Pelco CM6800E-48X8 manual

Page 1

I N S T A L L A T I O N / O P E R A T I O N

CM6800E-48X8

®

Matrix Switcher/Controller

C1528M-F (6/05)

Image 1
Contents CM6800E-48X8 Contents Control Genex Multiplexer and Genex Multiplexer Displays List of Illustrations List of Tables C1528M-F 6/05 For Qualified Service Personnel only Important Safeguards and WarningsSample CM6800E-48X8 System DescriptionSample CM6800E 96 x 16 System System Access and Priority Sequences, Macros, Presets, Patterns, and ZonesProgramming KeyboardsPower, Mounting Methods Alarm InputsAuxiliary Outputs Continuous Operating DeviceCompatible Products ModelsAdditional Resources Associated EquipmentMounting InstallationVideo Sources 96 x 16 System Default Camera NumbersCable Type Maximum Distance Main unit Cameras Expansion unit CamerasConnecting Looping Video Sources 96 x 16 System PTZ Control Capacity Control Lines96 x 16 System Monitor Capacity MonitorsMain unit Monitor Expansion Unit Monitor 96 x 16 System Alarm Capacity AlarmsMain unit Alarms Expansion Unit Alarms Input Type Wiring Pin-Outs Default Device Connecting Devices Through the Communication PortsCM9760-MDA, Ascii Ground Tx+ RS-232 Pin-Outs RJ-45 RS-485 Pin-Outs Ascii device CM9760-MDA, Satellite Rx+Port RS-485, 19200 baud, no parity, 8 data bits, 1 stop bitCM6800E Communication Port Connections and Options KBD100, KBD200A, and KBD300A Series Keyboards KBD100, KBD200A, and KBD300A Direct-Powered KeyboardsTable E. Switch Settings-KBD200A/300A Keyboards Only Keyboard Address Switch SettingsKeyboard Switch OFFRemote Keyboards KBD100, KBD200A, and KBD300A Remote KeyboardsDevices Addressing Devices KBD960, ALM2064, REL2064KBD960/KBR960 REL2064 ALM2064 Connecting a KBD960/KBR960 to the CM6800E Connecting a Single KBD960/KBR960 KeyboardTo connect a single ALM2064 Alarm Interface Unit Connecting a Single ALM2064 Alarm Interface UnitTo connect a single REL2064 Relay Interface Unit Connecting a Single REL2064 Relay Interface UnitMultiple M Devices Local Connection Multiple M DevicesMultiple M Devices Remote Connection Connecting Multiple M Devices Remote ConnectionPC Connection to RJ-45 Port Connecting a PCConnecting Genex Multiplexers Connecting Genex MultiplexersLocal Auxiliaries Connecting Relay Contacts AUX 196 x 16 System Auxiliary Capacity Main unit AUX Expansion Unit AUXWiring the F3 TTL Output Connecting the Open Collector Output F3 TTLCM6800E-48X8 Main Unit Connecting a 96 X 16 SystemSystem START-UP POWER-UP the SystemInitialize Keyboards Port Default Settings Configure the SystemCommunication Ports COMKBD960/KBR960 Keyboard 96 X 16 System SettingsGenex Multiplexer Control MUXProgram Presets Monitor Color AdjustmentAdditional Programming Programming the CM6800E Exit Programming Mode CM6800E Programming ModeSelect Language Function Entries in Programming ModeKeyboard Navigate to the Next or Previous field Press F1 Navigate to the Help field Press F1Keyboard to Monitor AccessCamera to Keyboard Camera to MonitorProgram Alarm Groups Alarm ProgrammingProgram AN Internal or External Alarm Contact ACK Type AUX field, select an auxiliary to be activatedType PriorityProgram Video Loss Alarms Program a Video Loss AlarmAssign a Logical Alarm Number Assign a Logical Alarm Number OptionalMode field for each auxiliary, select either LAT or MOM Alarm-based OperationAuxiliary Outputs Latching or Momentary OperationProgram Logical Numbers Camera ProgrammingIf necessary, first program logical camera number Program Cameras Select Character Program Vertical Drive Option OptionalEvent Timers Macro Status View Screen MacrosMonitor Monitor DisplayCamera Title Type Display ValuesALM Status Display Values Monitor Status Display ValuesTime DateUse the Set Password screen to change the system password PasswordSerial Port Input on CM6800E rear panel Ports SERIAL/COM PortsAction Ascii text Port PriorityOptions Level 1 = highest priority Level 8 = lowest priorityChange the System Setting 96 X 16 System SettingsSequence SequencesTurn global auxiliary on AUX and ##Turn global auxiliary off Turn camera auxiliary onTime and Date PATTERNS, PRESETS, and ZonesOptions DD/MMM/YY MMM/DD/YY YY/MMM/DD DD/MM/YY YY/MM/DD Operation Switch MonitorsOverview Operating the CM6800EControl Receivers To move through the sequence one camera at a time Operate SequencesSelect Macro to start the macro RUN a MacroSelect To start the macro Call a Preset Acknowledge AN AlarmPatterns are not available with the KBD100 keyboard Create and RUN a PatternOperate a Local Auxiliary Operate AUXILIARIES/RELAYSOperate an External Auxiliary Operate an Auxiliary in a ReceiverOperate Scanning Functions Control Genex Multiplexer and Genex Multiplexer DisplaysDetect Video Loss Define ZonesCM6800E DIP Switch Default Setting CM6800E DIP SwitchesSwitch AppendixMonitor Alarm Alarms Alarm Group Display OptionsBlock Build Chronological Pair D and QReverse Chronological Pair M and L Monitor Alarm Alarms Next Display CycleSalvo Group Description Specify Fields Macro CommandsAuxiliary Notes Quad PipoNano HEXInstall the CM6800E AS a Satellite Device Page Satellite Monitor Access Configure the CM6800E AS a Satellite DeviceChange the Port Setting Satellite Port SettingsEnable Alarm Contacts Satellite Alarms OptionalAdd a Satellite Device in the CM9700-MGR Configure CM9700-MGR System Manager SettingsConfigure CM9760-MGR System Manager Settings Click the Comms tab. The Comms page appears Program the Comms FileClick the Cameras tab. The Cameras page appears Program the Cameras FileClick the Link Cameras tab. The Link Cameras page appears Program the Link Cameras FileClick the Alarms tab. The Alarms page appears Program the Alarms File OptionalClick OK to close the Alarm Camera Switches dialog box How to Exit Programming Mode How to Display the CM6800E Programming Main MenuHow to Select a Numerical Value in an Option Field Press 89 PresetLink Camera Name Logical Number Assignment Table for Link CamerasLink Camera page Phy Num column Functional Procedure Commands Result Ascii Operating Commands3Ma16#a Uppercase characters Desired Action Command ResultClear an alarm #Ia 48~Jva Trigger an alarm #EaAcknowledge an alarm #Ka Panel An alarm is triggered #Ea Logical Alarm Number in the Alarm Programming sectionGaining Initial Control TroubleshootingWait AT Least Five Seconds Dip Switch Cover Plate Software ResetProblem Remedy Solutions to Common ProblemsIcon/Button Legend KBD960/KBR960 ICON/BUTTON LegendUpgrade the CM6800 Switcher Software Upgrade the CM6800 Switcher SoftwareTerm Definition GlossaryAscii PAL NtscPTZ Star configuration All four wiresRS-422 Recommended distance is 4,000 feet 1,219 mSpecifications 48 x 8 System Regulatory Notices96 x 16 System Product Warranty and Return Information C1528M-F 6/05 105 ISO9001
Related manuals
Manual 20 pages 33.51 Kb