Liebert 600TTM installation manual Grounding Configuration with Ungrounded Delta Source Input

Page 22

7.2Grounding Configuration, 480 or 600 VAC Input and Output, Delta Source

Figure 4 Grounding Configuration with Ungrounded Delta Source Input

As previously mentioned, Series 600T UPS systems require a bypass input netrual for sensing and monitoring. With a wye-connected input source, the installer should always connect the building service neutral to the System Control Cabinet (SCC) output neutral to achieve this. When the building service is delta-connected, however, the installer must take special steps to ensure reliable UPS functioning.

If building service is ungrounded delta (and there is no intent to operate with one corner of the delta grounded, either on purpose or accidentally), the SCC requires the Series 600T Artificial Neutral Kit for proper operation. This kit uses a resistor network to create a reference point for the bypass input. In this case, the SCC output neutral must be bonded to the SCC ground.

If the building service is corner-grounded delta or an Impedance-grounded wye, the SCC requires the Isolated Neutral Kit. This kit uses control isolation transformers to create a reference point. For this application, the SCC output neutral must not be bonded to the SCC ground.

NOTE

The Artificial Neutral Kit introduces a maximum current of 0.3 amps to ground. Take care to ensure that this does not interfere with the operation of any upstream ground-fault detection devices.

16 Configuring Your Neutral and Ground Connections

Image 22
Contents Power Protection Series 600T UPSArning Hazard Table of Contents Page List of Figures Page Important Safety Instructions Page Safety Precautions Installation Considerations Handling CabinetUPS Multi-Module Unit Block Diagram Types of System Control Cabinets System Control CabinetsUnloading and Handling Internal Inspections External InspectionsInspections Equipment Location Battery Safety Precautions Battery InstallationBattery Installation Battery Installation Matching Battery Cabinets Non-Standard BatteriesConfiguring Your Neutral and Ground Connections Configuring Your Neutral and Ground Connections Grounding Configuration with Ungrounded Delta Source Input Preferred Grounding Configuration with Power-Tie Switchgear Preferred Grounding Configuration, Power-Tie SystemsGrounding Configurations, Battery Systems Battery Cabinet Grounding ConfigurationWiring Considerations Power Wiring Control Wiring Battery Wiring EquipmentScct Scci / Sccc BFB BIB CB1 CB2 MBB MBD Mbfb MIB RIB SBB SBS For Battery Cabinets Wiring Inspection Power Wiring Terminals Factory SuppliedCopper Aluminum or Copper-Clad Aluminum Installation Drawings Outline Drawing, 500 kVA Multi-Module UPS, 6-Pulse RectifierInstallation Drawings Installation Drawings Installation Drawings Outline Drawing, System Control Cabinet SCCT, 200-1200 Amps Outline Drawing, System Control Cabinet SCCT, 1600-2500 Amps Outline Drawing, System Control Cabinet SCCT, 3000 Amps Outline Drawing, System Control Cabinet Scct 4000 Amps Battery Power Pack, Size a Battery Power Pack, Size B Battery Power Pack, Three-Pack System Base Mounting Patterns, 500 kVA Module, 12-Pulse Rectifier Base Mounting Patterns, 625-750 kVA Module, 6-Pulse Installation Drawings Installation Drawings Installation Drawings Base Mounting Patterns SCCT, 3000 Amps Base Mounting Patterns SCCT, 4000 Amps Installation Drawings Installation Drawings Installation Drawings Terminal Details, 500 kVA Module, 6-Pulse Rectifier Terminal Details, 500 kVA Module, 12-Pulse Rectifier Installation Drawings Installation Drawings Installation Drawings Control Connection Location, 500 kVA Modules Control Connection Location Diagram, 625 & 750 kVA Modules Control Connection Location Diagram, Sccc & Scci Control Connection Location Diagram, Scct Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Internal Modem Installation Drawings Installation Drawings Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface External Interconnections, Module 1/SCC, Cable Groups 21 External Interconnections, Module 2/SCC, Cable Groups 21 Wiring Configurations, UPS Video Display Terminal Installation Drawings Installation Drawings Remote Status Panel, Surface Mount Circuit Breaker Schedule, Multi-Module UPS, 300-750 kVA Installation Drawings Installation Drawings Appendix a Site Planning Data 500-750kVA Multi-Module SystemsSeries 600T Multi-Module Systems, 500-750 kVA 480 Volt Input Series 600T Multi-Module Systems, 500-750 kVA 600 Volt Input Appendix B Field Supplied Lugs One-Hole LugsAppendix B Field Supplied Lugs Series 600T UPS