7.2Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source
Figure 4 Grounding Configuration with Ungrounded Delta Source Input
As previously mentioned, Series 600T UPS systems require a bypass input netrual for sensing and monitoring. With a
If building service is ungrounded delta (and there is no intent to operate with one corner of the delta grounded, either on purpose or accidentally), the SCC requires the Series 600T Artificial Neutral Kit for proper operation. This kit uses a resistor network to create a reference point for the bypass input. In this case, the SCC output neutral must be bonded to the SCC ground.
If the building service is
NOTE
The Artificial Neutral Kit introduces a maximum current of 0.3 amps to ground. Take care to ensure that this does not interfere with the operation of any upstream