CAUTION
After cutting holes in the access plates, be certain that no foreign matter (metal shavings, sawdust, insulation or wire fragments, etc.) remains inside the UPS. Likewise be certain to block any “extra” holes in the plates through which foreign matter could later enter the UPS.
6. Power cables must be rated for less than 2 volts line drop at maximum rated system current.
7. If site equipment includes a backup generator and automatic transfer switch(es), consult the manufacturers of those devices for information on sizing and interfacing to the UPS system.
8. The installing contractor can remove the access plates from the left and right side of the cable- access area in the top of the UPS in order to cut entry holes for conduit. For units that also have bottom cable access, there is a third access plate on the right side of the module.
An insulated grounding conductor must be sized in accordance with the NEC and local codes. It must be green (with or without one or more yellow stripes) and be installed as part of the branch circuit that supplies the unit or system.
The grounding conductor described above is to be grounded to earth at the service equipment or, if supplied by a separately derived system, at the supply transformer or motor-generator set in accordance with the instructions in Section 7 of this Manual. The attachment-plug receptacles in the vicinity of the unit or system are all to be of a grounding type, and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment.
Power and control wiring must be separated!
CAUTION

8.1Power Wiring

1.Power wiring must be run in individual, separate conduits or cable trays. Refer to the Outline and Terminal Details drawings (Figure 8 to Figure 15 and Figure 29 to Figure 32) for locations of the various power connections within the UPS and SCC. In particular, note the location of the rectifier input power connections.

2. !Observe local, state and national electrical codes. Verify utility power and its overcurrent protection rating will accommodate the UPS input rating, including battery recharging.

3. A safety ground wire must be run from building ground to ground point in the UPS Module Cabinets, the System Control Cabinet, and the Power-Tie Cabinet (if applicable). See Sections 7.1 through 7.4. The grounding conductor shall comply with the following conditions of installation:

a.

b.

c.

4. When possible, input to the UPS and bypass should be four wire plus ground. When input is straight delta, the UPS artificial neutral kit should be ordered. When input is corner- grounded delta, the isolated neutral kit should be ordered.

5. Observe clockwise phase rotation of all power wiring. Phase A leads Phase B leads Phase C. A qualified electrician should check the phase rotation.

!

20 Wiring Considerations

Image 26
Contents Power Protection Series 600T UPSArning Hazard Table of Contents Page List of Figures Page Important Safety Instructions Page Safety Precautions Installation Considerations Handling CabinetUPS Multi-Module Unit Block Diagram Types of System Control Cabinets System Control CabinetsUnloading and Handling Inspections External InspectionsInternal Inspections Equipment Location Battery Safety Precautions Battery InstallationBattery Installation Battery Installation Matching Battery Cabinets Non-Standard BatteriesConfiguring Your Neutral and Ground Connections Configuring Your Neutral and Ground Connections Grounding Configuration with Ungrounded Delta Source Input Preferred Grounding Configuration with Power-Tie Switchgear Preferred Grounding Configuration, Power-Tie SystemsGrounding Configurations, Battery Systems Battery Cabinet Grounding ConfigurationWiring Considerations Power Wiring Control Wiring Battery Wiring EquipmentScct Scci / Sccc BFB BIB CB1 CB2 MBB MBD Mbfb MIB RIB SBB SBS For Battery Cabinets Wiring Inspection Power Wiring Terminals Factory SuppliedCopper Aluminum or Copper-Clad Aluminum Installation Drawings Outline Drawing, 500 kVA Multi-Module UPS, 6-Pulse RectifierInstallation Drawings Installation Drawings Installation Drawings Outline Drawing, System Control Cabinet SCCT, 200-1200 Amps Outline Drawing, System Control Cabinet SCCT, 1600-2500 Amps Outline Drawing, System Control Cabinet SCCT, 3000 Amps Outline Drawing, System Control Cabinet Scct 4000 Amps Battery Power Pack, Size a Battery Power Pack, Size B Battery Power Pack, Three-Pack System Base Mounting Patterns, 500 kVA Module, 12-Pulse Rectifier Base Mounting Patterns, 625-750 kVA Module, 6-Pulse Installation Drawings Installation Drawings Installation Drawings Base Mounting Patterns SCCT, 3000 Amps Base Mounting Patterns SCCT, 4000 Amps Installation Drawings Installation Drawings Installation Drawings Terminal Details, 500 kVA Module, 6-Pulse Rectifier Terminal Details, 500 kVA Module, 12-Pulse Rectifier Installation Drawings Installation Drawings Installation Drawings Control Connection Location, 500 kVA Modules Control Connection Location Diagram, 625 & 750 kVA Modules Control Connection Location Diagram, Sccc & Scci Control Connection Location Diagram, Scct Installation Drawings Installation Drawings Installation Drawings Installation Drawings Installation Drawings Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Internal Modem Installation Drawings Installation Drawings Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface External Interconnections, Module 1/SCC, Cable Groups 21 External Interconnections, Module 2/SCC, Cable Groups 21 Wiring Configurations, UPS Video Display Terminal Installation Drawings Installation Drawings Remote Status Panel, Surface Mount Circuit Breaker Schedule, Multi-Module UPS, 300-750 kVA Installation Drawings Installation Drawings Appendix a Site Planning Data 500-750kVA Multi-Module SystemsSeries 600T Multi-Module Systems, 500-750 kVA 480 Volt Input Series 600T Multi-Module Systems, 500-750 kVA 600 Volt Input Appendix B Field Supplied Lugs One-Hole LugsAppendix B Field Supplied Lugs Series 600T UPS