7.4Grounding Configurations, Battery Systems

Figure 6 Battery Cabinet Grounding Configuration

Large, open-rack battery systems are normally either locally grounded or left ungrounded, depending on local code requirements.

Battery cabinet systems, on the other hand, should be grounded to the UPS module ground bus. The figure above illustrates how a simple one-cabinet system would be grounded. For systems with multiple cabinets, the same configuration would apply. However, for simplicity the installer can connect all the battery cabinet grounds for a particular module together and run a single ground conductor to that UPS module ground.

18 Configuring Your Neutral and Ground Connections

Image 24
Contents Power Protection Series 600T UPSArning Hazard Table of Contents Page List of Figures Page Important Safety Instructions Page Safety Precautions Installation Considerations Handling CabinetUPS Multi-Module Unit Block Diagram Types of System Control Cabinets System Control CabinetsUnloading and Handling External Inspections Internal InspectionsInspections Equipment Location Battery Safety Precautions Battery InstallationBattery Installation Battery Installation Matching Battery Cabinets Non-Standard BatteriesConfiguring Your Neutral and Ground Connections Configuring Your Neutral and Ground Connections Grounding Configuration with Ungrounded Delta Source Input Preferred Grounding Configuration with Power-Tie Switchgear Preferred Grounding Configuration, Power-Tie SystemsGrounding Configurations, Battery Systems Battery Cabinet Grounding ConfigurationWiring Considerations Power Wiring Control Wiring Battery Wiring EquipmentScct Scci / Sccc BFB BIB CB1 CB2 MBB MBD Mbfb MIB RIB SBB SBS For Battery Cabinets Wiring Inspection Power Wiring Terminals Factory SuppliedCopper Aluminum or Copper-Clad Aluminum Installation Drawings Outline Drawing, 500 kVA Multi-Module UPS, 6-Pulse RectifierInstallation Drawings Installation Drawings Installation Drawings Outline Drawing, System Control Cabinet SCCT, 200-1200 Amps Outline Drawing, System Control Cabinet SCCT, 1600-2500 Amps Outline Drawing, System Control Cabinet SCCT, 3000 Amps Outline Drawing, System Control Cabinet Scct 4000 Amps Battery Power Pack, Size a Battery Power Pack, Size B Battery Power Pack, Three-Pack System Base Mounting Patterns, 500 kVA Module, 12-Pulse Rectifier Base Mounting Patterns, 625-750 kVA Module, 6-Pulse Installation Drawings Installation Drawings Installation Drawings Base Mounting Patterns SCCT, 3000 Amps Base Mounting Patterns SCCT, 4000 Amps Installation Drawings Installation Drawings Installation Drawings Terminal Details, 500 kVA Module, 6-Pulse Rectifier Terminal Details, 500 kVA Module, 12-Pulse Rectifier Installation Drawings Installation Drawings Installation Drawings Control Connection Location, 500 kVA Modules Control Connection Location Diagram, 625 & 750 kVA Modules Control Connection Location Diagram, Sccc & Scci Control Connection Location Diagram, Scct Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Internal Modem Installation Drawings Installation Drawings Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface External Interconnections, Module 1/SCC, Cable Groups 21 External Interconnections, Module 2/SCC, Cable Groups 21 Wiring Configurations, UPS Video Display Terminal Installation Drawings Installation Drawings Remote Status Panel, Surface Mount Circuit Breaker Schedule, Multi-Module UPS, 300-750 kVA Installation Drawings Installation Drawings Appendix a Site Planning Data 500-750kVA Multi-Module SystemsSeries 600T Multi-Module Systems, 500-750 kVA 480 Volt Input Series 600T Multi-Module Systems, 500-750 kVA 600 Volt Input Appendix B Field Supplied Lugs One-Hole LugsAppendix B Field Supplied Lugs Series 600T UPS