8.3Battery Wiring

Power wiring to the Battery Cabinet connects positive, negative, and ground power cables from the Battery Cabinet to the associated UPS. Connection of the UPS to the Battery Cabinet serves to both charge and discharge the batteries (when needed). The battery disconnect (circuit breaker) requires a control cable. Liebert Battery Cabinets include power and control cables to join multi- ple cabinets together into a system. Additional (field-supplied) power or control wiring might be necessary to connect the battery cabinet system to the UPS. Refer to Figure 16 through Figure 18.

 

DANGER

 

A BATTERY INTERCELL CONNECTION ON EACH TIER OF THE

 

LIEBERT BATTERY CABINET IS DISCONNECTED FOR SAFETY

 

DURING SHIPMENT. DO NOT COMPLETE THESE

 

CONNECTIONS. THE LIEBERT GLOBAL SERVICES

 

REPRESENTATIVE WILL COMPLETE THESE CONNECTIONS

 

AS PART OF START-UP. AN IMPROPERLY INSTALLED UNIT

 

CAN RESULT IN INJURY TO PERSONNEL OR DAMAGE TO

 

EQUIPMENT.

 

CAUTION

 

Be sure polarity is correct when wiring the Battery Cabinet to the

 

connected equipment (positive to positive; negative to negative).

 

If polarity is not correct, fuse failures or equipment damage can

!

result.

!

CAUTION

DC power cables should be installed in conduit with conductors

in matched pairs (positive and negative).

NOTE

A Liebert Battery Specialist can perform a detailed inspection of the entire

battery system to ensure it meets current IEEE standards. This inspection

 

service is recommended because batteries are a very critical part of the UPS

 

system.

22 Wiring Considerations

Image 28
Contents Power Protection Series 600T UPSArning Hazard Table of Contents Page List of Figures Page Important Safety Instructions Page Safety Precautions Installation Considerations Handling CabinetUPS Multi-Module Unit Block Diagram Types of System Control Cabinets System Control CabinetsUnloading and Handling Internal Inspections External InspectionsInspections Equipment Location Battery Safety Precautions Battery InstallationBattery Installation Battery Installation Matching Battery Cabinets Non-Standard BatteriesConfiguring Your Neutral and Ground Connections Configuring Your Neutral and Ground Connections Grounding Configuration with Ungrounded Delta Source Input Preferred Grounding Configuration with Power-Tie Switchgear Preferred Grounding Configuration, Power-Tie SystemsGrounding Configurations, Battery Systems Battery Cabinet Grounding ConfigurationWiring Considerations Power Wiring Control Wiring Battery Wiring EquipmentScct Scci / Sccc BFB BIB CB1 CB2 MBB MBD Mbfb MIB RIB SBB SBS For Battery Cabinets Wiring Inspection Power Wiring Terminals Factory SuppliedCopper Aluminum or Copper-Clad Aluminum Installation Drawings Outline Drawing, 500 kVA Multi-Module UPS, 6-Pulse RectifierInstallation Drawings Installation Drawings Installation Drawings Outline Drawing, System Control Cabinet SCCT, 200-1200 Amps Outline Drawing, System Control Cabinet SCCT, 1600-2500 Amps Outline Drawing, System Control Cabinet SCCT, 3000 Amps Outline Drawing, System Control Cabinet Scct 4000 Amps Battery Power Pack, Size a Battery Power Pack, Size B Battery Power Pack, Three-Pack System Base Mounting Patterns, 500 kVA Module, 12-Pulse Rectifier Base Mounting Patterns, 625-750 kVA Module, 6-Pulse Installation Drawings Installation Drawings Installation Drawings Base Mounting Patterns SCCT, 3000 Amps Base Mounting Patterns SCCT, 4000 Amps Installation Drawings Installation Drawings Installation Drawings Terminal Details, 500 kVA Module, 6-Pulse Rectifier Terminal Details, 500 kVA Module, 12-Pulse Rectifier Installation Drawings Installation Drawings Installation Drawings Control Connection Location, 500 kVA Modules Control Connection Location Diagram, 625 & 750 kVA Modules Control Connection Location Diagram, Sccc & Scci Control Connection Location Diagram, Scct Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Internal Modem Installation Drawings Installation Drawings Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface External Interconnections, Module 1/SCC, Cable Groups 21 External Interconnections, Module 2/SCC, Cable Groups 21 Wiring Configurations, UPS Video Display Terminal Installation Drawings Installation Drawings Remote Status Panel, Surface Mount Circuit Breaker Schedule, Multi-Module UPS, 300-750 kVA Installation Drawings Installation Drawings Appendix a Site Planning Data 500-750kVA Multi-Module SystemsSeries 600T Multi-Module Systems, 500-750 kVA 480 Volt Input Series 600T Multi-Module Systems, 500-750 kVA 600 Volt Input Appendix B Field Supplied Lugs One-Hole LugsAppendix B Field Supplied Lugs Series 600T UPS