13.The following text displays:
Get SCM ShMgr Mode - Enter address (in hex):
Enter the same host address you entered for step 10. If the on-board Shelf Manager is disabled, this message displays:
SCM ShMgr Mode: Enabled
14.Enter q to exit the rsys_debug mode.
15.Remove the SCM and reinstall it in a RadiSys shelf. For removal instructions, see the Switch and Control Module Reference. For installation instructions, see Install the SCM in the shelf on page 5 of this manual.
16.If you are planning to remove a second SCM from the non-RadiSys shelf, connect to it and run through the same set of procedures described in steps 1 through 15.
Rear I/O connectivity
The ATCA-5010 shelf peripheral module (SPM) provides rear I/O connectivity on the SCM. The configuration of the SCM determines the functionality of the Fabric ports, the Base ports, and the Telco alarm connection on the SPM. For more information, see the ATCA-5010 Shelf Peripheral Module Installation Guide and the ATCA-5010 Shelf Peripheral Module Reference.
COM Express module setup
SCMs with the optional Procelerant™ CE3100 COM Express module and SAS/SATA drive ship with a factory-installed basic software package. Once the SCM is installed, and depending on your organization’s needs, you may choose to change the BIOS setting or install an operating system and drivers. See the ATCA-2210 Switch and Control Module Reference for instructions on performing such procedures.
Where to go from here
See the ATCA-2210 Switch and Control Module Reference for detailed information on the SCM’s electrical, mechanical, and environmental aspects. Software information is covered in the following manuals: the Shelf Management Software Reference, the Software Guide for Management Processors and General Purpose Computing Processors, and the Command Line Interface Reference. For information on integrating the SCM into the platform, refer to the appropriate Platform Hardware Reference for SYS-6000/6010,SYS-6006, or SYS-6014/6016.
After your system has been assembled, verify a link has been established between the components and that traffic is being passed. The Base Ethernet and Fabric Ethernet switches can be checked by pinging from component to component.
You should also set passwords for the root and the admin users, and create user accounts for those who do not require administrative privileges. See the Software Guide for Management Processors and General Purpose Computing Processors for more information.