1.1 Safety and EMC Considerations

This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).

This instrument is a panel mount device protected in accordance with EN 61010-1:2001, electrical safety requirements for electrical equipment for measurement, control and laboratory. Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.

This instrument has no power-on switch. An external switch or circuit-breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close proximity to the equipment within easy reach of the operator. The switch or circuit- breaker shall meet the relevant requirements of IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The switch shall not be incorporated in the main supply cord.

Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment, an overcurrent protection device shall be installed.

Do not exceed voltage rating on the label located on the top of the

instrument housing.

Always disconnect power before changing signal and power connections.

Do not use this instrument on a work bench without its case for safety reasons.

Do not operate this instrument in flammable or explosive atmospheres.

Do not expose this instrument to rain or moisture.

Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating temperature rating.

Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock hazards.

EMC Considerations

Whenever EMC is an issue, always use shielded cables.

Never run signal and power wires in the same conduit.

Use signal wire connections with twisted-pair cables.

Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.

Failure to follow all instructions and warnings may result in injury!

2

Image 8
Contents User’s Guide Page Table of Contents Dhcp DNSList of Figures IServer Diagnostics Assigning an IP Address using iConnectAccessing the iServer’s Home ARP Commands and ResponsesData Transmission Characteristics RS485 ILog Error MessagesList of Tables Table K-1TIP Before You BeginPart Introduction EMC ConsiderationsAccessing Devices Over the Ethernet DescriptionPhysical Characteristics and Mounting Part HardwareNetwork Communication Interface Section Serial Communication Interfaces For Models with -C4EITWiring Master/Slave Units via RS485 Interface Half Duplex Hookup Pin# ISeriesRJ-45 Pinout Connecting iServer to PC/Hub/Switch/Router Network Communication Interfaces 1 10BASE-T RJ-45 PinoutEthernet MAC Address Part Network ConfigurationNetwork Protocols IP Address DhcpDNS Example C\Telnet 192.168.1.200 Part Operations Serial Interface Configuration Communication ProtocolCommand Prefix Letters LSB MSB Default IP Address Pinging the iServer from a DOS PromptAccess and Configuration Using a Web Browser IServer LoginOverview 4a iServer -C4EIT OverviewIServer Network Network IServer Serial Page RS485 Serial Port IServer Serial Page Network to Serial IServer Serial Page Packing Techniques IServer Serial Page Multi-Host Connection 10 iServer Configuration Page Ethernet Configuration Date and Time 11 iServer Management Page Email, Snmp Management Email Snmp 12 iServer Management Page Alarm AT&T 13 iServer Security 14 iServer Device Query Device Setup -C4EIT 15 iServer Device Setup Page RS485 -C4EIT16 iServer Device Parameters Page -C4EIT 17 iServer Device Setup Page -EIT Device Parameters -EIT 18 iServer Device Parameters Page -EITReadings Readings Device SetpointsTerminal 21 iServer TerminalSystem 22 iServer SystemDiagnostics 23 iServer Diagnostics Page 4.5.12.1 Diagnostics Serial PortDiagnostics Ethernet Port Diagnostics PingPart Specifications Serial Interface -C4EITTime-Lag, IEC 127-3 recognized Network Interface Serial InterfaceElectrical Safety EN61010-12001 PartMeasurement Category Transients Overvoltage Surge 1.2 / 50uS pulseAppendix Aglossary Appendix B IP Address Appendix C IP Netmask Mask Dotted Notation Mask Binary Mask Bits Class aClass B Class CDec Hex Binary Char No Parity No parity Appendix D Ascii ChartDec Hex Binary Appendix D Ascii Chart Continuation Ascii Control CodesDec Hex Ctrl Key Definition Dec Hex Ctrl Key Definition Char EquivFigure E-1 Assigning an IP Address using iConnect Appendix E IConnect SoftwareFigure E-2 Accessing the iServer’s Home Appendix F HTTPget Program Communication interface skip for embedded ethernet -EIT\iServerhttpget -r -S *02X01\r Network read timeout \iServerhttpget -r -S *02X01\r 192.168.1.2002000Appendix G ARP Program Arp -g fi Same as arp -a192.168.1.96 Admin Port Appendix H Telnet SetupISeries? Figure H-3 Telnet Setup iServer Help Figure I-1a Serial Tunneling iSeries -C4EIT Figure I-1b Serial Tunneling iSeries -EITFigure I-2 Device-to-Device Communication Remote iSeries -EIT/-C4EITLocal iSeries -EIT/-C4EIT Figure I-3 Serial Multi-Host Connection -C4EIT Tunneling Troubleshooting Appendix J IPORT IPORT, COM Port RedirectorIPORT Overview Figure J-2a Redirect Serial Connection Figure J-3 iPORT Main Window IPORT Configurations Figure K-1 iLog Software Logging Data for an iSeries Appendix K ILog SoftwareWireless Devices Table K-1 iLog Excel ApplicationsNetworked Product ILOG File Alternate ISeriesTable K-2 iLog Error Messages Error # Description Page Page Page Page Page WARRANTY/DISCLAIMER Shop on line at omega.com