7.0CONFIGURING YOUR NEUTRAL AND GROUND CONNECTIONS
Improper grounding is the largest single cause of UPS installation and
•What is the configuration of the input power source? Most of the recommended schemes for UPS grounding require
•What are the UPS input and output voltages? Systems with 480 VAC input and output have significantly different needs than systems with 208/208 VAC.
•What is the connected load? Does the critical load consist of one or more Power Distribution Units (PDUs)? Do the PDUs have isolation transformers?
The following sections discuss recommended grounding procedures for various system configura- tions.
NOTE
Some UPS modules are equipped with input isolation transformers. However, these transformers have no effect upon any system grounding considerations. These modules will be grounded exactly as shown in the following examples.
14 Configuring Your Neutral and Ground Connections