RuggedCom RS900L manual DC Power Supply Wiring and Grounding

Page 10

2.2.2 DC Power Supply Wiring and Grounding

Figure 5 - DC Power supply wiring and grounding diagram

The low voltage DC power supply features reverse polarity protection and dual independent inputs. The latter feature allows the connection of two DC sources with the same nominal voltage to provide redundant power supply inputs.

The DC power supply inputs should be connected as follows:

1.Connect to the DC inputs according to the polarity markings on the unit.

2.Surge Ground should be connected to the Chassis Ground via a braided cable or other appropriate grounding wire. Surge Ground is used as the ground conductor for all surge and transient suppression circuitry internal to the unit.

3.Chassis Ground must be connected to the protective earth.

NOTES:

1.Equipment must be installed according to the applicable country wiring codes.

2.All line-to-ground transient energy is shunted to the Surge Ground terminal. In cases where users require the inputs to be isolated from ground, remove the ground braid between Surge and Chassis Ground. Note that all line-to-ground transient protection circuitry will be disabled.

 

10

2007 RuggedCom Inc. All rights reserved

Rev101

Image 10
Contents RuggedSwitch RS900L Installation GuideTrademarks Table of Contents Table of Figures Product Overview Feature HighlightsFunctional Overview Front Panel Description Front Panel DescriptionBottom Panel Description Bottom Panel DescriptionInstallation Din Rail MountingPower Supply Wiring and Grounding AC Power Supply Wiring and GroundingDC Power Supply Wiring and Grounding DC Power supply wiring and grounding diagramFailsafe Output Wiring Failsafe Output RelayDielectric Strength Testing Dielectric Strength TestingRS232 Console Port Wiring RS232 Female DCE pin-outRJ11 Ethernet over Vdsl Port Ethernet PortsOverview Configuration & Setup WiringPerformance  2007 RuggedCom Inc. All rights reserved Rev101 RJ45 Ethernet Ports RJ45 port pin-out and LEDs 2007 RuggedCom Inc. All rights reserved Rev101 100FX Mtrj connector Fiber Optic Ethernet PortsFailsafe Relay Specifications Technical SpecificationsPower Supply Specifications Operating EnvironmentRJ11 Ethernet over Vdsl Port Specifications RJ45 Ethernet Port SpecificationsFiber Optic Ethernet Port Specifications Communication StandardsMechanical Specifications Parameter ValueType Tests IEC 61850-3 Type TestsIeee 1613 Type Tests IEC Environmental Type TestsWarranty