4.5.3.2
For units with
RS485 Serial Port tab will not be part of web page.
Figure 4.7 iServer SERIAL Page – Network to Serial
Local Port – This is the port number assigned to the iServer’s serial port for the purpose of TCP, UDP, or ModbusTCP connection. Any number between 500 and 9999 can be used with the exceptions of 1000 and 2002 which are reserved by the iServer for other purposes (port 1000 is described in the previous section and port 2002 is the iServer’s Telnet console port). The default is 2000.
Port number 502 is the default port number for Modbus/TCP protocol.
If Modbus/TCP is enabled in the iServer, set port 502 as the iServer’s Local Port .
Disconnect after Data Sent – If checked, the iServer receives a command, sends it to the serial port and waits for a reply. If a reply is recieved it will close the connection.
19