Liebert 600TTM installation manual Important Safety Instructions

Page 7

IMPORTANT SAFETY INSTRUCTIONS

Save These Instructions.

This manual contains important instructions that should be followed during installation of your Series 600T UPS and batteries.

 

WARNING

!

EXERCISE EXTREME CARE WHEN HANDLING UPS CABINETS

TO AVOID EQUIPMENT DAMAGE OR INJURY TO PERSONNEL.

THE UPS MODULE WEIGHT RANGES UP TO 12,000 POUNDS

(5,455 KG), INCLUDING INPUT TRANSFORMER. THE BATTERY

CABINETS WEIGH BETWEEN 3000 POUNDS (1364 KG) AND 4900

POUNDS (2227 KG).

LOCATE CENTER OF GRAVITY SYMBOLS BEFORE HANDLING

EACH CABINET. TEST LIFT AND BALANCE THE CABINETS

BEFORE TRANSPORTING. MAINTAIN MINIMUM TILT FROM

VERTICAL AT ALL TIMES.

SLOTS AT THE BASE OF THE MODULES AND BATTERY

CABINETS ARE INTENDED FOR FORKLIFT USE. BASE SLOTS

WILL SUPPORT THE UNIT ONLY IF THE FORKS ARE

COMPLETELY BENEATH THE UNIT.

SYSTEM CONTROL CABINETS (SCC’S) HAVE HOLES

INTENDED FOR RIGGING BARS OR CHAINS. PREVENT

CHAINS OR CABLES FROM CONTACTING CABINET BY USING

SPREADER BAR AND ADEQUATE PADDING.

FOLLOW ALL BATTERY SAFETY PRECAUTIONS WHEN

 

INSTALLING, CHARGING, OR SERVICING BATTERIES. IN

 

ADDITION TO THE HAZARD OF ELECTRIC SHOCK, GAS

 

PRODUCED BY BATTERIES CAN BE EXPLOSIVE AND

 

SULFURIC ACID CAN CAUSE SEVERE BURNS.

 

IN CASE OF FIRE INVOLVING ELECTRICAL EQUIPMENT,

 

ONLY CARBON DIOXIDE FIRE EXTINGUISHERS, OR THOSE

 

APPROVED FOR USE IN ELECTRICAL FIRE FIGHTING,

 

SHOULD BE USED.

 

EXTREME CAUTION IS REQUIRED WHEN PERFORMING

 

MAINTENANCE.

 

BE CONSTANTLY AWARE THAT THE UPS SYSTEM CONTAINS

 

HIGH DC AS WELL AS AC VOLTAGES.

 

CHECK FOR VOLTAGE WITH BOTH AC AND DC VOLTMETERS

 

PRIOR TO MAKING CONTACT.

1

Image 7
Contents Series 600T UPS Power ProtectionArning Hazard Table of Contents Page List of Figures Page Important Safety Instructions Page Safety Precautions Handling Cabinet Installation ConsiderationsUPS Multi-Module Unit Block Diagram System Control Cabinets Types of System Control CabinetsUnloading and Handling Internal Inspections External InspectionsInspections Equipment Location Battery Installation Battery Safety PrecautionsBattery Installation Battery Installation Non-Standard Batteries Matching Battery CabinetsConfiguring Your Neutral and Ground Connections Configuring Your Neutral and Ground Connections Grounding Configuration with Ungrounded Delta Source Input Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration with Power-Tie SwitchgearBattery Cabinet Grounding Configuration Grounding Configurations, Battery SystemsWiring Considerations Power Wiring Control Wiring Equipment Battery WiringScct Scci / Sccc BFB BIB CB1 CB2 MBB MBD Mbfb MIB RIB SBB SBS For Battery Cabinets Power Wiring Terminals Factory Supplied Wiring InspectionCopper Aluminum or Copper-Clad Aluminum Outline Drawing, 500 kVA Multi-Module UPS, 6-Pulse Rectifier Installation DrawingsInstallation Drawings Installation Drawings Installation Drawings Outline Drawing, System Control Cabinet SCCT, 200-1200 Amps Outline Drawing, System Control Cabinet SCCT, 1600-2500 Amps Outline Drawing, System Control Cabinet SCCT, 3000 Amps Outline Drawing, System Control Cabinet Scct 4000 Amps Battery Power Pack, Size a Battery Power Pack, Size B Battery Power Pack, Three-Pack System Base Mounting Patterns, 500 kVA Module, 12-Pulse Rectifier Base Mounting Patterns, 625-750 kVA Module, 6-Pulse Installation Drawings Installation Drawings Installation Drawings Base Mounting Patterns SCCT, 3000 Amps Base Mounting Patterns SCCT, 4000 Amps Installation Drawings Installation Drawings Installation Drawings Terminal Details, 500 kVA Module, 6-Pulse Rectifier Terminal Details, 500 kVA Module, 12-Pulse Rectifier Installation Drawings Installation Drawings Installation Drawings Control Connection Location, 500 kVA Modules Control Connection Location Diagram, 625 & 750 kVA Modules Control Connection Location Diagram, Sccc & Scci Control Connection Location Diagram, Scct Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Internal Modem Installation Drawings Installation Drawings Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface External Interconnections, Module 1/SCC, Cable Groups 21 External Interconnections, Module 2/SCC, Cable Groups 21 Wiring Configurations, UPS Video Display Terminal Installation Drawings Installation Drawings Remote Status Panel, Surface Mount Circuit Breaker Schedule, Multi-Module UPS, 300-750 kVA Installation Drawings Installation Drawings 500-750kVA Multi-Module Systems Appendix a Site Planning DataSeries 600T Multi-Module Systems, 500-750 kVA 480 Volt Input Series 600T Multi-Module Systems, 500-750 kVA 600 Volt Input One-Hole Lugs Appendix B Field Supplied LugsAppendix B Field Supplied Lugs Series 600T UPS