 

H

 

 

F

E

 

 

3

G

 

 

 

K

 

J

 

4

 

 

To Turn the UPS System OFF: Press the UPS's “OFF” Button until you hear a beep. The UPS will stop providing output power through its AC outlets. The LCD Display will show “STANDBY MODE.” The UPS will continue to charge its batteries as long as AC input power is present. To completely deactivate the UPS, disconnect the UPS from AC input power when the UPS system is in standby mode.

8

Image 8
Contents SmartOnline Hot-Swappable Modular UPS Systems Important Safety Warnings Front Control Panel Power Module Detachable Power Distribution Unit PDU External Battery Pack with Detachable Power Cable Mounting 4-Post Rackmount Mounting TowerHardwiring Cautions Attach the PDU to the Power Module and Battery PackHardwire the PDU to a Utility Power Source Connect the Battery Pack to the Power ModuleAdditional Battery Pack Connection Additional Battery Pack Connection ProcedureUSB and Serial Communication Connection EPO Port ConnectionStartup Self-Test Failed Self-TestOn Battery Alarm Normal OperationOutput Voltage Selection Additional Self-TestOverload Messages Bypass MessagesShutdown Messages ShutdownUPS Power Module Removal To reattach the PDU, reverse the process listed aboveHigh Voltage Warnings High Voltage Risk of electrical shockService WarrantyWarranty Registration StorageManual del Propietario Instrucciones de Seguridad Importantes Mute Select Setup Controles en el Panel FrontalCaracterísticas continuación Módulo de PotenciaUnidad de Distribución de Energía PDU Desmontable Módulo de Baterías Externas con Cable Desprendible Montaje Bastidor de 4 Postes Montaje TorreConecte el Módulo de Baterías al Módulo de Potencia Encienda el UPSConexión de Comunicaciones USB y Serial Conexión del Puerto EPOConexión del Módulo de Baterías Adicional Procedimiento para conectar Módulos de Baterías AdicionalesAuto Prueba de Arranque Auto Prueba FallidaAlarma de Modo de Respaldo Operación NormalSelección del Voltaje de Salida Auto Prueba AdicionalMensajes de Sobre Carga Mensajes en DerivaciónMensajes de Cierre INT Charger FailRemoción del Modulo de Potencia del UPS Servicio Procedimiento de Derivación Manual continuaciónAlmacenaje Aviso de la FCC sobre la interferencia de Radio/TV Cumplimiento con las Normas de Números de IdentificaciónManuel du propriétaire Importantes consignes de sécurité Panneau de commandes avant SetupCaractéristiques suite Module dalimentationUnité de distribution dalimentation PDU amovible Bloc-batterie externe avec câble dalimentation amovible Montage en tour MontageMontage en bâti à 4 montants Avertissements pour le câblage Fixer la PDU au module dalimentation et au bloc-batterieCâbler la PDU à une source de courant de secteur Connecter le bloc-batterie au module dalimentationConnexions optionnelles Auto-test de démarrage Échec de lauto-testFonctionnement normal Alarme de batterieFonctionnement suite Sélection de la tension de sortie Autre auto-testMessages de surcharge Messages de dérivationMessages darrêt Dépose du module dalimentation de londuleur Procédure de dérivation manuelle suite Haute tension Risque de choc électriqueEntreposage RéparationsAvis de la FCC sur les interférences radio et TV Conformité aux règlements Numéros didentification200807048

SU16000RT4U, SU16000RT4UHW specifications

The Tripp Lite SU16000RT4UHW is a high-capacity rack-mounted uninterruptible power supply (UPS) designed to provide reliable power protection for critical IT infrastructure. With a maximum output of 16,000 VA, this device is ideal for data centers, server rooms, and enterprise networks that demand continuous power and high performance. One of its standout features is its hybrid design, which allows for versatile installation in both rack and tower formats, making it suitable for various environments.

The SU16000RT4U offers advanced battery management technologies, ensuring long-lasting performance and efficiency. Its scalable architecture allows users to add additional battery packs for extended runtime, which is essential in situations where power outages can disrupt business operations. Equipped with smart features, it includes an LCD control panel that provides real-time information regarding battery status, load level, and other vital metrics, enabling users to monitor performance effortlessly.

Another significant characteristic of the SU16000RT4UHW is its compatibility with Tripp Lite's PowerAlert software. This software allows for advanced management of power conditions and remote monitoring via SNMP interface when paired with the optional SNMP/Web card. The UPS also includes a variety of outlets, including both NEMA and IEC standard configurations, catering to different equipment and ensuring adaptability.

Furthermore, this UPS is designed with enhanced protection features such as spike and surge suppression, which safeguards connected devices from electrical disturbances. The internal smart charging system also maximizes battery life by optimizing charging cycles based on usage patterns. This means that users can expect higher availability and a longer operational lifespan.

Constructed with durability in mind, Tripp Lite has included a fault-tolerant design that ensures uninterrupted power delivery even under extreme conditions. The SU16000RT4UHW's robust thermal management enhances cooling efficiency, contributing to reliable operation even in densely populated rack environments.

In conclusion, the Tripp Lite SU16000RT4UHW and its counterpart the SU16000RT4U are essential components for any organization that prioritizes reliable power management. With its high capacity, advanced features, and flexible configurations, it provides unmatched protection for critical IT equipment, ensuring business continuity in the face of electrical failures. Investing in such technology not only protects hardware but also secures data integrity and operational efficiency.